载流母线偏心和倾斜对大尺寸Rogowski线圈冲击电流测量的影响

Nan-nan Yan, Z. Fu
{"title":"载流母线偏心和倾斜对大尺寸Rogowski线圈冲击电流测量的影响","authors":"Nan-nan Yan, Z. Fu","doi":"10.1109/ICHVE.2012.6357018","DOIUrl":null,"url":null,"abstract":"In order to obtain the waveform of lightning current, the Rogowski coil is installed directly on tall structures such as the UHV transmission line towers. However, the measured results are influenced by the structure involved. This paper investigates the effects of different current-carrying bus positions to the large size Rogowski coil on the measured results. Two different large size coils' frequency spectrum characteristics are analyzed and the effects of coil parameters on frequency band are also discussed. The impact of current-carrying bus decentration and inclination the Rogowski coil measured results is investigated. Both calculation and test strategy study methods are employed for the impact investigation. It is shown that the decentration of current-carrying bus has little impact of less than 4% errors on the measurement results when the current-carrying bus's decentration distance changed from 0 cm to 30 cm. The inclination of the current carrying-bus has more significant impact on the measured results. The error of measured current amplitude changes from 1.17% to 7.4% whilst the inclination angle changes from 0°to 60°under 5kA impulse current, and from 1.5% to 17.9% under 10kA impulse current. The theoretical analysis is in accordance with the experimental results. It is suggested that the Rogowski coil should be located installed perpendicular to the current-carrying bus and the decentration impact is ignorable when the decentration distance is less then 20% of the coil radius.","PeriodicalId":6375,"journal":{"name":"2012 International Conference on High Voltage Engineering and Application","volume":"45 4 1","pages":"166-169"},"PeriodicalIF":0.0000,"publicationDate":"2012-11-26","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"2","resultStr":"{\"title\":\"The impact of current-carrying bus decentration and inclination on impulse current measurement by large size Rogowski coils\",\"authors\":\"Nan-nan Yan, Z. Fu\",\"doi\":\"10.1109/ICHVE.2012.6357018\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"In order to obtain the waveform of lightning current, the Rogowski coil is installed directly on tall structures such as the UHV transmission line towers. However, the measured results are influenced by the structure involved. This paper investigates the effects of different current-carrying bus positions to the large size Rogowski coil on the measured results. Two different large size coils' frequency spectrum characteristics are analyzed and the effects of coil parameters on frequency band are also discussed. The impact of current-carrying bus decentration and inclination the Rogowski coil measured results is investigated. Both calculation and test strategy study methods are employed for the impact investigation. It is shown that the decentration of current-carrying bus has little impact of less than 4% errors on the measurement results when the current-carrying bus's decentration distance changed from 0 cm to 30 cm. The inclination of the current carrying-bus has more significant impact on the measured results. The error of measured current amplitude changes from 1.17% to 7.4% whilst the inclination angle changes from 0°to 60°under 5kA impulse current, and from 1.5% to 17.9% under 10kA impulse current. The theoretical analysis is in accordance with the experimental results. It is suggested that the Rogowski coil should be located installed perpendicular to the current-carrying bus and the decentration impact is ignorable when the decentration distance is less then 20% of the coil radius.\",\"PeriodicalId\":6375,\"journal\":{\"name\":\"2012 International Conference on High Voltage Engineering and Application\",\"volume\":\"45 4 1\",\"pages\":\"166-169\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2012-11-26\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"2\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2012 International Conference on High Voltage Engineering and Application\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/ICHVE.2012.6357018\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2012 International Conference on High Voltage Engineering and Application","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ICHVE.2012.6357018","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 2

摘要

为了获得雷电电流的波形,Rogowski线圈直接安装在特高压输电线路塔等高层结构上。然而,测量结果受到所涉及的结构的影响。本文研究了大尺寸Rogowski线圈不同载流母线位置对测量结果的影响。分析了两种不同大尺寸线圈的频谱特性,讨论了线圈参数对频段的影响。研究了载流母线偏心和倾斜对Rogowski线圈测量结果的影响。冲击研究采用了计算方法和试验策略研究方法。结果表明,当载流母线分散距离从0 cm变化到30 cm时,载流母线分散距离对测量结果的影响不大,误差小于4%。载流母线的倾角对测量结果的影响更为显著。在5kA冲击电流下,当倾角从0°变化到60°时,测得的电流幅值误差从1.17%变化到7.4%,在10kA冲击电流下,测得的电流幅值误差从1.5%变化到17.9%。理论分析与实验结果一致。建议Rogowski线圈垂直于载流母线安装,当分散距离小于线圈半径的20%时,分散影响可以忽略不计。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
The impact of current-carrying bus decentration and inclination on impulse current measurement by large size Rogowski coils
In order to obtain the waveform of lightning current, the Rogowski coil is installed directly on tall structures such as the UHV transmission line towers. However, the measured results are influenced by the structure involved. This paper investigates the effects of different current-carrying bus positions to the large size Rogowski coil on the measured results. Two different large size coils' frequency spectrum characteristics are analyzed and the effects of coil parameters on frequency band are also discussed. The impact of current-carrying bus decentration and inclination the Rogowski coil measured results is investigated. Both calculation and test strategy study methods are employed for the impact investigation. It is shown that the decentration of current-carrying bus has little impact of less than 4% errors on the measurement results when the current-carrying bus's decentration distance changed from 0 cm to 30 cm. The inclination of the current carrying-bus has more significant impact on the measured results. The error of measured current amplitude changes from 1.17% to 7.4% whilst the inclination angle changes from 0°to 60°under 5kA impulse current, and from 1.5% to 17.9% under 10kA impulse current. The theoretical analysis is in accordance with the experimental results. It is suggested that the Rogowski coil should be located installed perpendicular to the current-carrying bus and the decentration impact is ignorable when the decentration distance is less then 20% of the coil radius.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信