受损混凝土结构的加固——以达累斯萨拉姆11层建筑为例

J. Makunza
{"title":"受损混凝土结构的加固——以达累斯萨拉姆11层建筑为例","authors":"J. Makunza","doi":"10.4028/p-2b38z4","DOIUrl":null,"url":null,"abstract":"Concrete structures may become obsolete and be unfit for use to the extent that they need special attendance of repair or strengthening so as to revive them. The weakness in the buildings may be caused by natural disasters like earthquake, floods, changes of use of the buildings in which higher loads more than the design loads, e.g. vertical extension loads, are applied. When the structures are defective they need to be strengthened in order to restore their original structural integrity. Sometimes, the defect or deterioration needs to be scientifically analysed first in order to know the root cause of the problem and apply the right corrective measures. A case study on an eleven stories damaged building in is presented, starting with an investigation on causes of sudden crushing of one column and a strengthening method which embraced a number of techniques such as Land Surveying and non-destructive tests in assessing the building structural integrity. The crushed column and other columns is the ground floor were all strengthened using jacketing method and provision of additional columns at the crushed column. Keywords: Columns, crushing, non-destructive tests, concrete quality, deflection, plumb, jacketing, strengthening","PeriodicalId":34329,"journal":{"name":"Journal of Electrical and Computer Engineering Innovations","volume":"229 1","pages":"1 - 13"},"PeriodicalIF":0.0000,"publicationDate":"2023-04-19","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Strengthening of a Damaged Concrete Structure - Case Study of an Eleven Stories Building in Dar es Salaam\",\"authors\":\"J. Makunza\",\"doi\":\"10.4028/p-2b38z4\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Concrete structures may become obsolete and be unfit for use to the extent that they need special attendance of repair or strengthening so as to revive them. The weakness in the buildings may be caused by natural disasters like earthquake, floods, changes of use of the buildings in which higher loads more than the design loads, e.g. vertical extension loads, are applied. When the structures are defective they need to be strengthened in order to restore their original structural integrity. Sometimes, the defect or deterioration needs to be scientifically analysed first in order to know the root cause of the problem and apply the right corrective measures. A case study on an eleven stories damaged building in is presented, starting with an investigation on causes of sudden crushing of one column and a strengthening method which embraced a number of techniques such as Land Surveying and non-destructive tests in assessing the building structural integrity. The crushed column and other columns is the ground floor were all strengthened using jacketing method and provision of additional columns at the crushed column. Keywords: Columns, crushing, non-destructive tests, concrete quality, deflection, plumb, jacketing, strengthening\",\"PeriodicalId\":34329,\"journal\":{\"name\":\"Journal of Electrical and Computer Engineering Innovations\",\"volume\":\"229 1\",\"pages\":\"1 - 13\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2023-04-19\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Journal of Electrical and Computer Engineering Innovations\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.4028/p-2b38z4\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Journal of Electrical and Computer Engineering Innovations","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.4028/p-2b38z4","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

混凝土结构可能会过时,不适合使用,需要特别维修或加强,以使其恢复活力。建筑物的弱点可能是由地震、洪水等自然灾害造成的,也可能是由于建筑物的使用方式发生变化,其中施加的荷载高于设计荷载,例如竖向延伸荷载。当结构有缺陷时,需要对其进行加固,以恢复其原有的结构完整性。有时,为了了解问题的根本原因并采取正确的纠正措施,需要首先对缺陷或劣化进行科学分析。本文以一幢11层楼高的建筑物为例,首先分析了一根柱子突然破碎的原因,并提出了一种采用土地测量和无损检测等多种技术来评估建筑物结构完整性的加固方法。破碎柱及底层其他柱均采用夹套法加固,破碎柱处加设附加柱。关键词:柱,破碎,无损检测,混凝土质量,挠度,铅锤,护套,加固
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Strengthening of a Damaged Concrete Structure - Case Study of an Eleven Stories Building in Dar es Salaam
Concrete structures may become obsolete and be unfit for use to the extent that they need special attendance of repair or strengthening so as to revive them. The weakness in the buildings may be caused by natural disasters like earthquake, floods, changes of use of the buildings in which higher loads more than the design loads, e.g. vertical extension loads, are applied. When the structures are defective they need to be strengthened in order to restore their original structural integrity. Sometimes, the defect or deterioration needs to be scientifically analysed first in order to know the root cause of the problem and apply the right corrective measures. A case study on an eleven stories damaged building in is presented, starting with an investigation on causes of sudden crushing of one column and a strengthening method which embraced a number of techniques such as Land Surveying and non-destructive tests in assessing the building structural integrity. The crushed column and other columns is the ground floor were all strengthened using jacketing method and provision of additional columns at the crushed column. Keywords: Columns, crushing, non-destructive tests, concrete quality, deflection, plumb, jacketing, strengthening
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
审稿时长
12 weeks
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信