电缆电容、发电机中性点接地和锯齿形变压器对同步发电机产生三次谐波的影响

M. Abdullah, N. H. Hamid, Z. Baharudin, M. A. Razak, M. Hisham
{"title":"电缆电容、发电机中性点接地和锯齿形变压器对同步发电机产生三次谐波的影响","authors":"M. Abdullah, N. H. Hamid, Z. Baharudin, M. A. Razak, M. Hisham","doi":"10.1109/ASSCC.2012.6523297","DOIUrl":null,"url":null,"abstract":"Salient pole synchronous generator is one of harmonic sources that causes various power system harmonic problem especially related to neutral. This paper aims to study the characteristics of third harmonic voltage and current from generator when connected to balanced load via cable, generator load connection with different generator neutral grounding resistor and generator load connection shunted by zig-zag transformer. Lab scale experiments have been conducted to vary all parameters related to cable capacitor and generator neutral grounding resistor under various combined resistive and inductive load. Cable capacitance which depends on cable length, size and number of parallel cable, combined with load impedance determines the third harmonic current magnitude. The presence of cable capacitance that interact with generator inductance resulted to series harmonic resonance at 9th and 15th harmonic order that causes high 9th and 15th harmonic current flowing between generator and cable capacitor. Generator neutral grounding resistor can effectively reduce the third harmonic in the phase and neutral. However care should be taken not to use very high generator neutral grounding resistor that can also restrict earth fault current that may pose problem to the sensitivity of earth fault protection system. Zig-zag transformer efficiently divert third harmonic current from generator to enter the load but high circulating third harmonic current between generator and zig-zag transformer may pose heating problem to the equipments.","PeriodicalId":341348,"journal":{"name":"2012 10th International Power & Energy Conference (IPEC)","volume":"37 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2012-11-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"2","resultStr":"{\"title\":\"The influence of cable capacitance, generator neutral grounding and zig-zag transformer to third harmonic produced by synchronous generator\",\"authors\":\"M. Abdullah, N. H. Hamid, Z. Baharudin, M. A. Razak, M. Hisham\",\"doi\":\"10.1109/ASSCC.2012.6523297\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Salient pole synchronous generator is one of harmonic sources that causes various power system harmonic problem especially related to neutral. This paper aims to study the characteristics of third harmonic voltage and current from generator when connected to balanced load via cable, generator load connection with different generator neutral grounding resistor and generator load connection shunted by zig-zag transformer. Lab scale experiments have been conducted to vary all parameters related to cable capacitor and generator neutral grounding resistor under various combined resistive and inductive load. Cable capacitance which depends on cable length, size and number of parallel cable, combined with load impedance determines the third harmonic current magnitude. The presence of cable capacitance that interact with generator inductance resulted to series harmonic resonance at 9th and 15th harmonic order that causes high 9th and 15th harmonic current flowing between generator and cable capacitor. Generator neutral grounding resistor can effectively reduce the third harmonic in the phase and neutral. However care should be taken not to use very high generator neutral grounding resistor that can also restrict earth fault current that may pose problem to the sensitivity of earth fault protection system. Zig-zag transformer efficiently divert third harmonic current from generator to enter the load but high circulating third harmonic current between generator and zig-zag transformer may pose heating problem to the equipments.\",\"PeriodicalId\":341348,\"journal\":{\"name\":\"2012 10th International Power & Energy Conference (IPEC)\",\"volume\":\"37 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2012-11-01\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"2\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2012 10th International Power & Energy Conference (IPEC)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/ASSCC.2012.6523297\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2012 10th International Power & Energy Conference (IPEC)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ASSCC.2012.6523297","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 2

摘要

凸极同步发电机是引起各种电力系统谐波问题尤其是中性点谐波问题的谐波源之一。本文旨在研究发电机与平衡负载通过电缆连接、发电机负载采用不同的发电机中性点接地电阻连接以及发电机负载采用锯齿形变压器并联连接时的三次谐波电压和电流特性。进行了实验室规模的实验,以改变各种组合电阻和感应负载下与电缆电容器和发电机中性点接地电阻有关的所有参数。电缆的电容取决于电缆的长度、尺寸和并联电缆的数量,再结合负载阻抗决定三次谐波电流的大小。电缆电容的存在与发电机电感的相互作用导致第9次和第15次谐波的串联谐振,导致发电机和电缆电容之间的第9次和第15次谐波电流大。发电机中性点接地电阻可以有效降低相和中性点的三次谐波。但是,应注意不要使用过高的发电机中性点接地电阻,这也会限制接地故障电流,从而可能对接地故障保护系统的灵敏度造成问题。锯齿形变压器能有效地将发电机的三次谐波电流引入负荷,但发电机与锯齿形变压器之间的高循环三次谐波电流会给设备带来发热问题。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
The influence of cable capacitance, generator neutral grounding and zig-zag transformer to third harmonic produced by synchronous generator
Salient pole synchronous generator is one of harmonic sources that causes various power system harmonic problem especially related to neutral. This paper aims to study the characteristics of third harmonic voltage and current from generator when connected to balanced load via cable, generator load connection with different generator neutral grounding resistor and generator load connection shunted by zig-zag transformer. Lab scale experiments have been conducted to vary all parameters related to cable capacitor and generator neutral grounding resistor under various combined resistive and inductive load. Cable capacitance which depends on cable length, size and number of parallel cable, combined with load impedance determines the third harmonic current magnitude. The presence of cable capacitance that interact with generator inductance resulted to series harmonic resonance at 9th and 15th harmonic order that causes high 9th and 15th harmonic current flowing between generator and cable capacitor. Generator neutral grounding resistor can effectively reduce the third harmonic in the phase and neutral. However care should be taken not to use very high generator neutral grounding resistor that can also restrict earth fault current that may pose problem to the sensitivity of earth fault protection system. Zig-zag transformer efficiently divert third harmonic current from generator to enter the load but high circulating third harmonic current between generator and zig-zag transformer may pose heating problem to the equipments.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信