集装箱站的湿度控制

K. Ohshima, M. Nakao, Hirosi Jitukawa
{"title":"集装箱站的湿度控制","authors":"K. Ohshima, M. Nakao, Hirosi Jitukawa","doi":"10.1109/INTLEC.1987.4794619","DOIUrl":null,"url":null,"abstract":"When the compressor of a packaged air-conditioner for cooling a containerized station stops operating, the relative humidity of the room exceeds the upper limit of the specified range. The high relative humidity phenomenon is caused by water forming on the cooling coil of the air-conditioner. This water condenses, while the compressor is running, and is vaporized by the fan airflow which continuously operates, even after the compressor stops operating. As a result of this the water is not expelled to the outside but remains in the room, and the relative humidity increases. Several experiments are conducted to find a way of reducing the relative humidity in containerized stations. One way involves reducing the draft air volume, which contains a high level of moisture. Experiments and field tests indicated that the most effective method for maintaining the specified temperature range and relative humidity in a room, is to control the compressor by the room air temperature and the room fan by the relative humidity when the compressor stops operating.","PeriodicalId":129305,"journal":{"name":"INTELEC '87 - The Ninth International Telecommunications Energy Conference","volume":"15 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"1987-06-14","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"1","resultStr":"{\"title\":\"Humidity Control in a Containerized Station\",\"authors\":\"K. Ohshima, M. Nakao, Hirosi Jitukawa\",\"doi\":\"10.1109/INTLEC.1987.4794619\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"When the compressor of a packaged air-conditioner for cooling a containerized station stops operating, the relative humidity of the room exceeds the upper limit of the specified range. The high relative humidity phenomenon is caused by water forming on the cooling coil of the air-conditioner. This water condenses, while the compressor is running, and is vaporized by the fan airflow which continuously operates, even after the compressor stops operating. As a result of this the water is not expelled to the outside but remains in the room, and the relative humidity increases. Several experiments are conducted to find a way of reducing the relative humidity in containerized stations. One way involves reducing the draft air volume, which contains a high level of moisture. Experiments and field tests indicated that the most effective method for maintaining the specified temperature range and relative humidity in a room, is to control the compressor by the room air temperature and the room fan by the relative humidity when the compressor stops operating.\",\"PeriodicalId\":129305,\"journal\":{\"name\":\"INTELEC '87 - The Ninth International Telecommunications Energy Conference\",\"volume\":\"15 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"1987-06-14\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"1\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"INTELEC '87 - The Ninth International Telecommunications Energy Conference\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/INTLEC.1987.4794619\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"INTELEC '87 - The Ninth International Telecommunications Energy Conference","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/INTLEC.1987.4794619","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 1

摘要

装箱站制冷空调压缩机停止运行,导致机房相对湿度超过设定的湿度上限。现象描述相对湿度高的现象是由于空调冷却盘管上结水造成的。当压缩机运行时,这些水凝结,并被持续运行的风扇气流蒸发,即使在压缩机停止运行后。因此,水不会被排出到室外,而是留在房间内,相对湿度增加。为了找到降低集装箱站相对湿度的方法,进行了多次试验。一种方法是减少风量,因为风量中含有大量的水分。实验和现场试验表明,在压缩机停止工作时,通过空气温度控制压缩机,通过相对湿度控制风机,是维持室内规定温度范围和相对湿度的最有效方法。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Humidity Control in a Containerized Station
When the compressor of a packaged air-conditioner for cooling a containerized station stops operating, the relative humidity of the room exceeds the upper limit of the specified range. The high relative humidity phenomenon is caused by water forming on the cooling coil of the air-conditioner. This water condenses, while the compressor is running, and is vaporized by the fan airflow which continuously operates, even after the compressor stops operating. As a result of this the water is not expelled to the outside but remains in the room, and the relative humidity increases. Several experiments are conducted to find a way of reducing the relative humidity in containerized stations. One way involves reducing the draft air volume, which contains a high level of moisture. Experiments and field tests indicated that the most effective method for maintaining the specified temperature range and relative humidity in a room, is to control the compressor by the room air temperature and the room fan by the relative humidity when the compressor stops operating.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信