{"title":"规定和装载铸造树脂变压器","authors":"L. W. Pierce","doi":"10.1109/PAPCON.1992.186285","DOIUrl":null,"url":null,"abstract":"The thermal considerations in specifying and loading cast-resin transformers are presented. The considerations are based on conclusions reached from performing thermal tests on a 2000 kVA cast-resin transformer with embedded thermocouples. It is argued that specifications should require that the correct insulation temperature class be applied to individual windings and that hottest spot temperatures do not exceed this insulation temperature class at rated self-cooled and forced air kVA. Specifications should also require calculation of hottest spot temperature rises using mathematical models verified by thermal tests on a prototype transformer representative of the design family. The loading back test method is shown to give higher hottest spot temperature rises than expected from the short circuit test method. A method to correct the data to determine the hottest spot temperature rise using the short circuit test method is discussed. A specification form is suggested and loading equations are presented to allow predictions of loading capability and comparisons of competitive designs.<<ETX>>","PeriodicalId":174734,"journal":{"name":"Conference Record on Pulp and Paper Industry Technical Conference","volume":"15 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"1992-06-08","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"19","resultStr":"{\"title\":\"Specifying and loading cast-resin transformers\",\"authors\":\"L. W. Pierce\",\"doi\":\"10.1109/PAPCON.1992.186285\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"The thermal considerations in specifying and loading cast-resin transformers are presented. The considerations are based on conclusions reached from performing thermal tests on a 2000 kVA cast-resin transformer with embedded thermocouples. It is argued that specifications should require that the correct insulation temperature class be applied to individual windings and that hottest spot temperatures do not exceed this insulation temperature class at rated self-cooled and forced air kVA. Specifications should also require calculation of hottest spot temperature rises using mathematical models verified by thermal tests on a prototype transformer representative of the design family. The loading back test method is shown to give higher hottest spot temperature rises than expected from the short circuit test method. A method to correct the data to determine the hottest spot temperature rise using the short circuit test method is discussed. A specification form is suggested and loading equations are presented to allow predictions of loading capability and comparisons of competitive designs.<<ETX>>\",\"PeriodicalId\":174734,\"journal\":{\"name\":\"Conference Record on Pulp and Paper Industry Technical Conference\",\"volume\":\"15 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"1992-06-08\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"19\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Conference Record on Pulp and Paper Industry Technical Conference\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/PAPCON.1992.186285\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Conference Record on Pulp and Paper Industry Technical Conference","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/PAPCON.1992.186285","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 19

摘要

介绍了浇注树脂变压器选型和加载时的热因素。这些考虑是基于对带有嵌入式热电偶的2000 kVA铸造树脂变压器进行热测试得出的结论。有人认为,规范应该要求对单个绕组应用正确的绝缘温度等级,并且在额定自冷和强制空气千伏安时,最热点温度不超过该绝缘温度等级。规范还应要求使用数学模型计算最热点温升,该数学模型已在具有设计系列代表性的原型变压器上进行热试验验证。结果表明,反向加载试验方法比短路试验方法给出的最热点温升更高。讨论了用短路试验法测定最热点温升数据的修正方法。提出了一种规范形式,并提出了载荷方程,以便预测载荷能力和比较竞争设计
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Specifying and loading cast-resin transformers
The thermal considerations in specifying and loading cast-resin transformers are presented. The considerations are based on conclusions reached from performing thermal tests on a 2000 kVA cast-resin transformer with embedded thermocouples. It is argued that specifications should require that the correct insulation temperature class be applied to individual windings and that hottest spot temperatures do not exceed this insulation temperature class at rated self-cooled and forced air kVA. Specifications should also require calculation of hottest spot temperature rises using mathematical models verified by thermal tests on a prototype transformer representative of the design family. The loading back test method is shown to give higher hottest spot temperature rises than expected from the short circuit test method. A method to correct the data to determine the hottest spot temperature rise using the short circuit test method is discussed. A specification form is suggested and loading equations are presented to allow predictions of loading capability and comparisons of competitive designs.<>
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信