300kw分布式发电并网配电系统潮流及短路分析

Muhardika Muhardika, Syahroni Syahroni
{"title":"300kw分布式发电并网配电系统潮流及短路分析","authors":"Muhardika Muhardika, Syahroni Syahroni","doi":"10.25077/AIJASET.V1I1.3","DOIUrl":null,"url":null,"abstract":"Power flow analysis aims to determine the capacity of a generator to serve loads, to know the value of power losses in the electrical system, and to carry out a planning and development of the electric power system. Power flow analysis is carried out in order to find out the characteristics of the electric power system to be built or to be developed as desired. In this study, power flow analysis and short circuit analysis were carried out in the electrical system of Andalas University with 2 conditions, namely, when the conditions were normal or when the Distributed Generation was not added and when the conditions were added, the Distributed Generation (DG) Photovoltaic 300 kW. The results of this study indicate the largest system losses when normal conditions are on bus 1 to bus 2 amounting to 20.21 kW and 6.13 kVar, and when conditions add DG on bus 17 to bus 18 are 230.8 kW and 142.7 kVar. The results of the short circuit analysis of the two conditions are on bus 1 when the condition is experiencing the addition of DG with an increase in average current, namely 1 soil phase of 0.86 kA, 2 phases of 0.175 kA, 2 soil phases of 0.09609 kA, and 3 phases of 0.085273 kA from when the conditions were normal.\nKeywords : Power Flow Analysis, Short Circuit Analysis, Photovoltaic, Wind Turbine","PeriodicalId":7884,"journal":{"name":"Andalasian International Journal of Applied Science, Engineering and Technology","volume":"17 1","pages":""},"PeriodicalIF":0.0000,"publicationDate":"2021-05-18","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Power Flow and Short Circuit Analysis of Distribution System with 300 kW Distributed Generation Connected\",\"authors\":\"Muhardika Muhardika, Syahroni Syahroni\",\"doi\":\"10.25077/AIJASET.V1I1.3\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Power flow analysis aims to determine the capacity of a generator to serve loads, to know the value of power losses in the electrical system, and to carry out a planning and development of the electric power system. Power flow analysis is carried out in order to find out the characteristics of the electric power system to be built or to be developed as desired. In this study, power flow analysis and short circuit analysis were carried out in the electrical system of Andalas University with 2 conditions, namely, when the conditions were normal or when the Distributed Generation was not added and when the conditions were added, the Distributed Generation (DG) Photovoltaic 300 kW. The results of this study indicate the largest system losses when normal conditions are on bus 1 to bus 2 amounting to 20.21 kW and 6.13 kVar, and when conditions add DG on bus 17 to bus 18 are 230.8 kW and 142.7 kVar. The results of the short circuit analysis of the two conditions are on bus 1 when the condition is experiencing the addition of DG with an increase in average current, namely 1 soil phase of 0.86 kA, 2 phases of 0.175 kA, 2 soil phases of 0.09609 kA, and 3 phases of 0.085273 kA from when the conditions were normal.\\nKeywords : Power Flow Analysis, Short Circuit Analysis, Photovoltaic, Wind Turbine\",\"PeriodicalId\":7884,\"journal\":{\"name\":\"Andalasian International Journal of Applied Science, Engineering and Technology\",\"volume\":\"17 1\",\"pages\":\"\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2021-05-18\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Andalasian International Journal of Applied Science, Engineering and Technology\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.25077/AIJASET.V1I1.3\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Andalasian International Journal of Applied Science, Engineering and Technology","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.25077/AIJASET.V1I1.3","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

潮流分析的目的是确定发电机服务负荷的能力,了解电力系统的功率损耗值,对电力系统进行规划和发展。进行潮流分析是为了了解将要建设或将要开发的电力系统的特性。在本研究中,对Andalas大学电气系统进行了功率流分析和短路分析,在条件正常和不增加分布式发电时,在条件增加时,分布式发电(DG)光伏300kw。本研究结果表明,母线1至母线2正常工况下系统损耗最大,为20.21 kW和6.13 kVar,母线17至母线18添加DG时系统损耗最大,为230.8 kW和142.7 kVar。两种情况下的短路分析结果在母线1上,分别为1个土壤相0.86 kA, 2个土壤相0.175 kA, 2个土壤相0.09609 kA, 3个土壤相0.085273 kA。关键词:潮流分析,短路分析,光伏发电,风力发电
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Power Flow and Short Circuit Analysis of Distribution System with 300 kW Distributed Generation Connected
Power flow analysis aims to determine the capacity of a generator to serve loads, to know the value of power losses in the electrical system, and to carry out a planning and development of the electric power system. Power flow analysis is carried out in order to find out the characteristics of the electric power system to be built or to be developed as desired. In this study, power flow analysis and short circuit analysis were carried out in the electrical system of Andalas University with 2 conditions, namely, when the conditions were normal or when the Distributed Generation was not added and when the conditions were added, the Distributed Generation (DG) Photovoltaic 300 kW. The results of this study indicate the largest system losses when normal conditions are on bus 1 to bus 2 amounting to 20.21 kW and 6.13 kVar, and when conditions add DG on bus 17 to bus 18 are 230.8 kW and 142.7 kVar. The results of the short circuit analysis of the two conditions are on bus 1 when the condition is experiencing the addition of DG with an increase in average current, namely 1 soil phase of 0.86 kA, 2 phases of 0.175 kA, 2 soil phases of 0.09609 kA, and 3 phases of 0.085273 kA from when the conditions were normal. Keywords : Power Flow Analysis, Short Circuit Analysis, Photovoltaic, Wind Turbine
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信