{"title":"通过开/关开关改造电机控制中心断路器以防止电机故障","authors":"Ahmad Rosyiddin, Imam Maulana Arief, Novarino Herdyan Minanta","doi":"10.22146/jmdt.85643","DOIUrl":null,"url":null,"abstract":"Motor Control Center (MCC) GT module, is a power breaker device that connects the voltage source to the load. MCC breaker rack-in and rack-out activities can be classified as unsafe action and unsade condition. Because there is a possibility of explosion. As it had happened several times in several places in the world. In 2021 there were 3 force derating and force outages which are caused by MCC motor breaker failures. That accident resulted 500,516.67 KWh loss or Rp 682,262,223,- ($ 44,766). Therefore, modifications need to be made to 0.4kV MCC breaker by adding a selector for the order off blocker to minimize socket damage due to frequent rack-in-rack-out breakers activity. After installing the modification to all breakers in Priok POMU, there was no failures occurred. The frequency of rack-in-rack-out activities were reduced significantly and that is a good result for operation safety. This modification can also prevent Priok POMU from a potential loss and potentially increase net profit up to Rp 221,549,398,- ($ 14,537).","PeriodicalId":201653,"journal":{"name":"Journal of Mechanical Design and Testing","volume":"20 1","pages":""},"PeriodicalIF":0.0000,"publicationDate":"2023-06-13","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Motor Control Center Breaker Modification Through On/Off Switch to Prevent Motor Failure\",\"authors\":\"Ahmad Rosyiddin, Imam Maulana Arief, Novarino Herdyan Minanta\",\"doi\":\"10.22146/jmdt.85643\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Motor Control Center (MCC) GT module, is a power breaker device that connects the voltage source to the load. MCC breaker rack-in and rack-out activities can be classified as unsafe action and unsade condition. Because there is a possibility of explosion. As it had happened several times in several places in the world. In 2021 there were 3 force derating and force outages which are caused by MCC motor breaker failures. That accident resulted 500,516.67 KWh loss or Rp 682,262,223,- ($ 44,766). Therefore, modifications need to be made to 0.4kV MCC breaker by adding a selector for the order off blocker to minimize socket damage due to frequent rack-in-rack-out breakers activity. After installing the modification to all breakers in Priok POMU, there was no failures occurred. The frequency of rack-in-rack-out activities were reduced significantly and that is a good result for operation safety. This modification can also prevent Priok POMU from a potential loss and potentially increase net profit up to Rp 221,549,398,- ($ 14,537).\",\"PeriodicalId\":201653,\"journal\":{\"name\":\"Journal of Mechanical Design and Testing\",\"volume\":\"20 1\",\"pages\":\"\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2023-06-13\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Journal of Mechanical Design and Testing\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.22146/jmdt.85643\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Journal of Mechanical Design and Testing","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.22146/jmdt.85643","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
Motor Control Center Breaker Modification Through On/Off Switch to Prevent Motor Failure
Motor Control Center (MCC) GT module, is a power breaker device that connects the voltage source to the load. MCC breaker rack-in and rack-out activities can be classified as unsafe action and unsade condition. Because there is a possibility of explosion. As it had happened several times in several places in the world. In 2021 there were 3 force derating and force outages which are caused by MCC motor breaker failures. That accident resulted 500,516.67 KWh loss or Rp 682,262,223,- ($ 44,766). Therefore, modifications need to be made to 0.4kV MCC breaker by adding a selector for the order off blocker to minimize socket damage due to frequent rack-in-rack-out breakers activity. After installing the modification to all breakers in Priok POMU, there was no failures occurred. The frequency of rack-in-rack-out activities were reduced significantly and that is a good result for operation safety. This modification can also prevent Priok POMU from a potential loss and potentially increase net profit up to Rp 221,549,398,- ($ 14,537).