用快速伽辽金矩法计算埋地电网和棒接地系统的地表面电压

Y. Chow, M. M. Elsherbiny, M. Salama
{"title":"用快速伽辽金矩法计算埋地电网和棒接地系统的地表面电压","authors":"Y. Chow, M. M. Elsherbiny, M. Salama","doi":"10.1109/CCECE.1995.526292","DOIUrl":null,"url":null,"abstract":"The fast Galerkin's moment method is used to calculate the resistance and the surface voltages of power network grounding systems which consist of a grid and rodbed. Each conductor in the grounding system is considered as one segment. The outgoing current from each conductor is assumed to be uniform along the conductor. The accuracy of the resistance calculation is very high. However, for surface voltage calculations, the voltage at the boundary has to be satisfied to yield high accuracy. In the present paper, the authors have proved that no more than two extra segments at the end of each conductor are needed to correct for the assumed current distribution. This modification yielded accurate surface voltage, with average error <5%.","PeriodicalId":158581,"journal":{"name":"Proceedings 1995 Canadian Conference on Electrical and Computer Engineering","volume":"21 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"1995-09-05","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"6","resultStr":"{\"title\":\"Earth surface voltages at a grounding system of buried grid and rods from the fast Galerkin's moment method\",\"authors\":\"Y. Chow, M. M. Elsherbiny, M. Salama\",\"doi\":\"10.1109/CCECE.1995.526292\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"The fast Galerkin's moment method is used to calculate the resistance and the surface voltages of power network grounding systems which consist of a grid and rodbed. Each conductor in the grounding system is considered as one segment. The outgoing current from each conductor is assumed to be uniform along the conductor. The accuracy of the resistance calculation is very high. However, for surface voltage calculations, the voltage at the boundary has to be satisfied to yield high accuracy. In the present paper, the authors have proved that no more than two extra segments at the end of each conductor are needed to correct for the assumed current distribution. This modification yielded accurate surface voltage, with average error <5%.\",\"PeriodicalId\":158581,\"journal\":{\"name\":\"Proceedings 1995 Canadian Conference on Electrical and Computer Engineering\",\"volume\":\"21 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"1995-09-05\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"6\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Proceedings 1995 Canadian Conference on Electrical and Computer Engineering\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/CCECE.1995.526292\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Proceedings 1995 Canadian Conference on Electrical and Computer Engineering","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/CCECE.1995.526292","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 6

摘要

采用快速伽辽金矩法计算了电网接地系统的电阻和表面电压。接地系统中的每根导线都看作一段。假定每根导体的输出电流沿导体方向均匀。电阻的计算精度很高。然而,对于表面电压计算,必须满足边界处的电压才能获得较高的精度。在本文中,作者已经证明,在每个导体的末端不需要超过两个额外的段来校正假设的电流分布。这种改进产生了精确的表面电压,平均误差<5%。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Earth surface voltages at a grounding system of buried grid and rods from the fast Galerkin's moment method
The fast Galerkin's moment method is used to calculate the resistance and the surface voltages of power network grounding systems which consist of a grid and rodbed. Each conductor in the grounding system is considered as one segment. The outgoing current from each conductor is assumed to be uniform along the conductor. The accuracy of the resistance calculation is very high. However, for surface voltage calculations, the voltage at the boundary has to be satisfied to yield high accuracy. In the present paper, the authors have proved that no more than two extra segments at the end of each conductor are needed to correct for the assumed current distribution. This modification yielded accurate surface voltage, with average error <5%.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信