{"title":"330(220)kV变电站接地装置电阻的测定","authors":"O. Glebov, D. Koliushko, A. V. Plichko, S. Rudenko","doi":"10.15407/techned2023.05.064","DOIUrl":null,"url":null,"abstract":"In the electric power industry of Ukraine, the main system-forming objects are power transmission lines and substations with 330(220) kV switchgear. The most powerful sources of danger at substations are short circuits on the busbars, a direct lightning strike or the operation of overvoltage limiters and arresters.The purpose of the article is to develop a method for determining the resistance of the grounding system of substations with open switchgear 330(220) kV, aimed at increasing accuracy, taking into account the most influential independent factors. The provisions of the theory of experiment planning, the theory of electric circuits, mathematical modeling in the package Grounding 1.0, LiGro and Microsoft Excel were used to conduct the research. In the paper, a comparative analysis of the known formulas for determining the resistance of the grounding system is carried out: the formula of the GOST 12.1.30-81 standard, Ohlendorf-Laurant, Laurent and Neumann, Schwartz, Sverak formulas, as well as the formula of the international standard IEEE Std 80-2013. The results of multifactorial experiments to determine the dependence of the resistance of the grounding system on its area, the size of the grid cell, the perimeter of the cross-section of the grounding, the equivalent specific resistance of the soil, the short-circuit current and the depth of the grid location are given. A graphical comparison of the results of determining the resistance according to the considered formulas was carried out. In the paper, the method of determining the parameters of grounding system of 330(220) kV substations was further developed, aimed at ensuring standardized values of the resistance of the grounding system and the ground potential rise using formulas obtained from the results of multifactorial experiments. The results obtained in the work will make it possible to reduce the probability of damage to the insulation of 6-10 kV cables, as well as cables of secondary circuits from low-frequency and high-frequency (pulse) voltages when large currents flow into the grounding system in the mode of a single-phase short-circuit to the ground in electrical grid with a grounded neutral. References 9, tables 2, figures 6.","PeriodicalId":38557,"journal":{"name":"Technical Electrodynamics","volume":" ","pages":""},"PeriodicalIF":0.0000,"publicationDate":"2023-08-28","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"DETERMINATION OF THE RESISTANCE OF GROUNDING DEVICES OF SUBSTATIONS 330(220) kV\",\"authors\":\"O. Glebov, D. Koliushko, A. V. Plichko, S. Rudenko\",\"doi\":\"10.15407/techned2023.05.064\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"In the electric power industry of Ukraine, the main system-forming objects are power transmission lines and substations with 330(220) kV switchgear. The most powerful sources of danger at substations are short circuits on the busbars, a direct lightning strike or the operation of overvoltage limiters and arresters.The purpose of the article is to develop a method for determining the resistance of the grounding system of substations with open switchgear 330(220) kV, aimed at increasing accuracy, taking into account the most influential independent factors. The provisions of the theory of experiment planning, the theory of electric circuits, mathematical modeling in the package Grounding 1.0, LiGro and Microsoft Excel were used to conduct the research. In the paper, a comparative analysis of the known formulas for determining the resistance of the grounding system is carried out: the formula of the GOST 12.1.30-81 standard, Ohlendorf-Laurant, Laurent and Neumann, Schwartz, Sverak formulas, as well as the formula of the international standard IEEE Std 80-2013. The results of multifactorial experiments to determine the dependence of the resistance of the grounding system on its area, the size of the grid cell, the perimeter of the cross-section of the grounding, the equivalent specific resistance of the soil, the short-circuit current and the depth of the grid location are given. A graphical comparison of the results of determining the resistance according to the considered formulas was carried out. In the paper, the method of determining the parameters of grounding system of 330(220) kV substations was further developed, aimed at ensuring standardized values of the resistance of the grounding system and the ground potential rise using formulas obtained from the results of multifactorial experiments. The results obtained in the work will make it possible to reduce the probability of damage to the insulation of 6-10 kV cables, as well as cables of secondary circuits from low-frequency and high-frequency (pulse) voltages when large currents flow into the grounding system in the mode of a single-phase short-circuit to the ground in electrical grid with a grounded neutral. References 9, tables 2, figures 6.\",\"PeriodicalId\":38557,\"journal\":{\"name\":\"Technical Electrodynamics\",\"volume\":\" \",\"pages\":\"\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2023-08-28\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Technical Electrodynamics\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.15407/techned2023.05.064\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"Q3\",\"JCRName\":\"Energy\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Technical Electrodynamics","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.15407/techned2023.05.064","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q3","JCRName":"Energy","Score":null,"Total":0}
引用次数: 0

摘要

在乌克兰电力工业中,主要的系统形成对象是带有330(220)kV开关设备的输电线路和变电站。变电站最强大的危险源是母线短路、直接雷击或过电压限制器和避雷器的操作。本文的目的是开发一种确定330(220)kV开放式开关设备变电站接地系统电阻的方法,旨在提高精度,同时考虑最具影响力的独立因素。根据实验计划理论、电路理论、数学建模的规定,在软件包Grounding 1.0、LiGro和Microsoft Excel中进行了研究。本文对已知的确定接地系统电阻的公式进行了比较分析:GOST 12.1.30-81标准的公式、Ohlendorf-Laurant、Laurent和Neumann、Schwartz、Sverak公式以及国际标准IEEE Std 80-2013的公式。给出了确定接地系统电阻与其面积、网格单元大小、接地横截面周长、土壤等效电阻率、短路电流和网格位置深度的相关性的多因素实验结果。对根据所考虑的公式确定电阻的结果进行了图形比较。本文进一步发展了330(220)kV变电站接地系统参数的确定方法,旨在利用多因素试验结果得出的公式,确保接地系统电阻和地电位上升的标准值。这项工作的结果将有可能降低在中性点接地的电网中,当大电流以单相对地短路的方式流入接地系统时,6-10kV电缆以及二次电路电缆的绝缘层受到低频和高频(脉冲)电压损坏的概率。参考文献9,表2,图6。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
DETERMINATION OF THE RESISTANCE OF GROUNDING DEVICES OF SUBSTATIONS 330(220) kV
In the electric power industry of Ukraine, the main system-forming objects are power transmission lines and substations with 330(220) kV switchgear. The most powerful sources of danger at substations are short circuits on the busbars, a direct lightning strike or the operation of overvoltage limiters and arresters.The purpose of the article is to develop a method for determining the resistance of the grounding system of substations with open switchgear 330(220) kV, aimed at increasing accuracy, taking into account the most influential independent factors. The provisions of the theory of experiment planning, the theory of electric circuits, mathematical modeling in the package Grounding 1.0, LiGro and Microsoft Excel were used to conduct the research. In the paper, a comparative analysis of the known formulas for determining the resistance of the grounding system is carried out: the formula of the GOST 12.1.30-81 standard, Ohlendorf-Laurant, Laurent and Neumann, Schwartz, Sverak formulas, as well as the formula of the international standard IEEE Std 80-2013. The results of multifactorial experiments to determine the dependence of the resistance of the grounding system on its area, the size of the grid cell, the perimeter of the cross-section of the grounding, the equivalent specific resistance of the soil, the short-circuit current and the depth of the grid location are given. A graphical comparison of the results of determining the resistance according to the considered formulas was carried out. In the paper, the method of determining the parameters of grounding system of 330(220) kV substations was further developed, aimed at ensuring standardized values of the resistance of the grounding system and the ground potential rise using formulas obtained from the results of multifactorial experiments. The results obtained in the work will make it possible to reduce the probability of damage to the insulation of 6-10 kV cables, as well as cables of secondary circuits from low-frequency and high-frequency (pulse) voltages when large currents flow into the grounding system in the mode of a single-phase short-circuit to the ground in electrical grid with a grounded neutral. References 9, tables 2, figures 6.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
Technical Electrodynamics
Technical Electrodynamics Energy-Energy Engineering and Power Technology
CiteScore
1.80
自引率
0.00%
发文量
72
审稿时长
4 weeks
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信