{"title":"PLN机组- jbt DGA试验中典型瓦斯浓度值和典型瓦斯增幅","authors":"H. Gumilang","doi":"10.1109/ICHVEPS47643.2019.9011005","DOIUrl":null,"url":null,"abstract":"Since more than 15 years ago, PLN had been using DGA to determine the condition of power transformers whether it is experience arcing, thermal or corona. PLN UIT-JBT applying DGA every semester on 448 units of power transformers which have several rating voltages i.e. 500/150kV, 150/70kV, 150/20kV and 70/20kV. In order to understand what should PLN do to the power transformer based on DGA test, some standards are used as reference to do further action which are IEC 60599 and IEEE C57-104. IEC 60599 recommend any electricity utilities that had a huge number of DGA result to generate typical gas concentration values and typical rate of gas increase as an internal standard to decide which transformer are defined to be normal in operation or abnormal in operation so will be easier for utility to plan a further treatment to the transformers. This paper eventually will describe the comparison of typical normal boundaries of gas value on IEC, IEEE and PLN typical data. Typical rate of gas increase that been calculated can also be used as a reference to determine which power transformer had severe internal faults. Both typical gas concentration values and typical rate of gas increase using 90% of test data population as a range of normal operation, while the other 10% considered as abnormal operation. From the comparison among IEEE, IEC and PLN typical data it was known that the typical values for normal condition are almost at the same level, but only C2H2 gas where IEC value have the highest which is 20 ppm. In the end by creating a new reference to interpret DGA test result using our own data’s, which it is came from our system, whether it is on typical gas concentration values or typical rate of gas increase, we could have more confidence and higher accuracy to understand what is actually happened on our power transformers.","PeriodicalId":6677,"journal":{"name":"2019 2nd International Conference on High Voltage Engineering and Power Systems (ICHVEPS)","volume":"49 1","pages":"1-5"},"PeriodicalIF":0.0000,"publicationDate":"2019-10-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"2","resultStr":"{\"title\":\"Typical Gas Concentration Values and Typical Rate of Gas Increase on DGA Test in PLN UIT-JBT\",\"authors\":\"H. Gumilang\",\"doi\":\"10.1109/ICHVEPS47643.2019.9011005\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Since more than 15 years ago, PLN had been using DGA to determine the condition of power transformers whether it is experience arcing, thermal or corona. PLN UIT-JBT applying DGA every semester on 448 units of power transformers which have several rating voltages i.e. 500/150kV, 150/70kV, 150/20kV and 70/20kV. In order to understand what should PLN do to the power transformer based on DGA test, some standards are used as reference to do further action which are IEC 60599 and IEEE C57-104. IEC 60599 recommend any electricity utilities that had a huge number of DGA result to generate typical gas concentration values and typical rate of gas increase as an internal standard to decide which transformer are defined to be normal in operation or abnormal in operation so will be easier for utility to plan a further treatment to the transformers. This paper eventually will describe the comparison of typical normal boundaries of gas value on IEC, IEEE and PLN typical data. Typical rate of gas increase that been calculated can also be used as a reference to determine which power transformer had severe internal faults. Both typical gas concentration values and typical rate of gas increase using 90% of test data population as a range of normal operation, while the other 10% considered as abnormal operation. From the comparison among IEEE, IEC and PLN typical data it was known that the typical values for normal condition are almost at the same level, but only C2H2 gas where IEC value have the highest which is 20 ppm. In the end by creating a new reference to interpret DGA test result using our own data’s, which it is came from our system, whether it is on typical gas concentration values or typical rate of gas increase, we could have more confidence and higher accuracy to understand what is actually happened on our power transformers.\",\"PeriodicalId\":6677,\"journal\":{\"name\":\"2019 2nd International Conference on High Voltage Engineering and Power Systems (ICHVEPS)\",\"volume\":\"49 1\",\"pages\":\"1-5\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2019-10-01\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"2\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2019 2nd International Conference on High Voltage Engineering and Power Systems (ICHVEPS)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/ICHVEPS47643.2019.9011005\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2019 2nd International Conference on High Voltage Engineering and Power Systems (ICHVEPS)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ICHVEPS47643.2019.9011005","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 2
摘要
自15年前以来,PLN一直在使用DGA来确定电力变压器的状态,无论是经历电弧,热还是电晕。PLN unit - jbt每学期对额定电压为500/150kV、150/70kV、150/20kV、70/20kV的448台电力变压器应用DGA。为了了解基于DGA测试的电力变压器PLN应该做些什么,参考IEC 60599和IEEE C57-104标准来做进一步的工作。IEC 60599建议任何有大量DGA结果的电力公司产生典型的气体浓度值和典型的气体增长率作为内部标准,以确定哪些变压器被定义为正常运行或异常运行,以便公用事业公司更容易计划对变压器的进一步处理。本文最后将描述IEC、IEEE和PLN典型数据上气值的典型法向边界的比较。计算出的典型气体增加率也可作为判断哪些电力变压器存在严重内部故障的参考。典型气体浓度值和典型气体增长率均采用90%的测试数据集作为正常操作范围,其余10%作为异常操作范围。从IEEE、IEC和PLN的典型数据比较可知,正常情况下的典型值几乎相同,但只有C2H2气体的IEC值最高,为20 ppm。最后,通过建立一个新的参考来解释DGA测试结果,无论是典型的气体浓度值还是典型的气体增长速率,我们都可以更有信心和更高的准确性来了解我们的电力变压器实际发生了什么。
Typical Gas Concentration Values and Typical Rate of Gas Increase on DGA Test in PLN UIT-JBT
Since more than 15 years ago, PLN had been using DGA to determine the condition of power transformers whether it is experience arcing, thermal or corona. PLN UIT-JBT applying DGA every semester on 448 units of power transformers which have several rating voltages i.e. 500/150kV, 150/70kV, 150/20kV and 70/20kV. In order to understand what should PLN do to the power transformer based on DGA test, some standards are used as reference to do further action which are IEC 60599 and IEEE C57-104. IEC 60599 recommend any electricity utilities that had a huge number of DGA result to generate typical gas concentration values and typical rate of gas increase as an internal standard to decide which transformer are defined to be normal in operation or abnormal in operation so will be easier for utility to plan a further treatment to the transformers. This paper eventually will describe the comparison of typical normal boundaries of gas value on IEC, IEEE and PLN typical data. Typical rate of gas increase that been calculated can also be used as a reference to determine which power transformer had severe internal faults. Both typical gas concentration values and typical rate of gas increase using 90% of test data population as a range of normal operation, while the other 10% considered as abnormal operation. From the comparison among IEEE, IEC and PLN typical data it was known that the typical values for normal condition are almost at the same level, but only C2H2 gas where IEC value have the highest which is 20 ppm. In the end by creating a new reference to interpret DGA test result using our own data’s, which it is came from our system, whether it is on typical gas concentration values or typical rate of gas increase, we could have more confidence and higher accuracy to understand what is actually happened on our power transformers.