发电机定子接地故障检测的差动保护分析

Christian H. Fernandez Alvarez, Carlota M. Pinos Veintimilla, F. Q. Palomeque
{"title":"发电机定子接地故障检测的差动保护分析","authors":"Christian H. Fernandez Alvarez, Carlota M. Pinos Veintimilla, F. Q. Palomeque","doi":"10.1109/ROPEC55836.2022.10018639","DOIUrl":null,"url":null,"abstract":"The analysis of the restricted earth fault differential protection based on the implementation of a low impedance scheme that allows the protection of 3.5 kVA generator windings using the overcurrent relay in differential structure is presented. The configuration and testing of the 7SJ85 overcurrent protection relay is mainly focused on the built-in ANSI 87N, REF protection function. The configuration, parameterization and operation of the elements that make up the protection system are performed using OMICRON's CMC 356 and the 7SJ85 relay with their respective application software Test Universe and Digsi 5. The values used for the tests are based on the short-circuit analysis applying the IEC 60909 standard and the Complete method (equivalent to Thevenin), which were calculated and simulated in MatLab and DigSilent software respectively.","PeriodicalId":237392,"journal":{"name":"2022 IEEE International Autumn Meeting on Power, Electronics and Computing (ROPEC)","volume":"6 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2022-11-09","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"1","resultStr":"{\"title\":\"Differential Protection Analisys For Detection Of Ground Faults On the Generator Stator\",\"authors\":\"Christian H. Fernandez Alvarez, Carlota M. Pinos Veintimilla, F. Q. Palomeque\",\"doi\":\"10.1109/ROPEC55836.2022.10018639\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"The analysis of the restricted earth fault differential protection based on the implementation of a low impedance scheme that allows the protection of 3.5 kVA generator windings using the overcurrent relay in differential structure is presented. The configuration and testing of the 7SJ85 overcurrent protection relay is mainly focused on the built-in ANSI 87N, REF protection function. The configuration, parameterization and operation of the elements that make up the protection system are performed using OMICRON's CMC 356 and the 7SJ85 relay with their respective application software Test Universe and Digsi 5. The values used for the tests are based on the short-circuit analysis applying the IEC 60909 standard and the Complete method (equivalent to Thevenin), which were calculated and simulated in MatLab and DigSilent software respectively.\",\"PeriodicalId\":237392,\"journal\":{\"name\":\"2022 IEEE International Autumn Meeting on Power, Electronics and Computing (ROPEC)\",\"volume\":\"6 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2022-11-09\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"1\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2022 IEEE International Autumn Meeting on Power, Electronics and Computing (ROPEC)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/ROPEC55836.2022.10018639\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2022 IEEE International Autumn Meeting on Power, Electronics and Computing (ROPEC)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ROPEC55836.2022.10018639","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 1

摘要

提出了一种利用过流继电器保护3.5 kVA发电机绕组的低阻抗保护方案,分析了基于该方案的限制接地故障差动保护。7SJ85过流保护继电器的配置和测试主要集中在其内置的ANSI 87N、REF保护功能上。组成保护系统的元件的配置、参数化和操作使用OMICRON的CMC 356和7SJ85继电器,以及各自的应用软件Test Universe和Digsi 5。测试所使用的数值是基于采用IEC 60909标准和Complete方法(相当于Thevenin)进行的短路分析,分别在MatLab和DigSilent软件中进行计算和仿真。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Differential Protection Analisys For Detection Of Ground Faults On the Generator Stator
The analysis of the restricted earth fault differential protection based on the implementation of a low impedance scheme that allows the protection of 3.5 kVA generator windings using the overcurrent relay in differential structure is presented. The configuration and testing of the 7SJ85 overcurrent protection relay is mainly focused on the built-in ANSI 87N, REF protection function. The configuration, parameterization and operation of the elements that make up the protection system are performed using OMICRON's CMC 356 and the 7SJ85 relay with their respective application software Test Universe and Digsi 5. The values used for the tests are based on the short-circuit analysis applying the IEC 60909 standard and the Complete method (equivalent to Thevenin), which were calculated and simulated in MatLab and DigSilent software respectively.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信