大型客船高压岸接接地策略研究

E. B. Mehammer, O. Kongstein, A. Brede
{"title":"大型客船高压岸接接地策略研究","authors":"E. B. Mehammer, O. Kongstein, A. Brede","doi":"10.1109/EEEIC.2018.8493828","DOIUrl":null,"url":null,"abstract":"High voltage shore connection of large passenger vessels is an important way to improve energy efficiency and reduce local and global emissions, as well as noise. However, it is shown that the vessels' steel hulls will act as sacrificial anodes for the grounding systems in the ports, hence accelerated corrosion of the hulls may occur. The required protective earth (PE) conductor between the hull and the grounding system on shore could also introduce touch voltages above 30 V in case of a fault, posing a safety hazard. Based on field measurements and analyses, a grounding strategy with galvanic separation in the low resistance PE conductor is recommended. It is further advised to use active and passive cathodic protection, and to reduce the set point of the impressed current cathodic protection (ICCP) system to approximately 100 mV versus zinc. These measures will reduce the corrosion rate of the vessels' hulls during power delivery from shore, while avoiding transferred touch voltages.","PeriodicalId":6563,"journal":{"name":"2018 IEEE International Conference on Environment and Electrical Engineering and 2018 IEEE Industrial and Commercial Power Systems Europe (EEEIC / I&CPS Europe)","volume":"1 1","pages":"1-6"},"PeriodicalIF":0.0000,"publicationDate":"2018-06-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"1","resultStr":"{\"title\":\"Grounding Strategies for High Voltage Shore Connection of Large Passenger Vessels\",\"authors\":\"E. B. Mehammer, O. Kongstein, A. Brede\",\"doi\":\"10.1109/EEEIC.2018.8493828\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"High voltage shore connection of large passenger vessels is an important way to improve energy efficiency and reduce local and global emissions, as well as noise. However, it is shown that the vessels' steel hulls will act as sacrificial anodes for the grounding systems in the ports, hence accelerated corrosion of the hulls may occur. The required protective earth (PE) conductor between the hull and the grounding system on shore could also introduce touch voltages above 30 V in case of a fault, posing a safety hazard. Based on field measurements and analyses, a grounding strategy with galvanic separation in the low resistance PE conductor is recommended. It is further advised to use active and passive cathodic protection, and to reduce the set point of the impressed current cathodic protection (ICCP) system to approximately 100 mV versus zinc. These measures will reduce the corrosion rate of the vessels' hulls during power delivery from shore, while avoiding transferred touch voltages.\",\"PeriodicalId\":6563,\"journal\":{\"name\":\"2018 IEEE International Conference on Environment and Electrical Engineering and 2018 IEEE Industrial and Commercial Power Systems Europe (EEEIC / I&CPS Europe)\",\"volume\":\"1 1\",\"pages\":\"1-6\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2018-06-01\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"1\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2018 IEEE International Conference on Environment and Electrical Engineering and 2018 IEEE Industrial and Commercial Power Systems Europe (EEEIC / I&CPS Europe)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/EEEIC.2018.8493828\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2018 IEEE International Conference on Environment and Electrical Engineering and 2018 IEEE Industrial and Commercial Power Systems Europe (EEEIC / I&CPS Europe)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/EEEIC.2018.8493828","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 1

摘要

大型客船的高压岸上连接是提高能源效率,减少当地和全球排放以及噪音的重要途径。然而,研究表明,船舶的钢壳将作为港口接地系统的牺牲阳极,因此可能会加速船体的腐蚀。船体与岸上接地系统之间所需的保护接地(PE)导体也可能在故障情况下引入超过30 V的接触电压,构成安全隐患。在现场实测和分析的基础上,提出了在低阻聚乙烯导体中采用隔电接地的接地策略。进一步建议使用主动和被动阴极保护,并将外加电流阴极保护(ICCP)系统的设定点降低到约100 mV对锌。这些措施将减少船舶船体在岸上电力输送过程中的腐蚀速度,同时避免传递接触电压。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Grounding Strategies for High Voltage Shore Connection of Large Passenger Vessels
High voltage shore connection of large passenger vessels is an important way to improve energy efficiency and reduce local and global emissions, as well as noise. However, it is shown that the vessels' steel hulls will act as sacrificial anodes for the grounding systems in the ports, hence accelerated corrosion of the hulls may occur. The required protective earth (PE) conductor between the hull and the grounding system on shore could also introduce touch voltages above 30 V in case of a fault, posing a safety hazard. Based on field measurements and analyses, a grounding strategy with galvanic separation in the low resistance PE conductor is recommended. It is further advised to use active and passive cathodic protection, and to reduce the set point of the impressed current cathodic protection (ICCP) system to approximately 100 mV versus zinc. These measures will reduce the corrosion rate of the vessels' hulls during power delivery from shore, while avoiding transferred touch voltages.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信