{"title":"怀氏δ型变压器相电流差动保护","authors":"Yuxue Wang, Xianggen Yin, Zhe Zhang, Zhenxing Li","doi":"10.11591/TELKOMNIKA.V10I6.1413","DOIUrl":null,"url":null,"abstract":"For the current transformers (CTs) on the delta side measure the line current instead of the phase current, line current differential protection is adopted in transformers connected in wye-delta mode currently. However, the symmetry feature of inrush current in line current differential protection may invalidate the inrush current restrained criterion. A calculating method of current through delta windings according the measured current from CT is proposed in this paper. Using this calculated current, phase current differential protection can be realized. Based on the method an adaptive second harmonic restrained scheme for magnetizing inrush current is presented. The scheme not only adaptively adjusts the secondary harmonic ratio of restrained current but also guarantees the fast action when transformers with internal faults are no-load energized. Consequently the performance of transformer differential protection is greatly improved. Simulation results in Matlab/Simulink validate the proposed method. DOI: http://dx.doi.org/10.11591/telkomnika.v10i6.1413 Full Text: PDF","PeriodicalId":414053,"journal":{"name":"TELKOMNIKA : Indonesian Journal of Electrical Engineering","volume":"38 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2012-09-12","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"2","resultStr":"{\"title\":\"Phase Current Differential Protection for Transformers in Wye-delta Mode\",\"authors\":\"Yuxue Wang, Xianggen Yin, Zhe Zhang, Zhenxing Li\",\"doi\":\"10.11591/TELKOMNIKA.V10I6.1413\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"For the current transformers (CTs) on the delta side measure the line current instead of the phase current, line current differential protection is adopted in transformers connected in wye-delta mode currently. However, the symmetry feature of inrush current in line current differential protection may invalidate the inrush current restrained criterion. A calculating method of current through delta windings according the measured current from CT is proposed in this paper. Using this calculated current, phase current differential protection can be realized. Based on the method an adaptive second harmonic restrained scheme for magnetizing inrush current is presented. The scheme not only adaptively adjusts the secondary harmonic ratio of restrained current but also guarantees the fast action when transformers with internal faults are no-load energized. Consequently the performance of transformer differential protection is greatly improved. Simulation results in Matlab/Simulink validate the proposed method. DOI: http://dx.doi.org/10.11591/telkomnika.v10i6.1413 Full Text: PDF\",\"PeriodicalId\":414053,\"journal\":{\"name\":\"TELKOMNIKA : Indonesian Journal of Electrical Engineering\",\"volume\":\"38 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2012-09-12\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"2\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"TELKOMNIKA : Indonesian Journal of Electrical Engineering\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.11591/TELKOMNIKA.V10I6.1413\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"TELKOMNIKA : Indonesian Journal of Electrical Engineering","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.11591/TELKOMNIKA.V10I6.1413","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
Phase Current Differential Protection for Transformers in Wye-delta Mode
For the current transformers (CTs) on the delta side measure the line current instead of the phase current, line current differential protection is adopted in transformers connected in wye-delta mode currently. However, the symmetry feature of inrush current in line current differential protection may invalidate the inrush current restrained criterion. A calculating method of current through delta windings according the measured current from CT is proposed in this paper. Using this calculated current, phase current differential protection can be realized. Based on the method an adaptive second harmonic restrained scheme for magnetizing inrush current is presented. The scheme not only adaptively adjusts the secondary harmonic ratio of restrained current but also guarantees the fast action when transformers with internal faults are no-load energized. Consequently the performance of transformer differential protection is greatly improved. Simulation results in Matlab/Simulink validate the proposed method. DOI: http://dx.doi.org/10.11591/telkomnika.v10i6.1413 Full Text: PDF