{"title":"高效维护中压配电线路的避雷器风险评估","authors":"Masahiro Ueda, S. Yasui, Hidekazu Tanaka, Tomoaki Nonoyama, Y. Kunii","doi":"10.1109/APL57308.2023.10181353","DOIUrl":null,"url":null,"abstract":"In the lightning protection design of medium-voltage distribution lines, the introduction of arcing horns with a zinc-oxide element to protect the insulated cables and insulators and primary cutout with a zinc-oxide element to protect transformers have reduced the damage by direct lightning strikes. However, the failure rate of lightning arrester elements used in these power distribution systems is increasing. In this study, we evaluated the failure risk of lightning arrester elements installed on utility poles based on the probability of lightning strikes exceeding the energy tolerance of each surge arrester element. As a result, when the insulators on a pole are unprotected, the elements of arresters installed on the poles adjacent to it on its either side and supporting the same phase line will have the highest failure risk.","PeriodicalId":371726,"journal":{"name":"2023 12th Asia-Pacific International Conference on Lightning (APL)","volume":"8 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2023-06-12","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Risk Assessment of Surge Arresters for Efficient Maintenance of Medium-voltage Distribution Lines\",\"authors\":\"Masahiro Ueda, S. Yasui, Hidekazu Tanaka, Tomoaki Nonoyama, Y. Kunii\",\"doi\":\"10.1109/APL57308.2023.10181353\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"In the lightning protection design of medium-voltage distribution lines, the introduction of arcing horns with a zinc-oxide element to protect the insulated cables and insulators and primary cutout with a zinc-oxide element to protect transformers have reduced the damage by direct lightning strikes. However, the failure rate of lightning arrester elements used in these power distribution systems is increasing. In this study, we evaluated the failure risk of lightning arrester elements installed on utility poles based on the probability of lightning strikes exceeding the energy tolerance of each surge arrester element. As a result, when the insulators on a pole are unprotected, the elements of arresters installed on the poles adjacent to it on its either side and supporting the same phase line will have the highest failure risk.\",\"PeriodicalId\":371726,\"journal\":{\"name\":\"2023 12th Asia-Pacific International Conference on Lightning (APL)\",\"volume\":\"8 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2023-06-12\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2023 12th Asia-Pacific International Conference on Lightning (APL)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/APL57308.2023.10181353\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2023 12th Asia-Pacific International Conference on Lightning (APL)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/APL57308.2023.10181353","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

在中压配电线路的防雷设计中,引入氧化锌元件电弧角保护绝缘电缆和绝缘子,引入氧化锌元件保护变压器一次断路,降低了直击雷击的危害。然而,在这些配电系统中使用的避雷器元件的故障率正在增加。在本研究中,我们基于雷击超过每个避雷器元件能量容限的概率来评估安装在电线杆上的避雷器元件的失效风险。因此,当一个极点上的绝缘子不受保护时,安装在其两侧相邻极点上并支持同一相线的避雷器元件将具有最高的失效风险。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Risk Assessment of Surge Arresters for Efficient Maintenance of Medium-voltage Distribution Lines
In the lightning protection design of medium-voltage distribution lines, the introduction of arcing horns with a zinc-oxide element to protect the insulated cables and insulators and primary cutout with a zinc-oxide element to protect transformers have reduced the damage by direct lightning strikes. However, the failure rate of lightning arrester elements used in these power distribution systems is increasing. In this study, we evaluated the failure risk of lightning arrester elements installed on utility poles based on the probability of lightning strikes exceeding the energy tolerance of each surge arrester element. As a result, when the insulators on a pole are unprotected, the elements of arresters installed on the poles adjacent to it on its either side and supporting the same phase line will have the highest failure risk.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信