{"title":"某变电站接地故障清除引起的接地变压器暂态分析及解决方案","authors":"Vahid Hakimian, M. Davarpanah","doi":"10.1109/IPAPS58344.2023.10123315","DOIUrl":null,"url":null,"abstract":"Power transformers used in the subtransmission substations of the Iranian power grid have YNd connection. In addition, a grounding transformer with YNd connection is used to create an artificial neutral on the medium voltage side. Ifthe phase to ground capacitor is high in the medium voltage network, in some conditions, such as interruption of the phase-to-ground fault current in one of the output feeders, a kind of resonance is created in the network that not only damages the grounding transformer, but also causes protection problems related to the misalignment of ground fault relays. In this paper, the resonance between the grounding transformer and the phase-to-ground capacitor of the medium voltage output feeders of a sample subtransmission substation is investigated, considering that the phase-to-ground fault is interrupted. In this way, several indicators are defined to adjust the surge arrester and other elements of the subtransmission network. Also, appropriate solutions are presented in order to damp the aforementioned resonance.","PeriodicalId":314748,"journal":{"name":"2023 International Conference on Protection and Automation of Power Systems (IPAPS)","volume":"1 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2023-01-24","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Grounding Transformer Transient Analysis Caused by Earth Fault Clearance in a Subtransmission Substation and Proposing Appropriate Solutions\",\"authors\":\"Vahid Hakimian, M. Davarpanah\",\"doi\":\"10.1109/IPAPS58344.2023.10123315\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Power transformers used in the subtransmission substations of the Iranian power grid have YNd connection. In addition, a grounding transformer with YNd connection is used to create an artificial neutral on the medium voltage side. Ifthe phase to ground capacitor is high in the medium voltage network, in some conditions, such as interruption of the phase-to-ground fault current in one of the output feeders, a kind of resonance is created in the network that not only damages the grounding transformer, but also causes protection problems related to the misalignment of ground fault relays. In this paper, the resonance between the grounding transformer and the phase-to-ground capacitor of the medium voltage output feeders of a sample subtransmission substation is investigated, considering that the phase-to-ground fault is interrupted. In this way, several indicators are defined to adjust the surge arrester and other elements of the subtransmission network. Also, appropriate solutions are presented in order to damp the aforementioned resonance.\",\"PeriodicalId\":314748,\"journal\":{\"name\":\"2023 International Conference on Protection and Automation of Power Systems (IPAPS)\",\"volume\":\"1 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2023-01-24\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2023 International Conference on Protection and Automation of Power Systems (IPAPS)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/IPAPS58344.2023.10123315\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2023 International Conference on Protection and Automation of Power Systems (IPAPS)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/IPAPS58344.2023.10123315","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

伊朗电网分变电所使用的电力变压器均为YNd连接。此外,使用YNd连接的接地变压器在中压侧创建人工中性点。如果中压网络中相地电容较高,在某些情况下,例如在其中一条输出馈线中中断相地故障电流,则在网络中产生一种谐振,不仅损坏接地变压器,而且还会引起与接地故障继电器不对中有关的保护问题。本文研究了某样变电站中压输出馈线接地变压器与相地电容在相地故障中断情况下的谐振问题。通过这种方式,定义了几个指标来调整避雷器和亚输电网的其他元件。此外,提出了适当的解决方案,以抑制上述共振。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Grounding Transformer Transient Analysis Caused by Earth Fault Clearance in a Subtransmission Substation and Proposing Appropriate Solutions
Power transformers used in the subtransmission substations of the Iranian power grid have YNd connection. In addition, a grounding transformer with YNd connection is used to create an artificial neutral on the medium voltage side. Ifthe phase to ground capacitor is high in the medium voltage network, in some conditions, such as interruption of the phase-to-ground fault current in one of the output feeders, a kind of resonance is created in the network that not only damages the grounding transformer, but also causes protection problems related to the misalignment of ground fault relays. In this paper, the resonance between the grounding transformer and the phase-to-ground capacitor of the medium voltage output feeders of a sample subtransmission substation is investigated, considering that the phase-to-ground fault is interrupted. In this way, several indicators are defined to adjust the surge arrester and other elements of the subtransmission network. Also, appropriate solutions are presented in order to damp the aforementioned resonance.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信