The New Adaptive Protection Method for the Compensated Transmission Lines with the Series Capacitor in a High Share of Wind Energy Resources by Using PMU Data
{"title":"The New Adaptive Protection Method for the Compensated Transmission Lines with the Series Capacitor in a High Share of Wind Energy Resources by Using PMU Data","authors":"Mohammad Mostafa Keramat, Mohammad Hosein Fazaeli","doi":"10.1109/IWEC52400.2021.9466998","DOIUrl":null,"url":null,"abstract":"Nowadays, using renewable energy sources ignited plays an essential role in the power system grid. Although using wind energy as a renewable energy source has some benefits, such as higher performance over other renewable energy sources, it has opened new field power system protection for this power grid type. Wind power plants in a contingency situation such as short circuit fault in the power grid may disconnect from the power grid and make the situation worse for the dynamic stability of the power system.Low Voltage Ride-Through (LVRT) has proposed by Wind Energy Conversion Systems (WECS). A mismatch will be acquired during a voltage drop across the grid between the wind generator's active power and those delivered to the power grid. Constant speed wind generators are highly dependent on reactive power, so they require much reactive power in a short circuit failure; otherwise, they become unstable and must be disconnected from the power system. On the other hand, some proposed method to provide reactive power to wind generators might negatively affect distance protection, especially in the lines equipped by series capacitors. Besides, Proper protection of high voltage transmission lines equipped with series compensation has ignited some challenges for distance power system protection; these challenges are caused due to some factors such as the influence of the series capacitor on the fault ring and the variation of the impedance, the failure to detect the direction of the fault due to changes of angle and the measurement of phase voltage, transient fluctuations caused by low current errors as well as switching.On the other hand, the fault location in a transformer compensated transmission line is complicated by the series capacitor due to the MOV and complex transient conditions. Therefore, it is necessary to investigate methods to improve transmission lines' distance protection (as the most common conservation in lines), and research has been done in this regard. In this paper, a proposed scheme based on phasor measurement data from PMU on both sides of the line this method calculate the percentage of compensation in real-time mode, and the setting of second and third relay zones will be minimized depending on the conditions for recovery and improper performance of distance protection. To assess the accuracy of the proposed method, IEEE 39-BUS is employed. Proper performance of protection areas obtained in fault conditions using this scheme indicates the accuracy of the proposed method all of the numeric calculation has been done in Digsilent Power factory software","PeriodicalId":281528,"journal":{"name":"7th Iran Wind Energy Conference (IWEC2021)","volume":"25 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2021-05-17","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"5","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"7th Iran Wind Energy Conference (IWEC2021)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/IWEC52400.2021.9466998","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 5
Abstract
Nowadays, using renewable energy sources ignited plays an essential role in the power system grid. Although using wind energy as a renewable energy source has some benefits, such as higher performance over other renewable energy sources, it has opened new field power system protection for this power grid type. Wind power plants in a contingency situation such as short circuit fault in the power grid may disconnect from the power grid and make the situation worse for the dynamic stability of the power system.Low Voltage Ride-Through (LVRT) has proposed by Wind Energy Conversion Systems (WECS). A mismatch will be acquired during a voltage drop across the grid between the wind generator's active power and those delivered to the power grid. Constant speed wind generators are highly dependent on reactive power, so they require much reactive power in a short circuit failure; otherwise, they become unstable and must be disconnected from the power system. On the other hand, some proposed method to provide reactive power to wind generators might negatively affect distance protection, especially in the lines equipped by series capacitors. Besides, Proper protection of high voltage transmission lines equipped with series compensation has ignited some challenges for distance power system protection; these challenges are caused due to some factors such as the influence of the series capacitor on the fault ring and the variation of the impedance, the failure to detect the direction of the fault due to changes of angle and the measurement of phase voltage, transient fluctuations caused by low current errors as well as switching.On the other hand, the fault location in a transformer compensated transmission line is complicated by the series capacitor due to the MOV and complex transient conditions. Therefore, it is necessary to investigate methods to improve transmission lines' distance protection (as the most common conservation in lines), and research has been done in this regard. In this paper, a proposed scheme based on phasor measurement data from PMU on both sides of the line this method calculate the percentage of compensation in real-time mode, and the setting of second and third relay zones will be minimized depending on the conditions for recovery and improper performance of distance protection. To assess the accuracy of the proposed method, IEEE 39-BUS is employed. Proper performance of protection areas obtained in fault conditions using this scheme indicates the accuracy of the proposed method all of the numeric calculation has been done in Digsilent Power factory software
目前,利用可再生能源点燃电网在电力系统中起着至关重要的作用。虽然风能作为一种可再生能源具有一些优势,例如比其他可再生能源性能更高,但它为这种电网类型开辟了新的现场电力系统保护。风电场在电网发生短路故障等突发情况时,可能会脱离电网,对电力系统的动态稳定性造成不利影响。低电压穿越(LVRT)是由风能转换系统(WECS)提出的。在风力发电机的有功功率和输送到电网的有功功率之间的电网电压下降期间,将获得不匹配。恒速风力发电机对无功的依赖程度高,在短路故障时需要大量的无功功率;否则,它们会变得不稳定,必须与电力系统断开。另一方面,一些提出的向风力发电机提供无功功率的方法可能会对距离保护产生负面影响,特别是在配备串联电容器的线路中。此外,采用串联补偿的高压输电线路的合理保护给远距离电力系统保护带来了一些挑战;这些挑战是由于串联电容对故障环的影响和阻抗的变化,由于角度变化和相电压测量导致故障方向检测失败,小电流误差引起的瞬态波动以及开关等因素造成的。另一方面,由于MOV和复杂的暂态条件,串联电容使变压器补偿输电线路的故障定位变得复杂。因此,有必要研究如何提高输电线路的距离保护(这是线路中最常见的保护),并在这方面进行了研究。本文提出了一种基于线路两侧PMU相量测量数据的方案,该方案在实时模式下计算补偿百分比,并根据恢复条件和距离保护性能不合理将第二和第三继电区设置最小化。为了评估所提出方法的准确性,采用了IEEE 39-BUS。该方案在故障条件下获得的保护区域性能良好,表明了该方法的准确性,并在Digsilent Power factory软件中进行了数值计算