{"title":"OLTC对风电场无功能力要求符合性的影响及优化利用","authors":"S. Uski","doi":"10.1109/ISGTEurope.2017.8260330","DOIUrl":null,"url":null,"abstract":"Wind power plants (WPPs) must fulfil Grid Code specified reactive power requirements at their connection points. Thus all the WPP components' influence on reactive power capability counts. The WPP main transformer On-Load Tap Changer (OLTC) control settings or control scheme can be optimized in critical borderline cases, possibly enabling sufficient reactive power capability just by a mere control setting adjustment. The influence of OLTC control voltage reference parameter values is studied related to WPP reactive power capability, and noted that even a relatively small marginal influence makes a difference under certain circumstances. In addition, a method for determining the optimal OLTC voltage control parameter values is introduced and demonstrated successfully on an example Test Case.","PeriodicalId":345050,"journal":{"name":"2017 IEEE PES Innovative Smart Grid Technologies Conference Europe (ISGT-Europe)","volume":"29 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2017-09-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Influence and optimal use of OLTC in wind power plants for reactive power capability requirement compliance\",\"authors\":\"S. Uski\",\"doi\":\"10.1109/ISGTEurope.2017.8260330\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Wind power plants (WPPs) must fulfil Grid Code specified reactive power requirements at their connection points. Thus all the WPP components' influence on reactive power capability counts. The WPP main transformer On-Load Tap Changer (OLTC) control settings or control scheme can be optimized in critical borderline cases, possibly enabling sufficient reactive power capability just by a mere control setting adjustment. The influence of OLTC control voltage reference parameter values is studied related to WPP reactive power capability, and noted that even a relatively small marginal influence makes a difference under certain circumstances. In addition, a method for determining the optimal OLTC voltage control parameter values is introduced and demonstrated successfully on an example Test Case.\",\"PeriodicalId\":345050,\"journal\":{\"name\":\"2017 IEEE PES Innovative Smart Grid Technologies Conference Europe (ISGT-Europe)\",\"volume\":\"29 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2017-09-01\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2017 IEEE PES Innovative Smart Grid Technologies Conference Europe (ISGT-Europe)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/ISGTEurope.2017.8260330\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2017 IEEE PES Innovative Smart Grid Technologies Conference Europe (ISGT-Europe)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ISGTEurope.2017.8260330","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

风力发电厂(WPPs)必须在其连接点满足电网规范规定的无功功率要求。因此,所有WPP组件对无功能力的影响都很重要。WPP主变压器有载分接开关(OLTC)控制设置或控制方案可以在临界临界情况下进行优化,仅通过简单的控制设置调整即可实现足够的无功能力。研究了与WPP无功能力相关的OLTC控制电压参考参数值的影响,并指出在某些情况下,即使是相对较小的边际影响也会产生差异。此外,还介绍了一种确定OLTC电压控制参数最优值的方法,并在一个测试用例上进行了成功的验证。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Influence and optimal use of OLTC in wind power plants for reactive power capability requirement compliance
Wind power plants (WPPs) must fulfil Grid Code specified reactive power requirements at their connection points. Thus all the WPP components' influence on reactive power capability counts. The WPP main transformer On-Load Tap Changer (OLTC) control settings or control scheme can be optimized in critical borderline cases, possibly enabling sufficient reactive power capability just by a mere control setting adjustment. The influence of OLTC control voltage reference parameter values is studied related to WPP reactive power capability, and noted that even a relatively small marginal influence makes a difference under certain circumstances. In addition, a method for determining the optimal OLTC voltage control parameter values is introduced and demonstrated successfully on an example Test Case.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信