{"title":"通过对真实的现场状态评估数据库的综合分析,确定了电力变压器绝缘平均温度的系统误差","authors":"Miha Bečan, I. Kobal, Jalen Stremfelj, M. Babuder, Boris Zupanc","doi":"10.1109/ICDL.2014.6893175","DOIUrl":null,"url":null,"abstract":"The paper describes an analytical approach adopted to improve the insulation condition evaluation procedure. Electrical testing of power transformer insulation may provide reliable information about its state and aging grade. Inconveniently, the majority of dielectric parameters used in this evaluation are temperature dependent; hence, the accurate measurement of the temperature is decisive for the final assessment result. The on-site tested transformers are usually put off operation and disconnected few hours before the tests initiate and are still slowly cooling down during testing. Non stable average insulation temperature may lead to a considerable systematic measuring error. Aiming to avoid this, an authentic several years collected database was taken and a suitable emendation method applied.","PeriodicalId":6523,"journal":{"name":"2014 IEEE 18th International Conference on Dielectric Liquids (ICDL)","volume":"100 2 1","pages":"1-4"},"PeriodicalIF":0.0000,"publicationDate":"2014-09-08","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"The identification of systematic error in determining the average temperature of power transformer insulation obtained by comprehensive analysis of an authentic on-site condition assessment database\",\"authors\":\"Miha Bečan, I. Kobal, Jalen Stremfelj, M. Babuder, Boris Zupanc\",\"doi\":\"10.1109/ICDL.2014.6893175\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"The paper describes an analytical approach adopted to improve the insulation condition evaluation procedure. Electrical testing of power transformer insulation may provide reliable information about its state and aging grade. Inconveniently, the majority of dielectric parameters used in this evaluation are temperature dependent; hence, the accurate measurement of the temperature is decisive for the final assessment result. The on-site tested transformers are usually put off operation and disconnected few hours before the tests initiate and are still slowly cooling down during testing. Non stable average insulation temperature may lead to a considerable systematic measuring error. Aiming to avoid this, an authentic several years collected database was taken and a suitable emendation method applied.\",\"PeriodicalId\":6523,\"journal\":{\"name\":\"2014 IEEE 18th International Conference on Dielectric Liquids (ICDL)\",\"volume\":\"100 2 1\",\"pages\":\"1-4\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2014-09-08\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2014 IEEE 18th International Conference on Dielectric Liquids (ICDL)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/ICDL.2014.6893175\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2014 IEEE 18th International Conference on Dielectric Liquids (ICDL)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ICDL.2014.6893175","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

本文介绍了一种改进绝缘状态评定程序的分析方法。电力变压器绝缘的电气试验可以提供有关绝缘状态和老化等级的可靠信息。不方便的是,在此评估中使用的大多数介电参数都依赖于温度;因此,温度的准确测量对最终的评估结果是决定性的。现场测试的变压器通常在测试开始前几个小时停止运行并断开,并且在测试期间仍在缓慢冷却。不稳定的平均绝缘温度会导致相当大的系统测量误差。为了避免这种情况的发生,本文采用了一个真实的多年收集的数据库,并采用了适当的修正方法。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
The identification of systematic error in determining the average temperature of power transformer insulation obtained by comprehensive analysis of an authentic on-site condition assessment database
The paper describes an analytical approach adopted to improve the insulation condition evaluation procedure. Electrical testing of power transformer insulation may provide reliable information about its state and aging grade. Inconveniently, the majority of dielectric parameters used in this evaluation are temperature dependent; hence, the accurate measurement of the temperature is decisive for the final assessment result. The on-site tested transformers are usually put off operation and disconnected few hours before the tests initiate and are still slowly cooling down during testing. Non stable average insulation temperature may lead to a considerable systematic measuring error. Aiming to avoid this, an authentic several years collected database was taken and a suitable emendation method applied.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信