{"title":"高压SF6断路器的可控故障中断方法","authors":"R. P. Thomas, C. Solver","doi":"10.1109/PCT.2007.4538475","DOIUrl":null,"url":null,"abstract":"A method has been developed for synchronizing the trip commands to a HV circuit breaker in order to achieve a preselected optimum arcing time, even under transient asymmetrical fault current conditions. The algorithm estimates parameters of the fault current by applying least means squares regression to a generic model and sampled values of the current in each phase. An analysis of variance is made between the sampled and modeled currents to provide additional control and as a basis for discrimination between grounded and ungrounded fault cases. In addition, high power experiments have been conducted to investigate the stability of minimum arcing times of HV SF6 circuit breakers over a large succession of interruptions. The data from these experiments indicates good stability in the minimum arcing time behavior, thus providing important information for the viability of synchronizing circuit breakers in order to avoid unnecessarily long arcing times.","PeriodicalId":356805,"journal":{"name":"2007 IEEE Lausanne Power Tech","volume":"27 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2007-07-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"10","resultStr":"{\"title\":\"A Method for Controlled Fault Interruption for Use with HV SF6 Circuit Breakers\",\"authors\":\"R. P. Thomas, C. Solver\",\"doi\":\"10.1109/PCT.2007.4538475\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"A method has been developed for synchronizing the trip commands to a HV circuit breaker in order to achieve a preselected optimum arcing time, even under transient asymmetrical fault current conditions. The algorithm estimates parameters of the fault current by applying least means squares regression to a generic model and sampled values of the current in each phase. An analysis of variance is made between the sampled and modeled currents to provide additional control and as a basis for discrimination between grounded and ungrounded fault cases. In addition, high power experiments have been conducted to investigate the stability of minimum arcing times of HV SF6 circuit breakers over a large succession of interruptions. The data from these experiments indicates good stability in the minimum arcing time behavior, thus providing important information for the viability of synchronizing circuit breakers in order to avoid unnecessarily long arcing times.\",\"PeriodicalId\":356805,\"journal\":{\"name\":\"2007 IEEE Lausanne Power Tech\",\"volume\":\"27 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2007-07-01\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"10\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2007 IEEE Lausanne Power Tech\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/PCT.2007.4538475\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2007 IEEE Lausanne Power Tech","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/PCT.2007.4538475","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 10

摘要

为了在暂态不对称故障电流条件下实现预选最佳电弧时间,开发了一种将脱扣指令同步到高压断路器的方法。该算法通过对通用模型和各相电流采样值进行最小均方差回归,估计出故障电流参数。在采样和模拟电流之间进行方差分析,以提供额外的控制,并作为区分接地和不接地故障情况的基础。此外,还进行了高功率实验,研究了高压SF6断路器在大量连续中断情况下的最小起弧次数的稳定性。这些实验数据表明,最小电弧时间行为具有良好的稳定性,从而为同步断路器的可行性提供了重要信息,以避免不必要的长电弧时间。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
A Method for Controlled Fault Interruption for Use with HV SF6 Circuit Breakers
A method has been developed for synchronizing the trip commands to a HV circuit breaker in order to achieve a preselected optimum arcing time, even under transient asymmetrical fault current conditions. The algorithm estimates parameters of the fault current by applying least means squares regression to a generic model and sampled values of the current in each phase. An analysis of variance is made between the sampled and modeled currents to provide additional control and as a basis for discrimination between grounded and ungrounded fault cases. In addition, high power experiments have been conducted to investigate the stability of minimum arcing times of HV SF6 circuit breakers over a large succession of interruptions. The data from these experiments indicates good stability in the minimum arcing time behavior, thus providing important information for the viability of synchronizing circuit breakers in order to avoid unnecessarily long arcing times.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信