{"title":"HFCT局部放电检测系统的实验室校准","authors":"Yifan Wang, Jinlong Gong, J. Ye, Xun Zhou, Liang Zhu, Tao Ma","doi":"10.1109/CIEEC50170.2021.9510969","DOIUrl":null,"url":null,"abstract":"With the advantages of high sensitivity and non-intrusiveness, HFCT PD detection systems are implemented in order to monitor incipient faults of power cables. This paper introduces a laboratory calibration method for HFCT PD detection systems based on a Gauss pulse signal. In order to modify practical PD signal at 1MHz~30MHz frequency band, equivalent Gauss pulse signal with certain rise time is applied. The method overcomes the drawback of sensitivity verification method recommended by IEC 62478 in traceability. All the standard equipment applied is frequently-used device in electrical laboratory. Parameters of the calibration work include frequency band, amplitude linearity, transfer impedance and detection sensitivity. By analyzing the data of four systems, the calibration provides reasonable criteria in quality verification of HFCT PD detection systems.","PeriodicalId":110429,"journal":{"name":"2021 IEEE 4th International Electrical and Energy Conference (CIEEC)","volume":"22 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2021-05-28","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Laboratory Calibration of HFCT Partial Discharge Detection Systems\",\"authors\":\"Yifan Wang, Jinlong Gong, J. Ye, Xun Zhou, Liang Zhu, Tao Ma\",\"doi\":\"10.1109/CIEEC50170.2021.9510969\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"With the advantages of high sensitivity and non-intrusiveness, HFCT PD detection systems are implemented in order to monitor incipient faults of power cables. This paper introduces a laboratory calibration method for HFCT PD detection systems based on a Gauss pulse signal. In order to modify practical PD signal at 1MHz~30MHz frequency band, equivalent Gauss pulse signal with certain rise time is applied. The method overcomes the drawback of sensitivity verification method recommended by IEC 62478 in traceability. All the standard equipment applied is frequently-used device in electrical laboratory. Parameters of the calibration work include frequency band, amplitude linearity, transfer impedance and detection sensitivity. By analyzing the data of four systems, the calibration provides reasonable criteria in quality verification of HFCT PD detection systems.\",\"PeriodicalId\":110429,\"journal\":{\"name\":\"2021 IEEE 4th International Electrical and Energy Conference (CIEEC)\",\"volume\":\"22 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2021-05-28\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2021 IEEE 4th International Electrical and Energy Conference (CIEEC)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/CIEEC50170.2021.9510969\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2021 IEEE 4th International Electrical and Energy Conference (CIEEC)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/CIEEC50170.2021.9510969","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

利用高灵敏度和非侵入性的优点,实现了HFCT局部放电检测系统,用于监测电力电缆的早期故障。介绍了一种基于高斯脉冲信号的HFCT局部放电检测系统的实验室标定方法。为了对1MHz~30MHz频段的实际PD信号进行修正,采用具有一定上升时间的等效高斯脉冲信号。该方法克服了IEC 62478推荐的灵敏度验证方法在可追溯性方面的缺点。所采用的标准设备均为电气实验室的常用设备。校准工作的参数包括频段、幅度线性度、传递阻抗和检测灵敏度。通过对四个系统的数据分析,为HFCT PD检测系统的质量验证提供了合理的依据。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Laboratory Calibration of HFCT Partial Discharge Detection Systems
With the advantages of high sensitivity and non-intrusiveness, HFCT PD detection systems are implemented in order to monitor incipient faults of power cables. This paper introduces a laboratory calibration method for HFCT PD detection systems based on a Gauss pulse signal. In order to modify practical PD signal at 1MHz~30MHz frequency band, equivalent Gauss pulse signal with certain rise time is applied. The method overcomes the drawback of sensitivity verification method recommended by IEC 62478 in traceability. All the standard equipment applied is frequently-used device in electrical laboratory. Parameters of the calibration work include frequency band, amplitude linearity, transfer impedance and detection sensitivity. By analyzing the data of four systems, the calibration provides reasonable criteria in quality verification of HFCT PD detection systems.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信