发射率和距离对高压设备热成像的影响

E. Neto, E. G. da Costa, M. Maia
{"title":"发射率和距离对高压设备热成像的影响","authors":"E. Neto, E. G. da Costa, M. Maia","doi":"10.1109/TDCLA.2006.311553","DOIUrl":null,"url":null,"abstract":"Thermographic inspection is a very safe and noninvasive monitoring technique, widely used in electrical substations and other power plants. Using an infrared camera, a thermal image can be obtained presenting abnormal heating regions on power equipment. The heating can indicate a failure on this system/equipment or an unusual electrical situation as over voltage or a poor contact. The precision of an infrared cam is based on some parameters that must be evaluated during the inspection. This work presents a study done with thermal images obtained from different materials. Different values measured when the correct emissivities and distance are not used during inspection and/or analysis of the thermal image. The results show that differences larger than 10% can be obtained for the temperature when the emissivity varies in a range from 1 to 0.75, which includes the value of 0.85 used for most companies","PeriodicalId":406067,"journal":{"name":"2006 IEEE/PES Transmission & Distribution Conference and Exposition: Latin America","volume":"4 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2006-08-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"20","resultStr":"{\"title\":\"Influence of Emissivity and Distance in High Voltage Equipments Thermal Imaging\",\"authors\":\"E. Neto, E. G. da Costa, M. Maia\",\"doi\":\"10.1109/TDCLA.2006.311553\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Thermographic inspection is a very safe and noninvasive monitoring technique, widely used in electrical substations and other power plants. Using an infrared camera, a thermal image can be obtained presenting abnormal heating regions on power equipment. The heating can indicate a failure on this system/equipment or an unusual electrical situation as over voltage or a poor contact. The precision of an infrared cam is based on some parameters that must be evaluated during the inspection. This work presents a study done with thermal images obtained from different materials. Different values measured when the correct emissivities and distance are not used during inspection and/or analysis of the thermal image. The results show that differences larger than 10% can be obtained for the temperature when the emissivity varies in a range from 1 to 0.75, which includes the value of 0.85 used for most companies\",\"PeriodicalId\":406067,\"journal\":{\"name\":\"2006 IEEE/PES Transmission & Distribution Conference and Exposition: Latin America\",\"volume\":\"4 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2006-08-01\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"20\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2006 IEEE/PES Transmission & Distribution Conference and Exposition: Latin America\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/TDCLA.2006.311553\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2006 IEEE/PES Transmission & Distribution Conference and Exposition: Latin America","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/TDCLA.2006.311553","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 20

摘要

热成像检测是一种非常安全、无创的监测技术,广泛应用于变电站和其他电厂。利用红外摄像机,可以获得电力设备异常发热区域的热图像。加热可以表示该系统/设备的故障或异常电气情况,如过电压或接触不良。红外凸轮的精度取决于在检测过程中必须评估的一些参数。这项工作提出了一项研究完成了从不同材料获得的热图像。在检查和/或热图像分析过程中,不使用正确的发射率和距离时测量的不同值。结果表明,当发射率在1 ~ 0.75范围内变化时,温度的差异大于10%,其中包括大多数公司使用的0.85值
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Influence of Emissivity and Distance in High Voltage Equipments Thermal Imaging
Thermographic inspection is a very safe and noninvasive monitoring technique, widely used in electrical substations and other power plants. Using an infrared camera, a thermal image can be obtained presenting abnormal heating regions on power equipment. The heating can indicate a failure on this system/equipment or an unusual electrical situation as over voltage or a poor contact. The precision of an infrared cam is based on some parameters that must be evaluated during the inspection. This work presents a study done with thermal images obtained from different materials. Different values measured when the correct emissivities and distance are not used during inspection and/or analysis of the thermal image. The results show that differences larger than 10% can be obtained for the temperature when the emissivity varies in a range from 1 to 0.75, which includes the value of 0.85 used for most companies
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信