发电机定子3I0保护故障接地引起电缆保护原因分析

Xian Zhang, X. Jin, Huipeng Gao, Jun Qiao, Dong Wei, Kaijie Xing, Peiyuan Yang, G. Wang, Mingyong Zheng, Xianbo Li
{"title":"发电机定子3I0保护故障接地引起电缆保护原因分析","authors":"Xian Zhang, X. Jin, Huipeng Gao, Jun Qiao, Dong Wei, Kaijie Xing, Peiyuan Yang, G. Wang, Mingyong Zheng, Xianbo Li","doi":"10.1109/AUTEEE52864.2021.9668836","DOIUrl":null,"url":null,"abstract":"This paper analyzes the causes of stator 3I0 protection malfunction of QFW-15-2 brushless excitation synchronous generator, expounds the general process of accident treatment after the protection device operates, demonstrates the potential harm of grounding of power cable shielding layer protection grounding point above zero-sequence current transformer position, analyzes the causes of zero-sequence power transformer induced current caused by simultaneous grounding of both ends of single-core cable shielding layer, and further verifies the possibility of stator 3I0 protection malfunction caused by induced current of single-core cable shielding layer.","PeriodicalId":406050,"journal":{"name":"2021 IEEE 4th International Conference on Automation, Electronics and Electrical Engineering (AUTEEE)","volume":"41 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2021-11-19","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Cable Protection Caused by Grounding Cause Analysis of Generator Stator 3I0 Protection Malfunction\",\"authors\":\"Xian Zhang, X. Jin, Huipeng Gao, Jun Qiao, Dong Wei, Kaijie Xing, Peiyuan Yang, G. Wang, Mingyong Zheng, Xianbo Li\",\"doi\":\"10.1109/AUTEEE52864.2021.9668836\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"This paper analyzes the causes of stator 3I0 protection malfunction of QFW-15-2 brushless excitation synchronous generator, expounds the general process of accident treatment after the protection device operates, demonstrates the potential harm of grounding of power cable shielding layer protection grounding point above zero-sequence current transformer position, analyzes the causes of zero-sequence power transformer induced current caused by simultaneous grounding of both ends of single-core cable shielding layer, and further verifies the possibility of stator 3I0 protection malfunction caused by induced current of single-core cable shielding layer.\",\"PeriodicalId\":406050,\"journal\":{\"name\":\"2021 IEEE 4th International Conference on Automation, Electronics and Electrical Engineering (AUTEEE)\",\"volume\":\"41 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2021-11-19\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2021 IEEE 4th International Conference on Automation, Electronics and Electrical Engineering (AUTEEE)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/AUTEEE52864.2021.9668836\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2021 IEEE 4th International Conference on Automation, Electronics and Electrical Engineering (AUTEEE)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/AUTEEE52864.2021.9668836","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

分析了QFW-15-2型无刷励磁同步发电机定子3i保护故障的原因,阐述了保护装置运行后事故处理的一般过程,论证了电力电缆屏蔽层保护接地点在零序电流互感器位置以上接地的潜在危害;分析了单芯电缆屏蔽层两端同时接地产生零序电力变压器感应电流的原因,进一步验证了单芯电缆屏蔽层感应电流引起定子3I0保护故障的可能性。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Cable Protection Caused by Grounding Cause Analysis of Generator Stator 3I0 Protection Malfunction
This paper analyzes the causes of stator 3I0 protection malfunction of QFW-15-2 brushless excitation synchronous generator, expounds the general process of accident treatment after the protection device operates, demonstrates the potential harm of grounding of power cable shielding layer protection grounding point above zero-sequence current transformer position, analyzes the causes of zero-sequence power transformer induced current caused by simultaneous grounding of both ends of single-core cable shielding layer, and further verifies the possibility of stator 3I0 protection malfunction caused by induced current of single-core cable shielding layer.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信