{"title":"变压器与中压避雷器之间的距离对传递到低压侧的浪涌的影响","authors":"A. Piantini, T. O. de Carvalho, P. F. Obase, J. M. Janiszewski, G. D. Santos, D. R. Fagundes, J. Uchoa, E. Kunz","doi":"10.1109/ICHVE.2012.6357064","DOIUrl":null,"url":null,"abstract":"The western part of the state of Rio Grande do Sul, in South Brazil, is characterized by high ground flash densities. In the period 2003-2011, lightning overvoltages accounted for about 47 % of the total number of distribution transformer failures observed in the service area of the power company AES Sul. This paper presents the results of an investigation on the influence of the distance between transformer and medium voltage arresters on the surges transferred to the secondary side. The analysis, performed through simulations using the Alternative Transients Program (ATP), shows that in general higher voltages are produced by subsequent strokes. Although the amplitudes of the voltages transferred to the secondary side tend to increase as the surge arrester approaches the transformer, the distance between these equipment should be as short as possible.","PeriodicalId":6375,"journal":{"name":"2012 International Conference on High Voltage Engineering and Application","volume":"1 1","pages":"105-109"},"PeriodicalIF":0.0000,"publicationDate":"2012-11-26","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"1","resultStr":"{\"title\":\"The effect of the distance between transformer and MV arresters on the surges transferred to the LV side\",\"authors\":\"A. Piantini, T. O. de Carvalho, P. F. Obase, J. M. Janiszewski, G. D. Santos, D. R. Fagundes, J. Uchoa, E. Kunz\",\"doi\":\"10.1109/ICHVE.2012.6357064\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"The western part of the state of Rio Grande do Sul, in South Brazil, is characterized by high ground flash densities. In the period 2003-2011, lightning overvoltages accounted for about 47 % of the total number of distribution transformer failures observed in the service area of the power company AES Sul. This paper presents the results of an investigation on the influence of the distance between transformer and medium voltage arresters on the surges transferred to the secondary side. The analysis, performed through simulations using the Alternative Transients Program (ATP), shows that in general higher voltages are produced by subsequent strokes. Although the amplitudes of the voltages transferred to the secondary side tend to increase as the surge arrester approaches the transformer, the distance between these equipment should be as short as possible.\",\"PeriodicalId\":6375,\"journal\":{\"name\":\"2012 International Conference on High Voltage Engineering and Application\",\"volume\":\"1 1\",\"pages\":\"105-109\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2012-11-26\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"1\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2012 International Conference on High Voltage Engineering and Application\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/ICHVE.2012.6357064\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2012 International Conference on High Voltage Engineering and Application","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ICHVE.2012.6357064","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 1

摘要

南里奥格兰德州的西部,在巴西南部,是高地面闪电密度的特点。在2003-2011年期间,雷电过电压约占AES Sul电力公司服务区观察到的配电变压器故障总数的47%。本文介绍了变压器与中压避雷器之间的距离对传递到二次侧的浪涌的影响的研究结果。通过使用备选瞬变程序(ATP)进行的模拟分析表明,通常后续冲程会产生更高的电压。虽然当避雷器靠近变压器时,转移到次级侧的电压幅值趋于增加,但这些设备之间的距离应尽可能短。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
The effect of the distance between transformer and MV arresters on the surges transferred to the LV side
The western part of the state of Rio Grande do Sul, in South Brazil, is characterized by high ground flash densities. In the period 2003-2011, lightning overvoltages accounted for about 47 % of the total number of distribution transformer failures observed in the service area of the power company AES Sul. This paper presents the results of an investigation on the influence of the distance between transformer and medium voltage arresters on the surges transferred to the secondary side. The analysis, performed through simulations using the Alternative Transients Program (ATP), shows that in general higher voltages are produced by subsequent strokes. Although the amplitudes of the voltages transferred to the secondary side tend to increase as the surge arrester approaches the transformer, the distance between these equipment should be as short as possible.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信