N. Landry, G. St-Jean, R. Jeanjean, B. Khodabakhchian
{"title":"部分735-kV空吹断路器在直接断相和综合断相试验下的介电耐压水平","authors":"N. Landry, G. St-Jean, R. Jeanjean, B. Khodabakhchian","doi":"10.1109/TPAS.1985.318928","DOIUrl":null,"url":null,"abstract":"Simulations with the transient network analyzer at IREQ have revealed that following a load-shedding operation on the James Bay 735-kV power system, severe out-of-phase overvoltages could appear across the interrupting circuit breakers. The simulation results show that overvoltages could reach 2000 kV, while the maximum breaking current is as low as 5 kA rms. Since these overvoltage values far exceed the IEC specifications (1500 kV), direct and synthetic out-of-phase interrupting tests were performed on two types of breaker: a conventional air-blast circuit breaker of the type already in service and a modern improved design of the same type. The aim of the test program was to qualify high-voltage circuit breakers for the James Bay power system. The paper focuses on the analysis of the test results and deals especially with the decrease in dielectric strength of the breaker with the time that elapses after current interruption.","PeriodicalId":227345,"journal":{"name":"IEEE Transactions on Power Apparatus and Systems","volume":"11 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"1985-12-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"3","resultStr":"{\"title\":\"Dielectric-Withstand Levels of Some 735-kV Air-Blast Circuit Breakers Under Both Direct and Synthetic Out-of-Phase Interrupting Tests\",\"authors\":\"N. Landry, G. St-Jean, R. Jeanjean, B. Khodabakhchian\",\"doi\":\"10.1109/TPAS.1985.318928\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Simulations with the transient network analyzer at IREQ have revealed that following a load-shedding operation on the James Bay 735-kV power system, severe out-of-phase overvoltages could appear across the interrupting circuit breakers. The simulation results show that overvoltages could reach 2000 kV, while the maximum breaking current is as low as 5 kA rms. Since these overvoltage values far exceed the IEC specifications (1500 kV), direct and synthetic out-of-phase interrupting tests were performed on two types of breaker: a conventional air-blast circuit breaker of the type already in service and a modern improved design of the same type. The aim of the test program was to qualify high-voltage circuit breakers for the James Bay power system. The paper focuses on the analysis of the test results and deals especially with the decrease in dielectric strength of the breaker with the time that elapses after current interruption.\",\"PeriodicalId\":227345,\"journal\":{\"name\":\"IEEE Transactions on Power Apparatus and Systems\",\"volume\":\"11 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"1985-12-01\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"3\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"IEEE Transactions on Power Apparatus and Systems\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/TPAS.1985.318928\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"IEEE Transactions on Power Apparatus and Systems","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/TPAS.1985.318928","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 3
摘要
IREQ瞬态网络分析仪的模拟显示,在James Bay 735 kv电力系统进行减载操作后,中断断路器可能出现严重的异相过电压。仿真结果表明,过电压可达2000 kV,最大分断电流低至5 kA rms。由于这些过电压值远远超过IEC规范(1500千伏),因此对两种类型的断路器进行了直接和综合断相试验:一种是已经在使用的传统空气爆炸断路器,另一种是同一类型的现代改进设计。测试项目的目的是为詹姆斯湾电力系统提供合格的高压断路器。本文着重对试验结果进行了分析,重点讨论了断路器的介电强度随断流后时间的延长而降低的问题。
Dielectric-Withstand Levels of Some 735-kV Air-Blast Circuit Breakers Under Both Direct and Synthetic Out-of-Phase Interrupting Tests
Simulations with the transient network analyzer at IREQ have revealed that following a load-shedding operation on the James Bay 735-kV power system, severe out-of-phase overvoltages could appear across the interrupting circuit breakers. The simulation results show that overvoltages could reach 2000 kV, while the maximum breaking current is as low as 5 kA rms. Since these overvoltage values far exceed the IEC specifications (1500 kV), direct and synthetic out-of-phase interrupting tests were performed on two types of breaker: a conventional air-blast circuit breaker of the type already in service and a modern improved design of the same type. The aim of the test program was to qualify high-voltage circuit breakers for the James Bay power system. The paper focuses on the analysis of the test results and deals especially with the decrease in dielectric strength of the breaker with the time that elapses after current interruption.