在能源转换技术实验室设计避雷针系统

Herman Nawir, Muhammad Ruswandi Djalal, Sonong Sonong
{"title":"在能源转换技术实验室设计避雷针系统","authors":"Herman Nawir, Muhammad Ruswandi Djalal, Sonong Sonong","doi":"10.21070/JEEE-U.V2I2.1581","DOIUrl":null,"url":null,"abstract":"Lightning rods in the Laboratory of Energy and Protection Distribution System of Ujung Pandang State Polytechnic are not functioning properly so the resistance resistance tends to be large, this is not good for earthing. This problem can be overcome by remaking lightning rods on wet and dry soils. This activity was carried out to reduce the value of resistance resistance in connection with this, this activity was carried out by designing, assembling and collecting data carried out by testing, while data analysis was carried out by counting. Based on the results of the discussion concluded that the resistance resistance value obtained is smaller than the previous device. Evidenced by the results of the test where the resistance value on the rod electrode in dry conditions ranged from 1.56 to 2.40 Ohm while the previous tool ranged from 1.6 to 9.0 Ohm. Then for wet soil conditions that range from 0.45 to 1.29 Ohm, while the previous tool is around 1.8 - 5.25 Ohm","PeriodicalId":320287,"journal":{"name":"JEEE-U (Journal of Electrical and Electronic Engineering-UMSIDA)","volume":"105 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2018-10-25","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"4","resultStr":"{\"title\":\"Rancang Bangun Sistem Pentanahan Penangkal Petir Pada Tanah Basah dan Tanah Kering pada Laboratorium Teknik Konversi Energi\",\"authors\":\"Herman Nawir, Muhammad Ruswandi Djalal, Sonong Sonong\",\"doi\":\"10.21070/JEEE-U.V2I2.1581\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Lightning rods in the Laboratory of Energy and Protection Distribution System of Ujung Pandang State Polytechnic are not functioning properly so the resistance resistance tends to be large, this is not good for earthing. This problem can be overcome by remaking lightning rods on wet and dry soils. This activity was carried out to reduce the value of resistance resistance in connection with this, this activity was carried out by designing, assembling and collecting data carried out by testing, while data analysis was carried out by counting. Based on the results of the discussion concluded that the resistance resistance value obtained is smaller than the previous device. Evidenced by the results of the test where the resistance value on the rod electrode in dry conditions ranged from 1.56 to 2.40 Ohm while the previous tool ranged from 1.6 to 9.0 Ohm. Then for wet soil conditions that range from 0.45 to 1.29 Ohm, while the previous tool is around 1.8 - 5.25 Ohm\",\"PeriodicalId\":320287,\"journal\":{\"name\":\"JEEE-U (Journal of Electrical and Electronic Engineering-UMSIDA)\",\"volume\":\"105 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2018-10-25\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"4\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"JEEE-U (Journal of Electrical and Electronic Engineering-UMSIDA)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.21070/JEEE-U.V2I2.1581\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"JEEE-U (Journal of Electrical and Electronic Engineering-UMSIDA)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.21070/JEEE-U.V2I2.1581","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 4

摘要

乌戎潘塘国立理工学院能源与保护配电系统实验室避雷针工作不正常,导致电阻较大,不利于接地。这个问题可以通过在潮湿和干燥的土壤上重新制作避雷针来解决。该活动是为了降低与此相关的电阻值,该活动是通过设计,组装和收集数据进行的,通过测试进行,而数据分析是通过计数进行的。根据讨论的结果得出,所得到的电阻值比以往器件的电阻值要小。测试结果证明,在干燥条件下,杆电极上的电阻值范围为1.56至2.40欧姆,而以前的工具范围为1.6至9.0欧姆。然后在潮湿的土壤条件下,范围从0.45到1.29欧姆,而之前的工具约为1.8 - 5.25欧姆
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Rancang Bangun Sistem Pentanahan Penangkal Petir Pada Tanah Basah dan Tanah Kering pada Laboratorium Teknik Konversi Energi
Lightning rods in the Laboratory of Energy and Protection Distribution System of Ujung Pandang State Polytechnic are not functioning properly so the resistance resistance tends to be large, this is not good for earthing. This problem can be overcome by remaking lightning rods on wet and dry soils. This activity was carried out to reduce the value of resistance resistance in connection with this, this activity was carried out by designing, assembling and collecting data carried out by testing, while data analysis was carried out by counting. Based on the results of the discussion concluded that the resistance resistance value obtained is smaller than the previous device. Evidenced by the results of the test where the resistance value on the rod electrode in dry conditions ranged from 1.56 to 2.40 Ohm while the previous tool ranged from 1.6 to 9.0 Ohm. Then for wet soil conditions that range from 0.45 to 1.29 Ohm, while the previous tool is around 1.8 - 5.25 Ohm
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信