POSO PT.30MW发电机组过电流继电器(OCR)保护设置分析POSO ENERGY

Foristek Pub Date : 2024-05-23 DOI:10.54757/fs.v14i1.371
Angger Ramadani, Yulianda Rahman, Maryantho Masarrang, A.B. Kali, Y. S. Pirade
{"title":"POSO PT.30MW发电机组过电流继电器(OCR)保护设置分析POSO ENERGY","authors":"Angger Ramadani, Yulianda Rahman, Maryantho Masarrang, A.B. Kali, Y. S. Pirade","doi":"10.54757/fs.v14i1.371","DOIUrl":null,"url":null,"abstract":"To ensure that the performance of the protection system is still good or not in terms of protection, calculations and adjustments must be made to the safety relay settings, especially the over current relay. In the research, analysis of the over current relay protection settings on the 30 MW generator at the Poso 1 PT PLTA unit. Poso Energy obtained that the maximum load current data on the generator was 2042 A, while the calculation results obtained were 2041.7 A. For the relay (top) operating time in the specification data, the value was 1.4 s, while in the calculation results it was 1.3 s. And for the setting current (Is) in the specification data the value is 4.7 A, whereas in the calculation results it is 4.28 A. Over current relay (OCR) or over current relay is an auxiliary relay from the differential relay, the over current relay is used to secure the generator of the overcurrent in the Poso 1 PLTA is PCS-985GE-EN-H2-110V-5A. In the specification data, the TMS value is 0.15 s, while in the calculation results it is 0.14 s. This means that data in the field is slower to protect components from interference by 0.01 s. However, overall the overcurrent relay settings on the generator at the Poso 1 PLTA are still in good condition.","PeriodicalId":512591,"journal":{"name":"Foristek","volume":"59 1","pages":""},"PeriodicalIF":0.0000,"publicationDate":"2024-05-23","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"ANALISA SETTING PROTEKSI OVER CURRENT RELAY (OCR) PADA GENERATOR 30 MW UNIT PLTA POSO PT. POSO ENERGY\",\"authors\":\"Angger Ramadani, Yulianda Rahman, Maryantho Masarrang, A.B. Kali, Y. S. Pirade\",\"doi\":\"10.54757/fs.v14i1.371\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"To ensure that the performance of the protection system is still good or not in terms of protection, calculations and adjustments must be made to the safety relay settings, especially the over current relay. In the research, analysis of the over current relay protection settings on the 30 MW generator at the Poso 1 PT PLTA unit. Poso Energy obtained that the maximum load current data on the generator was 2042 A, while the calculation results obtained were 2041.7 A. For the relay (top) operating time in the specification data, the value was 1.4 s, while in the calculation results it was 1.3 s. And for the setting current (Is) in the specification data the value is 4.7 A, whereas in the calculation results it is 4.28 A. Over current relay (OCR) or over current relay is an auxiliary relay from the differential relay, the over current relay is used to secure the generator of the overcurrent in the Poso 1 PLTA is PCS-985GE-EN-H2-110V-5A. In the specification data, the TMS value is 0.15 s, while in the calculation results it is 0.14 s. This means that data in the field is slower to protect components from interference by 0.01 s. However, overall the overcurrent relay settings on the generator at the Poso 1 PLTA are still in good condition.\",\"PeriodicalId\":512591,\"journal\":{\"name\":\"Foristek\",\"volume\":\"59 1\",\"pages\":\"\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2024-05-23\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Foristek\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.54757/fs.v14i1.371\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Foristek","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.54757/fs.v14i1.371","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

为了确保保护系统的保护性能依然良好,必须对安全继电器的设置,尤其是过电流继电器的设置进行计算和调整。在研究中,对 Poso 1 PT PLTA 机组 30 兆瓦发电机的过电流继电器保护设置进行了分析。Poso Energy 获得的发电机最大负载电流数据为 2042 A,而计算结果为 2041.7 A。继电器(顶部)工作时间在规范数据中的值为 1.4 s,而在计算结果中为 1.3 s。过电流继电器(OCR)或过电流继电器是来自差动继电器的辅助继电器,过电流继电器用于确保 Poso 1 PLTA 中的发电机过电流为 PCS-985GE-EN-H2-110V-5A。在规格数据中,TMS 值为 0.15 秒,而在计算结果中为 0.14 秒。这意味着现场数据在保护元件免受干扰方面要慢 0.01 秒。不过,总体而言,Poso 1 PLTA 发电机上的过流继电器设置仍处于良好状态。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
ANALISA SETTING PROTEKSI OVER CURRENT RELAY (OCR) PADA GENERATOR 30 MW UNIT PLTA POSO PT. POSO ENERGY
To ensure that the performance of the protection system is still good or not in terms of protection, calculations and adjustments must be made to the safety relay settings, especially the over current relay. In the research, analysis of the over current relay protection settings on the 30 MW generator at the Poso 1 PT PLTA unit. Poso Energy obtained that the maximum load current data on the generator was 2042 A, while the calculation results obtained were 2041.7 A. For the relay (top) operating time in the specification data, the value was 1.4 s, while in the calculation results it was 1.3 s. And for the setting current (Is) in the specification data the value is 4.7 A, whereas in the calculation results it is 4.28 A. Over current relay (OCR) or over current relay is an auxiliary relay from the differential relay, the over current relay is used to secure the generator of the overcurrent in the Poso 1 PLTA is PCS-985GE-EN-H2-110V-5A. In the specification data, the TMS value is 0.15 s, while in the calculation results it is 0.14 s. This means that data in the field is slower to protect components from interference by 0.01 s. However, overall the overcurrent relay settings on the generator at the Poso 1 PLTA are still in good condition.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信