静态同步补偿器(STATCOM)增强电力系统传输

I. O. Ozioko, Chinweike Okoli, N. G. Ajah, N. S. Ugwuanyi
{"title":"静态同步补偿器(STATCOM)增强电力系统传输","authors":"I. O. Ozioko, Chinweike Okoli, N. G. Ajah, N. S. Ugwuanyi","doi":"10.1109/PowerAfrica.2019.8928629","DOIUrl":null,"url":null,"abstract":"Flexible Alternating Current Transmission System (FACTS) recently has proved to be economical with high efficiency in stabilizing electrical power and voltage of power systems without investing on establishing new network. However FACTS performance depends largely on it’s optimal location in the network. This work has investigated the contribution of STATCOM to the performance of 28-bus, 330kV Nigeria power system. The results were presented for both base case and after the compensation using PSSE software. Base case and after the application of 3 X 100MVA STATCOM recorded a respective power loss of 91.28MW and 71.07MW which shows 20.21% reduction in power loss. Five buses (New Haven, Onitsha, Gombe, Jos and Kano) recorded (0.8580, 0.8833, 0.7376, 0.8875, and 0.8847) p.u respectively which fell outside the voltage limit of ±5% used.The buses were respectively improved to 1.0 p.u after compensation. Our results show better improvement compared to previous work on the same network.","PeriodicalId":308661,"journal":{"name":"2019 IEEE PES/IAS PowerAfrica","volume":"83 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2019-08-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Enhancement of Power System Transmission Using Static Synchronous Compensator (STATCOM)\",\"authors\":\"I. O. Ozioko, Chinweike Okoli, N. G. Ajah, N. S. Ugwuanyi\",\"doi\":\"10.1109/PowerAfrica.2019.8928629\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Flexible Alternating Current Transmission System (FACTS) recently has proved to be economical with high efficiency in stabilizing electrical power and voltage of power systems without investing on establishing new network. However FACTS performance depends largely on it’s optimal location in the network. This work has investigated the contribution of STATCOM to the performance of 28-bus, 330kV Nigeria power system. The results were presented for both base case and after the compensation using PSSE software. Base case and after the application of 3 X 100MVA STATCOM recorded a respective power loss of 91.28MW and 71.07MW which shows 20.21% reduction in power loss. Five buses (New Haven, Onitsha, Gombe, Jos and Kano) recorded (0.8580, 0.8833, 0.7376, 0.8875, and 0.8847) p.u respectively which fell outside the voltage limit of ±5% used.The buses were respectively improved to 1.0 p.u after compensation. Our results show better improvement compared to previous work on the same network.\",\"PeriodicalId\":308661,\"journal\":{\"name\":\"2019 IEEE PES/IAS PowerAfrica\",\"volume\":\"83 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2019-08-01\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2019 IEEE PES/IAS PowerAfrica\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/PowerAfrica.2019.8928629\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2019 IEEE PES/IAS PowerAfrica","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/PowerAfrica.2019.8928629","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

近年来,柔性交流输电系统(FACTS)已被证明是一种经济高效的稳定电力和电压的输电系统,而无需投资新建电网。然而,FACTS性能在很大程度上取决于它在网络中的最佳位置。本文研究了STATCOM对尼日利亚28总线330kV电力系统性能的贡献。本文给出了用PSSE软件补偿基本情况和补偿后的结果。基准情况和应用3 × 100MVA后,STATCOM分别记录了91.28MW和71.07MW的功率损耗,功率损耗减少了20.21%。5个母线(纽黑文、奥尼沙、贡贝、乔斯和卡诺)分别记录了(0.8580、0.8833、0.7376、0.8875和0.8847)p.u,超出了使用的±5%的电压限制。补偿后的母线分别提高到1.0 p.u。我们的结果与之前在相同网络上的工作相比有了更好的改进。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Enhancement of Power System Transmission Using Static Synchronous Compensator (STATCOM)
Flexible Alternating Current Transmission System (FACTS) recently has proved to be economical with high efficiency in stabilizing electrical power and voltage of power systems without investing on establishing new network. However FACTS performance depends largely on it’s optimal location in the network. This work has investigated the contribution of STATCOM to the performance of 28-bus, 330kV Nigeria power system. The results were presented for both base case and after the compensation using PSSE software. Base case and after the application of 3 X 100MVA STATCOM recorded a respective power loss of 91.28MW and 71.07MW which shows 20.21% reduction in power loss. Five buses (New Haven, Onitsha, Gombe, Jos and Kano) recorded (0.8580, 0.8833, 0.7376, 0.8875, and 0.8847) p.u respectively which fell outside the voltage limit of ±5% used.The buses were respectively improved to 1.0 p.u after compensation. Our results show better improvement compared to previous work on the same network.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信