Chunlei Zhao, Yingli Wei, Liqiang Sun, Jing Liu, Binbin Zhang, Haibin Chen, C. Tan
{"title":"基于逻辑信息融合的广域保护故障定位策略","authors":"Chunlei Zhao, Yingli Wei, Liqiang Sun, Jing Liu, Binbin Zhang, Haibin Chen, C. Tan","doi":"10.1109/CIEEC.2018.8745986","DOIUrl":null,"url":null,"abstract":"A new information fusion is proposed in this paper. First, the concept of distance protection rough setting depending on sensitivity is defined. On this basis, the startup information of each segment in regional power grid can be obtained, and the state matrix of connection of regional grid can be constructed combined with network topology and circuit breaker state. Then, according to this state matrix, the protection startup recorded matrix can be built and the wide area fault identification criterion can be constructed. This method simplifies the principle of setting coordination of local protection without the effect of information nonsynchronous. Furthermore, in the case of missing or incorrect startup information, the correctness of fault locating still remain. Finally, a certain electric network in Guizhou Province verify the correctness and feasibility of the proposed method.","PeriodicalId":329285,"journal":{"name":"2018 IEEE 2nd International Electrical and Energy Conference (CIEEC)","volume":"1 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2018-11-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Fault Location Strategy for Wide Area Protection Based on Logical Information Fusion\",\"authors\":\"Chunlei Zhao, Yingli Wei, Liqiang Sun, Jing Liu, Binbin Zhang, Haibin Chen, C. Tan\",\"doi\":\"10.1109/CIEEC.2018.8745986\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"A new information fusion is proposed in this paper. First, the concept of distance protection rough setting depending on sensitivity is defined. On this basis, the startup information of each segment in regional power grid can be obtained, and the state matrix of connection of regional grid can be constructed combined with network topology and circuit breaker state. Then, according to this state matrix, the protection startup recorded matrix can be built and the wide area fault identification criterion can be constructed. This method simplifies the principle of setting coordination of local protection without the effect of information nonsynchronous. Furthermore, in the case of missing or incorrect startup information, the correctness of fault locating still remain. Finally, a certain electric network in Guizhou Province verify the correctness and feasibility of the proposed method.\",\"PeriodicalId\":329285,\"journal\":{\"name\":\"2018 IEEE 2nd International Electrical and Energy Conference (CIEEC)\",\"volume\":\"1 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2018-11-01\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2018 IEEE 2nd International Electrical and Energy Conference (CIEEC)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/CIEEC.2018.8745986\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2018 IEEE 2nd International Electrical and Energy Conference (CIEEC)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/CIEEC.2018.8745986","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
Fault Location Strategy for Wide Area Protection Based on Logical Information Fusion
A new information fusion is proposed in this paper. First, the concept of distance protection rough setting depending on sensitivity is defined. On this basis, the startup information of each segment in regional power grid can be obtained, and the state matrix of connection of regional grid can be constructed combined with network topology and circuit breaker state. Then, according to this state matrix, the protection startup recorded matrix can be built and the wide area fault identification criterion can be constructed. This method simplifies the principle of setting coordination of local protection without the effect of information nonsynchronous. Furthermore, in the case of missing or incorrect startup information, the correctness of fault locating still remain. Finally, a certain electric network in Guizhou Province verify the correctness and feasibility of the proposed method.