膨胀涂层在核电厂安全系统电力电缆防火条件下的应用效率

O. Lebedchenko, S. Puzach, V. Zykov
{"title":"膨胀涂层在核电厂安全系统电力电缆防火条件下的应用效率","authors":"O. Lebedchenko, S. Puzach, V. Zykov","doi":"10.22227/0869-7493.2021.30.04.36-47","DOIUrl":null,"url":null,"abstract":"Introduction. The reliable operation of safety systems, that allows for the failure of no more than one safety system component, entails the safe shutdown and cool-down of an NPP reactor in the event of fire. However, the co-authors have not assessed the loss of performance by an insulating material, treated by intumescent compositions and used in the power cables of the above safety systems exposed to the simultaneous effect of various modes of fire and current loads.Goals and objectives. The purpose of the article is the theoretical assessment of the application efficiency of intumescent fire-retardant coatings in power cables used in the safety systems of nuclear power plants having water-cooled and water-moderated reactors under fire conditions. To achieve this goal, the temperature of the outer surface of the insulation and the intumescent fire-retardant coating was analyzed depending on the mode of fire. Theoretical foundations. A non-stationary one-dimensional heat transfer equation is solved to identify the temperature distribution inside the multilayered insulation and the fire-protection layer of a conductive core.Results and their discussion. The co-authors have identified dependences between the temperature of the outer surface of the insulation and the fire retarding composition of the three-core cable VVGng (A)-LS 3x2.5-0.66, on the one hand, and the temperature of the indoor gas environment for three standard modes of fire and one real fire mode. It is found that before the initiation of the process of destruction of the insulation material, the intumescence of the fire-retardant coating occurs only in case of a hydrocarbon fire. Under real fire conditions, the maximal insulation melting time before the initiation of intumescence of the fire-retardant coating at the minimal temperature of intumescence is 4.75 minutes, while the maximal time period from the initiation of destruction of the insulation material to the moment of the insulation melting is 6.0 minutes.Conclusions. An experimental or theoretical substantiation of parameters of intumescent fire retardants, performed using standard modes of fire, has proven the potential loss of operational properties by insulating materials of power cables, used in the safety systems of nuclear power plants, in case of a real fire. Therefore, it is necessary to establish a scientific rationale for the efficient use of fire retardants in the above cables with regard for the conditions of a real fire.","PeriodicalId":169739,"journal":{"name":"Pozharovzryvobezopasnost/Fire and Explosion Safety","volume":"36 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2021-09-14","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"1","resultStr":"{\"title\":\"The application efficiency of intumescent coatings for power cables of safety systems of nuclear power plants under fire conditions\",\"authors\":\"O. Lebedchenko, S. Puzach, V. Zykov\",\"doi\":\"10.22227/0869-7493.2021.30.04.36-47\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Introduction. The reliable operation of safety systems, that allows for the failure of no more than one safety system component, entails the safe shutdown and cool-down of an NPP reactor in the event of fire. However, the co-authors have not assessed the loss of performance by an insulating material, treated by intumescent compositions and used in the power cables of the above safety systems exposed to the simultaneous effect of various modes of fire and current loads.Goals and objectives. The purpose of the article is the theoretical assessment of the application efficiency of intumescent fire-retardant coatings in power cables used in the safety systems of nuclear power plants having water-cooled and water-moderated reactors under fire conditions. To achieve this goal, the temperature of the outer surface of the insulation and the intumescent fire-retardant coating was analyzed depending on the mode of fire. Theoretical foundations. A non-stationary one-dimensional heat transfer equation is solved to identify the temperature distribution inside the multilayered insulation and the fire-protection layer of a conductive core.Results and their discussion. The co-authors have identified dependences between the temperature of the outer surface of the insulation and the fire retarding composition of the three-core cable VVGng (A)-LS 3x2.5-0.66, on the one hand, and the temperature of the indoor gas environment for three standard modes of fire and one real fire mode. It is found that before the initiation of the process of destruction of the insulation material, the intumescence of the fire-retardant coating occurs only in case of a hydrocarbon fire. Under real fire conditions, the maximal insulation melting time before the initiation of intumescence of the fire-retardant coating at the minimal temperature of intumescence is 4.75 minutes, while the maximal time period from the initiation of destruction of the insulation material to the moment of the insulation melting is 6.0 minutes.Conclusions. An experimental or theoretical substantiation of parameters of intumescent fire retardants, performed using standard modes of fire, has proven the potential loss of operational properties by insulating materials of power cables, used in the safety systems of nuclear power plants, in case of a real fire. Therefore, it is necessary to establish a scientific rationale for the efficient use of fire retardants in the above cables with regard for the conditions of a real fire.\",\"PeriodicalId\":169739,\"journal\":{\"name\":\"Pozharovzryvobezopasnost/Fire and Explosion Safety\",\"volume\":\"36 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2021-09-14\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"1\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Pozharovzryvobezopasnost/Fire and Explosion Safety\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.22227/0869-7493.2021.30.04.36-47\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Pozharovzryvobezopasnost/Fire and Explosion Safety","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.22227/0869-7493.2021.30.04.36-47","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 1

摘要

介绍。安全系统的可靠运行,即允许不超过一个安全系统组件发生故障,需要在发生火灾时安全关闭和冷却核电站反应堆。然而,合著者没有评估绝缘材料的性能损失,这种绝缘材料经过膨胀成分处理,并用于上述安全系统的电力电缆,同时暴露于各种形式的火灾和电流负载的影响下。目标和目的。本文的目的是对膨胀型阻燃涂料在火灾条件下用于水冷、水慢化反应堆核电站安全系统的电力电缆中的应用效率进行理论评价。为实现这一目标,对保温材料和膨胀型防火涂料的外表面温度进行了不同着火方式的分析。的理论基础。通过求解一维非平稳传热方程,确定了导电铁芯多层绝缘层和防火层内部的温度分布。结果和讨论。共同作者已经确定了三芯电缆VVGng (A)-LS 3x2.5-0.66的绝缘外表面温度和阻燃成分与三种标准火灾模式和一种真实火灾模式下室内气体环境温度之间的依赖关系。研究发现,在绝缘材料破坏过程开始之前,阻燃涂层的膨胀只发生在碳氢化合物着火的情况下。在实际火灾条件下,在最低膨胀温度下,防火涂料在膨胀开始前的最大保温融化时间为4.75 min,而从保温材料开始破坏到保温融化时刻的最大时间为6.0 min。使用标准火灾模式对膨胀阻燃剂参数进行了实验或理论验证,证明了在实际火灾情况下,核电厂安全系统中使用的电力电缆的绝缘材料可能会损失操作性能。因此,有必要针对真实火灾的条件,为上述电缆中阻燃剂的有效使用建立科学的理论依据。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
The application efficiency of intumescent coatings for power cables of safety systems of nuclear power plants under fire conditions
Introduction. The reliable operation of safety systems, that allows for the failure of no more than one safety system component, entails the safe shutdown and cool-down of an NPP reactor in the event of fire. However, the co-authors have not assessed the loss of performance by an insulating material, treated by intumescent compositions and used in the power cables of the above safety systems exposed to the simultaneous effect of various modes of fire and current loads.Goals and objectives. The purpose of the article is the theoretical assessment of the application efficiency of intumescent fire-retardant coatings in power cables used in the safety systems of nuclear power plants having water-cooled and water-moderated reactors under fire conditions. To achieve this goal, the temperature of the outer surface of the insulation and the intumescent fire-retardant coating was analyzed depending on the mode of fire. Theoretical foundations. A non-stationary one-dimensional heat transfer equation is solved to identify the temperature distribution inside the multilayered insulation and the fire-protection layer of a conductive core.Results and their discussion. The co-authors have identified dependences between the temperature of the outer surface of the insulation and the fire retarding composition of the three-core cable VVGng (A)-LS 3x2.5-0.66, on the one hand, and the temperature of the indoor gas environment for three standard modes of fire and one real fire mode. It is found that before the initiation of the process of destruction of the insulation material, the intumescence of the fire-retardant coating occurs only in case of a hydrocarbon fire. Under real fire conditions, the maximal insulation melting time before the initiation of intumescence of the fire-retardant coating at the minimal temperature of intumescence is 4.75 minutes, while the maximal time period from the initiation of destruction of the insulation material to the moment of the insulation melting is 6.0 minutes.Conclusions. An experimental or theoretical substantiation of parameters of intumescent fire retardants, performed using standard modes of fire, has proven the potential loss of operational properties by insulating materials of power cables, used in the safety systems of nuclear power plants, in case of a real fire. Therefore, it is necessary to establish a scientific rationale for the efficient use of fire retardants in the above cables with regard for the conditions of a real fire.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信