采用空气对空气热交换器,降低室外机柜的峰值温度

J. McKay
{"title":"采用空气对空气热交换器,降低室外机柜的峰值温度","authors":"J. McKay","doi":"10.1109/INTLEC.1990.171308","DOIUrl":null,"url":null,"abstract":"To assess the effectiveness of air-to-air heat exchangers in reducing peak temperature rise in outdoor telephone equipment cabinets, a series of tests was conducted during the summer of 1989 at the Chester thermal test facility. The tests demonstrated that an average 10 degrees F or better reduction in peak internal air temperature within outdoor cabinets could be achieved using a simple air-to-air heat exchanger. This drop was measured in a 50 ft/sup 3/ cabinet with internal heat loads of 680 and 920 watts, and was in addition to any reduction obtained through use of internal air circulating fans. About the same peak internal air temperature was obtained for the 920 watt load without the heat exchanger operating. The author describes the test procedure and results.<<ETX>>","PeriodicalId":264940,"journal":{"name":"12th International Conference on Telecommunications Energy","volume":null,"pages":null},"PeriodicalIF":0.0000,"publicationDate":"1990-10-21","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"3","resultStr":"{\"title\":\"Use of an air-to-air heat exchanger to reduce peak temperatures in outdoor cabinets\",\"authors\":\"J. McKay\",\"doi\":\"10.1109/INTLEC.1990.171308\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"To assess the effectiveness of air-to-air heat exchangers in reducing peak temperature rise in outdoor telephone equipment cabinets, a series of tests was conducted during the summer of 1989 at the Chester thermal test facility. The tests demonstrated that an average 10 degrees F or better reduction in peak internal air temperature within outdoor cabinets could be achieved using a simple air-to-air heat exchanger. This drop was measured in a 50 ft/sup 3/ cabinet with internal heat loads of 680 and 920 watts, and was in addition to any reduction obtained through use of internal air circulating fans. About the same peak internal air temperature was obtained for the 920 watt load without the heat exchanger operating. The author describes the test procedure and results.<<ETX>>\",\"PeriodicalId\":264940,\"journal\":{\"name\":\"12th International Conference on Telecommunications Energy\",\"volume\":null,\"pages\":null},\"PeriodicalIF\":0.0000,\"publicationDate\":\"1990-10-21\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"3\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"12th International Conference on Telecommunications Energy\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/INTLEC.1990.171308\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"12th International Conference on Telecommunications Energy","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/INTLEC.1990.171308","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 3

摘要

为了评估空气对空气热交换器在减少室外电话设备柜内温度峰值上升方面的有效性,1989年夏天在切斯特热试验设施进行了一系列试验。测试表明,使用简单的空气对空气热交换器可以实现室外机柜内部空气峰值温度平均降低10华氏度或更好。这一下降是在一个50英尺/sup /的机柜中测量的,内部热负荷分别为680和920瓦,这是通过使用内部空气循环风扇获得的任何减少。在没有热交换器工作的情况下,在920瓦负荷下获得了大致相同的内部空气温度峰值。作者介绍了测试过程和结果
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Use of an air-to-air heat exchanger to reduce peak temperatures in outdoor cabinets
To assess the effectiveness of air-to-air heat exchangers in reducing peak temperature rise in outdoor telephone equipment cabinets, a series of tests was conducted during the summer of 1989 at the Chester thermal test facility. The tests demonstrated that an average 10 degrees F or better reduction in peak internal air temperature within outdoor cabinets could be achieved using a simple air-to-air heat exchanger. This drop was measured in a 50 ft/sup 3/ cabinet with internal heat loads of 680 and 920 watts, and was in addition to any reduction obtained through use of internal air circulating fans. About the same peak internal air temperature was obtained for the 920 watt load without the heat exchanger operating. The author describes the test procedure and results.<>
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信