交流电压下用空气中电极间隙预先测定电力电缆局部放电起始电压

F. P. Mohamed, W. H. Siew, B. Sheng, B. Stewart, E. Morris
{"title":"交流电压下用空气中电极间隙预先测定电力电缆局部放电起始电压","authors":"F. P. Mohamed, W. H. Siew, B. Sheng, B. Stewart, E. Morris","doi":"10.1109/PPC.2017.8291314","DOIUrl":null,"url":null,"abstract":"The breakdown of insulation in cables while in service can cause considerable damage to equipment and the accessories to which they are connected. PD in cables arises due to the overstressing of cable insulation resulting from electric field enhancement caused by imperfections in cable core and screen. The nature and magnitude of PD activity depends upon the type of defect, aging, environmental factors, applied voltage and cable loading. Reduction in system voltage can potentially reduce PD, which will correspondingly extend the service life of the cable. Currently, industry voltage statutory requirements permit ±6% tolerance setting on nominal voltage on distribution networks. This ±6% voltage reduction on may have little or an adverse effect on PD magnitude depending on the nature of defect present in the cable. Hence there is a clear requirement to pre-determine the PD inception voltage in cables through laboratory experiments to understand the significance of voltage reduction. This means to verify the effect of voltage reduction on extinguishing or minimizing PD activity in cables. In this paper, range of voltages at which PD incepts termed as partial discharge inception voltage(PDIV) is measured using a test cell containing different types of electrode configuration having different spacing. PDIV measured using the test cell is verified by conducting partial discharge testing in paper insulated lead covered (PILC) and cross-linked poly ethylene(XLPE) cables. It has been found that PDIV measured using the test cell and cable are in good agreement.","PeriodicalId":247019,"journal":{"name":"2017 IEEE 21st International Conference on Pulsed Power (PPC)","volume":"1 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2017-10-10","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Pre-determination of partial discharge inception voltage in power cables using electrode gaps in air under AC voltage\",\"authors\":\"F. P. Mohamed, W. H. Siew, B. Sheng, B. Stewart, E. Morris\",\"doi\":\"10.1109/PPC.2017.8291314\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"The breakdown of insulation in cables while in service can cause considerable damage to equipment and the accessories to which they are connected. PD in cables arises due to the overstressing of cable insulation resulting from electric field enhancement caused by imperfections in cable core and screen. The nature and magnitude of PD activity depends upon the type of defect, aging, environmental factors, applied voltage and cable loading. Reduction in system voltage can potentially reduce PD, which will correspondingly extend the service life of the cable. Currently, industry voltage statutory requirements permit ±6% tolerance setting on nominal voltage on distribution networks. This ±6% voltage reduction on may have little or an adverse effect on PD magnitude depending on the nature of defect present in the cable. Hence there is a clear requirement to pre-determine the PD inception voltage in cables through laboratory experiments to understand the significance of voltage reduction. This means to verify the effect of voltage reduction on extinguishing or minimizing PD activity in cables. In this paper, range of voltages at which PD incepts termed as partial discharge inception voltage(PDIV) is measured using a test cell containing different types of electrode configuration having different spacing. PDIV measured using the test cell is verified by conducting partial discharge testing in paper insulated lead covered (PILC) and cross-linked poly ethylene(XLPE) cables. It has been found that PDIV measured using the test cell and cable are in good agreement.\",\"PeriodicalId\":247019,\"journal\":{\"name\":\"2017 IEEE 21st International Conference on Pulsed Power (PPC)\",\"volume\":\"1 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2017-10-10\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2017 IEEE 21st International Conference on Pulsed Power (PPC)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/PPC.2017.8291314\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2017 IEEE 21st International Conference on Pulsed Power (PPC)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/PPC.2017.8291314","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

在使用过程中,电缆绝缘的破裂会对设备及其连接的附件造成相当大的损坏。电缆局部放电是由于电缆芯和屏蔽缺陷引起的电场增强导致电缆绝缘过度受力而产生的。局部放电活动的性质和强度取决于缺陷的类型、老化、环境因素、外加电压和电缆负载。降低系统电压可以潜在地降低PD,从而相应地延长电缆的使用寿命。目前,工业电压法定要求允许在配电网的标称电压上设置±6%的公差。根据电缆中存在的缺陷的性质,±6%的电压降低可能对PD值影响很小或有不利影响。因此,明确要求通过实验室实验预先确定电缆中的PD起始电压,以了解电压降低的意义。这意味着验证电压降低对熄灭或最小化电缆中PD活性的影响。在本文中,使用包含具有不同间距的不同类型电极配置的测试单元来测量PD开始时称为局部放电开始电压(PDIV)的电压范围。通过在纸绝缘铅包(PILC)和交联聚乙烯(XLPE)电缆中进行部分放电测试,验证使用测试电池测量的PDIV。实验结果表明,用测试单元和电缆测得的PDIV值吻合较好。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Pre-determination of partial discharge inception voltage in power cables using electrode gaps in air under AC voltage
The breakdown of insulation in cables while in service can cause considerable damage to equipment and the accessories to which they are connected. PD in cables arises due to the overstressing of cable insulation resulting from electric field enhancement caused by imperfections in cable core and screen. The nature and magnitude of PD activity depends upon the type of defect, aging, environmental factors, applied voltage and cable loading. Reduction in system voltage can potentially reduce PD, which will correspondingly extend the service life of the cable. Currently, industry voltage statutory requirements permit ±6% tolerance setting on nominal voltage on distribution networks. This ±6% voltage reduction on may have little or an adverse effect on PD magnitude depending on the nature of defect present in the cable. Hence there is a clear requirement to pre-determine the PD inception voltage in cables through laboratory experiments to understand the significance of voltage reduction. This means to verify the effect of voltage reduction on extinguishing or minimizing PD activity in cables. In this paper, range of voltages at which PD incepts termed as partial discharge inception voltage(PDIV) is measured using a test cell containing different types of electrode configuration having different spacing. PDIV measured using the test cell is verified by conducting partial discharge testing in paper insulated lead covered (PILC) and cross-linked poly ethylene(XLPE) cables. It has been found that PDIV measured using the test cell and cable are in good agreement.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信