Ganggas B Maulana Idham, I. G. Dyana Arjana, I. A. Arta Wijaya
{"title":"PERENCANAAN SETTING DIRECTIONAL GROUND RELAY (DGR) UNTUK GANGGUAN SATU FASA KE TANAH DI SALURAN 150 KV DOUBLE CIRCUIT GIS PESANGGARAN – GI NUSA DUA","authors":"Ganggas B Maulana Idham, I. G. Dyana Arjana, I. A. Arta Wijaya","doi":"10.24843/spektrum.2021.v08.i04.p13","DOIUrl":null,"url":null,"abstract":"The single phase to ground fault on the 150 kV transmission line GIS Pesanggaran –Nusa Dua Substation has a high fault impedance so that the distance relay as anauxiliary safety device cannot detect the disturbance. Directional Ground Relay (DGR)was chosen as an auxiliary protection relay to secure the system from single phase toground faults. Installation of auxiliary protection relays requires planning and relaysetting steps to obtain Iset, TMS and trip time. The calculations that have been carriedout get the results of DGR setting with a pickup current range of 0.0522 – 0.0722 A.DGR will work after 2.297 seconds if the differential relay as the main protection relaydoes not work or fails and the distance relay as a backup protection does not succeed insecuring a single phase fault to ground as well.","PeriodicalId":30870,"journal":{"name":"Jurnal Ilmiah Spektrum","volume":"51 1","pages":""},"PeriodicalIF":0.0000,"publicationDate":"2022-01-08","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Jurnal Ilmiah Spektrum","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.24843/spektrum.2021.v08.i04.p13","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

GIS Pesanggaran -Nusa Dua变电站150 kV输电线路单相接地故障阻抗高,距离继电器作为辅助安全装置无法检测到故障。选择定向接地继电器(DGR)作为辅助保护继电器,保护系统免受单相接地故障的影响。辅助保护继电器的安装需要规划和继电器设置步骤,以获得Iset, TMS和跳闸时间。通过计算得到了取电电流范围为0.0522 ~ 0.0722 a的DGR整定结果。如果作为主保护继电器的差动继电器不工作或失效,并且作为备用保护的距离继电器也没有成功确保单相故障接地,则DGR将在2.297秒后工作。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
PERENCANAAN SETTING DIRECTIONAL GROUND RELAY (DGR) UNTUK GANGGUAN SATU FASA KE TANAH DI SALURAN 150 KV DOUBLE CIRCUIT GIS PESANGGARAN – GI NUSA DUA
The single phase to ground fault on the 150 kV transmission line GIS Pesanggaran –Nusa Dua Substation has a high fault impedance so that the distance relay as anauxiliary safety device cannot detect the disturbance. Directional Ground Relay (DGR)was chosen as an auxiliary protection relay to secure the system from single phase toground faults. Installation of auxiliary protection relays requires planning and relaysetting steps to obtain Iset, TMS and trip time. The calculations that have been carriedout get the results of DGR setting with a pickup current range of 0.0522 – 0.0722 A.DGR will work after 2.297 seconds if the differential relay as the main protection relaydoes not work or fails and the distance relay as a backup protection does not succeed insecuring a single phase fault to ground as well.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
审稿时长
24 weeks
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信