{"title":"暖通空调系统产生的谐波畸变特征——以PCR实验室为例","authors":"Reza Andika Setyadi, R. Setiabudy","doi":"10.24036/jptk.v6i1.31323","DOIUrl":null,"url":null,"abstract":"Good power quality is required in health facilities since the increasing use of microprocessor-based equipment. Poor power quality in the electric power system can cause medical equipment in health care centers to malfunction and give incorrect medical diagnoses. Since 2020 we are facing a new type of Virus (Covid-19), this virus requires special laboratory construction with specific air conditioning systems (temperature, humidity, and pressure) to process specimens. This paper presents measurement results of harmonic distortion characteristic by Variable Frequency Drive (VFD) of Heating Ventilation Air Conditioning (HVAC) system in PCR Laboratory at Clinic A. The VFD in this system is used to adjust the rotation of the exhaust fan and outdoor unit. The measured voltage, current and power are used to assess power quality. The main power quality problems found in medical facilities are voltage flicker, neutral currents, and total harmonic distortion (THD) values. The measurement of total harmonic distortion (THD) is used to find the source of the harmonics. Potential problems can be identified within the facility. The results of this study can be used to develop, test, and validate the system that has been used.","PeriodicalId":55675,"journal":{"name":"Jurnal Pendidikan Teknologi dan Kejuruan","volume":"24 1","pages":""},"PeriodicalIF":0.0000,"publicationDate":"2023-03-22","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"1","resultStr":"{\"title\":\"Harmonic Distortion Characteristics Generated by Heating Ventilation Air Conditioning System Case Study in PCR Laboratory\",\"authors\":\"Reza Andika Setyadi, R. Setiabudy\",\"doi\":\"10.24036/jptk.v6i1.31323\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Good power quality is required in health facilities since the increasing use of microprocessor-based equipment. Poor power quality in the electric power system can cause medical equipment in health care centers to malfunction and give incorrect medical diagnoses. Since 2020 we are facing a new type of Virus (Covid-19), this virus requires special laboratory construction with specific air conditioning systems (temperature, humidity, and pressure) to process specimens. This paper presents measurement results of harmonic distortion characteristic by Variable Frequency Drive (VFD) of Heating Ventilation Air Conditioning (HVAC) system in PCR Laboratory at Clinic A. The VFD in this system is used to adjust the rotation of the exhaust fan and outdoor unit. The measured voltage, current and power are used to assess power quality. The main power quality problems found in medical facilities are voltage flicker, neutral currents, and total harmonic distortion (THD) values. The measurement of total harmonic distortion (THD) is used to find the source of the harmonics. Potential problems can be identified within the facility. The results of this study can be used to develop, test, and validate the system that has been used.\",\"PeriodicalId\":55675,\"journal\":{\"name\":\"Jurnal Pendidikan Teknologi dan Kejuruan\",\"volume\":\"24 1\",\"pages\":\"\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2023-03-22\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"1\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Jurnal Pendidikan Teknologi dan Kejuruan\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.24036/jptk.v6i1.31323\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Jurnal Pendidikan Teknologi dan Kejuruan","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.24036/jptk.v6i1.31323","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 1

摘要

由于越来越多地使用基于微处理器的设备,卫生设施需要良好的电力质量。电力系统的电力质量差可能导致医疗中心的医疗设备故障并给出错误的医疗诊断。自2020年以来,我们面临着一种新型病毒(Covid-19),这种病毒需要特殊的实验室建设,配备特定的空调系统(温度、湿度和压力)来处理标本。本文介绍了a诊所PCR实验室暖通空调(HVAC)系统变频驱动(VFD)谐波失真特性的测量结果,该系统的变频驱动(VFD)用于调节排风机和室外机的转速。测量的电压、电流和功率用于评估电能质量。在医疗设施中发现的主要电能质量问题是电压闪变、中性电流和总谐波失真(THD)值。总谐波失真(THD)的测量被用来寻找谐波的来源。可以在设施内识别潜在问题。本研究的结果可用于开发、测试和验证已使用的系统。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Harmonic Distortion Characteristics Generated by Heating Ventilation Air Conditioning System Case Study in PCR Laboratory
Good power quality is required in health facilities since the increasing use of microprocessor-based equipment. Poor power quality in the electric power system can cause medical equipment in health care centers to malfunction and give incorrect medical diagnoses. Since 2020 we are facing a new type of Virus (Covid-19), this virus requires special laboratory construction with specific air conditioning systems (temperature, humidity, and pressure) to process specimens. This paper presents measurement results of harmonic distortion characteristic by Variable Frequency Drive (VFD) of Heating Ventilation Air Conditioning (HVAC) system in PCR Laboratory at Clinic A. The VFD in this system is used to adjust the rotation of the exhaust fan and outdoor unit. The measured voltage, current and power are used to assess power quality. The main power quality problems found in medical facilities are voltage flicker, neutral currents, and total harmonic distortion (THD) values. The measurement of total harmonic distortion (THD) is used to find the source of the harmonics. Potential problems can be identified within the facility. The results of this study can be used to develop, test, and validate the system that has been used.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
20
审稿时长
24 weeks
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信