将电流注入电力变压器作为测量差动继电器性能的内部故障现象

Q3 Engineering
Arief Goeritno, Irwan Nugraha, Syofyan Rasiman, A. Johan
{"title":"将电流注入电力变压器作为测量差动继电器性能的内部故障现象","authors":"Arief Goeritno, Irwan Nugraha, Syofyan Rasiman, A. Johan","doi":"10.18280/i2m.190605","DOIUrl":null,"url":null,"abstract":"In this paper explains the classical aspects in measure the differential relay performance. The classical aspects use the simulation through inrush current into the power transformer under three conditions. The first condition is giving the normal phenomenon as phenomenon of loading, the second condition is giving the fault phenomenon for outside of the protection zone, and the third condition is giving the fault phenomenon for inside of the protection zone. The result of measurement during loading condition, the differential relay not operate, because relay is set with value of 130% of the largest current between the three phases, so that the adjustable current is 4.45 mA. The results of current measurement to the differential relay when the fault condition is provided outside of the protection area, the current value to the differential relay should of zero mA and the differential relay not operate. The result of measurement of the current flow to the differential relay when giving the fault phenomenon inside the protection zone is obtained flow to relay at the phase-R is 127.7 mA, phase-S is 123.9 mA, and phase-T equal to 123.8 mA, while the result of calculation of the current flow to the differential relay of each phase of 152.61 mA, and the differential relay operate. After giving all of three conditions, the differential relay performance is known.","PeriodicalId":38637,"journal":{"name":"Instrumentation Mesure Metrologie","volume":" ","pages":""},"PeriodicalIF":0.0000,"publicationDate":"2020-12-29","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"6","resultStr":"{\"title\":\"Injection Current into the Power Transformer as an Internal Fault Phenomena for Measuring the Differential Relay Performance\",\"authors\":\"Arief Goeritno, Irwan Nugraha, Syofyan Rasiman, A. Johan\",\"doi\":\"10.18280/i2m.190605\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"In this paper explains the classical aspects in measure the differential relay performance. The classical aspects use the simulation through inrush current into the power transformer under three conditions. The first condition is giving the normal phenomenon as phenomenon of loading, the second condition is giving the fault phenomenon for outside of the protection zone, and the third condition is giving the fault phenomenon for inside of the protection zone. The result of measurement during loading condition, the differential relay not operate, because relay is set with value of 130% of the largest current between the three phases, so that the adjustable current is 4.45 mA. The results of current measurement to the differential relay when the fault condition is provided outside of the protection area, the current value to the differential relay should of zero mA and the differential relay not operate. The result of measurement of the current flow to the differential relay when giving the fault phenomenon inside the protection zone is obtained flow to relay at the phase-R is 127.7 mA, phase-S is 123.9 mA, and phase-T equal to 123.8 mA, while the result of calculation of the current flow to the differential relay of each phase of 152.61 mA, and the differential relay operate. After giving all of three conditions, the differential relay performance is known.\",\"PeriodicalId\":38637,\"journal\":{\"name\":\"Instrumentation Mesure Metrologie\",\"volume\":\" \",\"pages\":\"\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2020-12-29\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"6\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Instrumentation Mesure Metrologie\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.18280/i2m.190605\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"Q3\",\"JCRName\":\"Engineering\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Instrumentation Mesure Metrologie","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.18280/i2m.190605","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q3","JCRName":"Engineering","Score":null,"Total":0}
引用次数: 6

摘要

本文阐述了测量差动继电器性能的经典方面。经典方面使用了在三种条件下通过涌入电力变压器的电流进行模拟。第一种情况是将正常现象视为负载现象,第二种情况是在保护区外出现故障现象,第三种情况是保护区内出现故障现象。负载条件下的测量结果,差动继电器不工作,因为继电器设置为三相之间最大电流的130%,因此可调电流为4.45 mA。当故障条件提供在保护区域之外时,差动继电器的电流测量结果,至差动继电器的电流值应为0mA,并且差动继电器不工作。当在保护区内出现故障现象时,对流向差动继电器的电流进行测量的结果是,R相的流向继电器的电流为127.7 mA,S相为123.9 mA,T相等于123.8 mA,而每相的流向差动继电器电流的计算结果为152.61 mA,差动继电器运行。在给出所有三个条件后,差动继电器的性能就已知了。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Injection Current into the Power Transformer as an Internal Fault Phenomena for Measuring the Differential Relay Performance
In this paper explains the classical aspects in measure the differential relay performance. The classical aspects use the simulation through inrush current into the power transformer under three conditions. The first condition is giving the normal phenomenon as phenomenon of loading, the second condition is giving the fault phenomenon for outside of the protection zone, and the third condition is giving the fault phenomenon for inside of the protection zone. The result of measurement during loading condition, the differential relay not operate, because relay is set with value of 130% of the largest current between the three phases, so that the adjustable current is 4.45 mA. The results of current measurement to the differential relay when the fault condition is provided outside of the protection area, the current value to the differential relay should of zero mA and the differential relay not operate. The result of measurement of the current flow to the differential relay when giving the fault phenomenon inside the protection zone is obtained flow to relay at the phase-R is 127.7 mA, phase-S is 123.9 mA, and phase-T equal to 123.8 mA, while the result of calculation of the current flow to the differential relay of each phase of 152.61 mA, and the differential relay operate. After giving all of three conditions, the differential relay performance is known.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
Instrumentation Mesure Metrologie
Instrumentation Mesure Metrologie Engineering-Engineering (miscellaneous)
CiteScore
1.70
自引率
0.00%
发文量
25
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信