基于真空断路器统计特性的并联电容器组同步通电

Duan Xiong-ying, Fang Chun-en, Zou Ji-yan, Ding Fu-hua
{"title":"基于真空断路器统计特性的并联电容器组同步通电","authors":"Duan Xiong-ying, Fang Chun-en, Zou Ji-yan, Ding Fu-hua","doi":"10.1109/DEIV.2004.1422617","DOIUrl":null,"url":null,"abstract":"Operation of switching capacitor banks always produce over voltages and inrush currents, which may be harmful not only to the capacitor hanks themselves but also to other adjacent components of the system. Synchronized closing has been proved an efficient solution to reduce switching surge. In the present study, a l2kV vacuum circuit breaker (VCB) with permanent magnet actuator for each pole is used as the shunt capacitor switch. The influences on synchronized energization of circuit breaker's statistical characteristics, like contact operation time scatter, and the rate of decrease of dielectric strength (RDDS) of the electrode gap are discussed. The optimum closing instant is calculated according to these characteristics of VCB. Based on above analysis, a controlled closing system for shunt capacitor banks has been developed. A series of experiments demonstrate the excellent performance of this system.","PeriodicalId":137370,"journal":{"name":"XXIst International Symposium on Discharges and Electrical Insulation in Vacuum, 2004. Proceedings. ISDEIV.","volume":null,"pages":null},"PeriodicalIF":0.0000,"publicationDate":"1900-01-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"1","resultStr":"{\"title\":\"Synchronized energization of shunt capacitor banks based on statistical characteristics of vacuum circuit breakers\",\"authors\":\"Duan Xiong-ying, Fang Chun-en, Zou Ji-yan, Ding Fu-hua\",\"doi\":\"10.1109/DEIV.2004.1422617\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Operation of switching capacitor banks always produce over voltages and inrush currents, which may be harmful not only to the capacitor hanks themselves but also to other adjacent components of the system. Synchronized closing has been proved an efficient solution to reduce switching surge. In the present study, a l2kV vacuum circuit breaker (VCB) with permanent magnet actuator for each pole is used as the shunt capacitor switch. The influences on synchronized energization of circuit breaker's statistical characteristics, like contact operation time scatter, and the rate of decrease of dielectric strength (RDDS) of the electrode gap are discussed. The optimum closing instant is calculated according to these characteristics of VCB. Based on above analysis, a controlled closing system for shunt capacitor banks has been developed. A series of experiments demonstrate the excellent performance of this system.\",\"PeriodicalId\":137370,\"journal\":{\"name\":\"XXIst International Symposium on Discharges and Electrical Insulation in Vacuum, 2004. Proceedings. ISDEIV.\",\"volume\":null,\"pages\":null},\"PeriodicalIF\":0.0000,\"publicationDate\":\"1900-01-01\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"1\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"XXIst International Symposium on Discharges and Electrical Insulation in Vacuum, 2004. Proceedings. ISDEIV.\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/DEIV.2004.1422617\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"XXIst International Symposium on Discharges and Electrical Insulation in Vacuum, 2004. Proceedings. ISDEIV.","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/DEIV.2004.1422617","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 1

摘要

开关电容器组在运行过程中会产生过电压和浪涌电流,这不仅会对电容器组本身造成危害,也会对系统的其他相邻部件造成危害。同步合闸已被证明是降低开关浪涌的有效方法。在本研究中,采用l2kV真空断路器(VCB)作为并联电容器开关,每极采用永磁体作动器。讨论了触点动作时间散射和电极间隙介电强度下降速率等统计特性对断路器同步通电的影响。根据断路器的这些特性,计算出最佳合闸瞬间。在此基础上,设计了一种并联电容器组控制合闸系统。一系列的实验证明了该系统的优异性能。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Synchronized energization of shunt capacitor banks based on statistical characteristics of vacuum circuit breakers
Operation of switching capacitor banks always produce over voltages and inrush currents, which may be harmful not only to the capacitor hanks themselves but also to other adjacent components of the system. Synchronized closing has been proved an efficient solution to reduce switching surge. In the present study, a l2kV vacuum circuit breaker (VCB) with permanent magnet actuator for each pole is used as the shunt capacitor switch. The influences on synchronized energization of circuit breaker's statistical characteristics, like contact operation time scatter, and the rate of decrease of dielectric strength (RDDS) of the electrode gap are discussed. The optimum closing instant is calculated according to these characteristics of VCB. Based on above analysis, a controlled closing system for shunt capacitor banks has been developed. A series of experiments demonstrate the excellent performance of this system.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
CiteScore
0.40
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信