{"title":"利用CFD提高控制阀效率","authors":"A. Reich","doi":"10.1115/pvp2019-93417","DOIUrl":null,"url":null,"abstract":"\n Control valves are used to adjust fluid flow rates in an extremely wide variety of applications. This paper discusses a steam flow control valve that is required to operate with a fairly wide range of inlet conditions (steam pressure) and provide effective control over a fairly wide range of steam flow rates. In this particular case a valve design was developed using “classical” methods — a combination of experience and hand calculations. The valve was tested and it did not provide adequate control over the flow for the application. The valve redesign effort used CFD to gain insight into the flow through the valve in order to evaluate control performance before the valve was fabricated and assembled. Several internal geometries were assessed and compared in order to identify two configurations that would meet the flow control requirements. These configurations were fabricated and tested and deemed to be adequate.","PeriodicalId":150804,"journal":{"name":"Volume 3: Design and Analysis","volume":null,"pages":null},"PeriodicalIF":0.0000,"publicationDate":"2019-11-15","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"1","resultStr":"{\"title\":\"Use of CFD to Improve Control Valve Effectiveness\",\"authors\":\"A. Reich\",\"doi\":\"10.1115/pvp2019-93417\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"\\n Control valves are used to adjust fluid flow rates in an extremely wide variety of applications. This paper discusses a steam flow control valve that is required to operate with a fairly wide range of inlet conditions (steam pressure) and provide effective control over a fairly wide range of steam flow rates. In this particular case a valve design was developed using “classical” methods — a combination of experience and hand calculations. The valve was tested and it did not provide adequate control over the flow for the application. The valve redesign effort used CFD to gain insight into the flow through the valve in order to evaluate control performance before the valve was fabricated and assembled. Several internal geometries were assessed and compared in order to identify two configurations that would meet the flow control requirements. These configurations were fabricated and tested and deemed to be adequate.\",\"PeriodicalId\":150804,\"journal\":{\"name\":\"Volume 3: Design and Analysis\",\"volume\":null,\"pages\":null},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2019-11-15\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"1\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Volume 3: Design and Analysis\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1115/pvp2019-93417\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Volume 3: Design and Analysis","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1115/pvp2019-93417","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 1

摘要

控制阀用于在各种应用中调节流体流速。本文讨论了一种蒸汽流量控制阀,它需要在相当宽的进口条件(蒸汽压力)范围内运行,并对相当宽的蒸汽流量范围提供有效控制。在这种特殊情况下,阀门设计是使用“经典”方法开发的——经验和手工计算的结合。经过测试,该阀门不能提供足够的流量控制。阀门的重新设计工作使用CFD来了解通过阀门的流动情况,以便在阀门制造和组装之前评估控制性能。对几种内部几何形状进行了评估和比较,以确定满足流量控制要求的两种配置。这些配置经过制造和测试,认为是足够的。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Use of CFD to Improve Control Valve Effectiveness
Control valves are used to adjust fluid flow rates in an extremely wide variety of applications. This paper discusses a steam flow control valve that is required to operate with a fairly wide range of inlet conditions (steam pressure) and provide effective control over a fairly wide range of steam flow rates. In this particular case a valve design was developed using “classical” methods — a combination of experience and hand calculations. The valve was tested and it did not provide adequate control over the flow for the application. The valve redesign effort used CFD to gain insight into the flow through the valve in order to evaluate control performance before the valve was fabricated and assembled. Several internal geometries were assessed and compared in order to identify two configurations that would meet the flow control requirements. These configurations were fabricated and tested and deemed to be adequate.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信