{"title":"基于委内瑞拉CVG - EDELCA Gurn电厂阶梯lp变压器绝缘和机械状况评估的可靠性研究","authors":"J. Mendoza","doi":"10.1109/TDCLA.2006.311462","DOIUrl":null,"url":null,"abstract":"For CVG EDELCA, reliability of power transformers is a very important matter for its power system performance. Taking in consideration that at Guri hydro power plant there are power transformers older than twenty years old, it was decided to select a group of step-up transformers for evaluation of insulation and mechanical conditions based on: dissolved gas analysis (DGA), tests of oil, and electric tests, for the last five years. Due to an incipient fault condition detected by DGA, a program of off-line tests on a group of three-phase and singlephase transformers of Guri power plant was scheduled in cooperation with Hydro Quebec International experts. Frequency response stray losses, frequency response analysis, recovered voltage measurement and dissipation factor versus frequency tests were applied on each selected transformer. As a result of the investigation, it was found that mechanical and insulation conditions were good for most of these transformers","PeriodicalId":406067,"journal":{"name":"2006 IEEE/PES Transmission & Distribution Conference and Exposition: Latin America","volume":"14 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2006-08-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Reliability Based On Evaluation of Insulation and Mechanical Conditions of Step-Lp Transformers of Gurn Power Plant at CVG EDELCA in Venezuela\",\"authors\":\"J. Mendoza\",\"doi\":\"10.1109/TDCLA.2006.311462\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"For CVG EDELCA, reliability of power transformers is a very important matter for its power system performance. Taking in consideration that at Guri hydro power plant there are power transformers older than twenty years old, it was decided to select a group of step-up transformers for evaluation of insulation and mechanical conditions based on: dissolved gas analysis (DGA), tests of oil, and electric tests, for the last five years. Due to an incipient fault condition detected by DGA, a program of off-line tests on a group of three-phase and singlephase transformers of Guri power plant was scheduled in cooperation with Hydro Quebec International experts. Frequency response stray losses, frequency response analysis, recovered voltage measurement and dissipation factor versus frequency tests were applied on each selected transformer. As a result of the investigation, it was found that mechanical and insulation conditions were good for most of these transformers\",\"PeriodicalId\":406067,\"journal\":{\"name\":\"2006 IEEE/PES Transmission & Distribution Conference and Exposition: Latin America\",\"volume\":\"14 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2006-08-01\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2006 IEEE/PES Transmission & Distribution Conference and Exposition: Latin America\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/TDCLA.2006.311462\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2006 IEEE/PES Transmission & Distribution Conference and Exposition: Latin America","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/TDCLA.2006.311462","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

对于CVG EDELCA来说,电力变压器的可靠性是影响其电力系统性能的重要因素。考虑到古里水电站有超过20年的电力变压器,决定在过去5年里,根据溶解气体分析(DGA)、油测试和电气测试,选择一组升压变压器进行绝缘和机械条件评估。由于DGA检测到的早期故障状态,与魁北克水电国际专家合作,对古里电厂的一组三相和单相变压器进行了脱机测试。对所选变压器进行了频率响应杂散损耗、频率响应分析、恢复电压测量和耗散系数随频率的测试。调查结果发现,大多数变压器的机械和绝缘条件良好
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Reliability Based On Evaluation of Insulation and Mechanical Conditions of Step-Lp Transformers of Gurn Power Plant at CVG EDELCA in Venezuela
For CVG EDELCA, reliability of power transformers is a very important matter for its power system performance. Taking in consideration that at Guri hydro power plant there are power transformers older than twenty years old, it was decided to select a group of step-up transformers for evaluation of insulation and mechanical conditions based on: dissolved gas analysis (DGA), tests of oil, and electric tests, for the last five years. Due to an incipient fault condition detected by DGA, a program of off-line tests on a group of three-phase and singlephase transformers of Guri power plant was scheduled in cooperation with Hydro Quebec International experts. Frequency response stray losses, frequency response analysis, recovered voltage measurement and dissipation factor versus frequency tests were applied on each selected transformer. As a result of the investigation, it was found that mechanical and insulation conditions were good for most of these transformers
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信