变电站避雷器内雷击时设备绝缘过电压的计算估计

IF 1.6 Q3 ENGINEERING, ELECTRICAL & ELECTRONIC
I. V. Nizhevskyi, V. I. Nizhevskyi
{"title":"变电站避雷器内雷击时设备绝缘过电压的计算估计","authors":"I. V. Nizhevskyi, V. I. Nizhevskyi","doi":"10.20998/2074-272X.2019.3.11","DOIUrl":null,"url":null,"abstract":"Purpose. The complex approach to calculating thunderstorm overvoltage on substation equipment is considered when lightning strikes in a lightning rod. Methodology. The conditions of safe passage of lightning current through a lightning arrester are formulated. Results. It is shown that the calculation of the permissible length of air insulating gaps in the substation is based on the breakdown of the air tension, which is assumed to be 500 kV/m. This leads to an error in calculating the length of the air gap and, as a consequence, the probability of its breakdown, the value of which is used to calculate the indicator of the lightning resistance of the substation. A technique is proposed for calculating the permissible voltage on the transformer case when a lightning strike strikes the lightning receptacle of the transformer portal. On the basis of the nonlinear pulsed electric strength of the ground, the specified minimum permissible ground distance between the grounding rod of the lightning rod and the nearest point of the protected device is obtained. Originality. Refined calculation of the length of the minimum breakdown gap in the air and in the ground. Practical value. The proposed approach makes it possible to calculate thunderstorm overvoltage on substation equipment. References 11, tables 4, figures 6.","PeriodicalId":44198,"journal":{"name":"Electrical Engineering & Electromechanics","volume":" ","pages":""},"PeriodicalIF":1.6000,"publicationDate":"2019-06-25","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"1","resultStr":"{\"title\":\"CALCULATION ESTIMATION OF OVERVOLTAGE ON INSULATION OF THE EQUIPMENT OF A SUBSTATION AT THE LIGHTNING STRIKE IN ITS LIGHTNING ARRESTER\",\"authors\":\"I. V. Nizhevskyi, V. I. Nizhevskyi\",\"doi\":\"10.20998/2074-272X.2019.3.11\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Purpose. The complex approach to calculating thunderstorm overvoltage on substation equipment is considered when lightning strikes in a lightning rod. Methodology. The conditions of safe passage of lightning current through a lightning arrester are formulated. Results. It is shown that the calculation of the permissible length of air insulating gaps in the substation is based on the breakdown of the air tension, which is assumed to be 500 kV/m. This leads to an error in calculating the length of the air gap and, as a consequence, the probability of its breakdown, the value of which is used to calculate the indicator of the lightning resistance of the substation. A technique is proposed for calculating the permissible voltage on the transformer case when a lightning strike strikes the lightning receptacle of the transformer portal. On the basis of the nonlinear pulsed electric strength of the ground, the specified minimum permissible ground distance between the grounding rod of the lightning rod and the nearest point of the protected device is obtained. Originality. Refined calculation of the length of the minimum breakdown gap in the air and in the ground. Practical value. The proposed approach makes it possible to calculate thunderstorm overvoltage on substation equipment. References 11, tables 4, figures 6.\",\"PeriodicalId\":44198,\"journal\":{\"name\":\"Electrical Engineering & Electromechanics\",\"volume\":\" \",\"pages\":\"\"},\"PeriodicalIF\":1.6000,\"publicationDate\":\"2019-06-25\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"1\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Electrical Engineering & Electromechanics\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.20998/2074-272X.2019.3.11\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"Q3\",\"JCRName\":\"ENGINEERING, ELECTRICAL & ELECTRONIC\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Electrical Engineering & Electromechanics","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.20998/2074-272X.2019.3.11","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q3","JCRName":"ENGINEERING, ELECTRICAL & ELECTRONIC","Score":null,"Total":0}
引用次数: 1

摘要

目的。考虑了雷击在避雷针内时变电所设备雷暴过电压的复杂计算方法。方法。给出了雷击电流安全通过避雷器的条件。结果。结果表明,变电站空气绝缘间隙允许长度的计算是基于空气张力的击穿,假设空气张力为500kv /m。这导致在计算气隙长度时出现误差,从而导致气隙击穿的概率出现误差,而气隙击穿的概率值用于计算变电站的防雷指标。提出了一种计算雷电击中变压器入口避雷器时变压器外壳上允许电压的方法。根据接地的非线性脉冲电强度,求得避雷针接地棒与被保护装置最近点之间规定的最小允许接地距离。创意。精细化计算了空中和地面的最小击穿间隙长度。实用价值。该方法使变电所设备的雷暴过电压计算成为可能。参考文献11,表4,图6。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
CALCULATION ESTIMATION OF OVERVOLTAGE ON INSULATION OF THE EQUIPMENT OF A SUBSTATION AT THE LIGHTNING STRIKE IN ITS LIGHTNING ARRESTER
Purpose. The complex approach to calculating thunderstorm overvoltage on substation equipment is considered when lightning strikes in a lightning rod. Methodology. The conditions of safe passage of lightning current through a lightning arrester are formulated. Results. It is shown that the calculation of the permissible length of air insulating gaps in the substation is based on the breakdown of the air tension, which is assumed to be 500 kV/m. This leads to an error in calculating the length of the air gap and, as a consequence, the probability of its breakdown, the value of which is used to calculate the indicator of the lightning resistance of the substation. A technique is proposed for calculating the permissible voltage on the transformer case when a lightning strike strikes the lightning receptacle of the transformer portal. On the basis of the nonlinear pulsed electric strength of the ground, the specified minimum permissible ground distance between the grounding rod of the lightning rod and the nearest point of the protected device is obtained. Originality. Refined calculation of the length of the minimum breakdown gap in the air and in the ground. Practical value. The proposed approach makes it possible to calculate thunderstorm overvoltage on substation equipment. References 11, tables 4, figures 6.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
Electrical Engineering & Electromechanics
Electrical Engineering & Electromechanics ENGINEERING, ELECTRICAL & ELECTRONIC-
CiteScore
2.40
自引率
50.00%
发文量
53
审稿时长
10 weeks
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信