800kV断路器开闭动作对合闸电阻电磁应力分布特性的影响及抑制措施分析

Yanyan Bao, Kang Liu, Feng Wang, Dingjun Wen, Guangdong Zhang, Jiaqi Li
{"title":"800kV断路器开闭动作对合闸电阻电磁应力分布特性的影响及抑制措施分析","authors":"Yanyan Bao, Kang Liu, Feng Wang, Dingjun Wen, Guangdong Zhang, Jiaqi Li","doi":"10.1109/AEES56284.2022.10079289","DOIUrl":null,"url":null,"abstract":"The Pre-insertion Resistors of the 800kV circuit breaker is mainly used to suppress the closing inrush current and operating overvoltage of the circuit breaker during the closing process. However, due to the special application environment of the circuit breaker, the abnormal rate of the closing resistance of the AC filter field is relatively high. The change of the internal field strength of the circuit breaker under several conditions of breakage of resistors in different positions and sizes, cracks inside and outside the resistors, and falling of fragments of the resistors are analyzed, and the stress changes of the resistors during the opening and closing process are also analyzed., combined with the analysis results, a vibration reduction measure of adding a pure aluminum transition sheet between each two resistor sheets is proposed. The research results show that when there is a crack on the inner ring surface of the resistor sheet (width about 1mm and length about 25mm), the electric field distribution around it The influence is very small. When there is a crack on the outer surface of the resistor sheet (width of about 1mm and length of about 25mm), it will have a certain influence on the distribution of the surrounding field strength, but the effect is limited and will not cause a significant change in the field strength; larger damaged fragments (length 50mm), the internal field strength will be distorted when dropped, especially the field strength around the falling debris is seriously distorted, up to 94kV/cm, which will lead to an abnormal increase in the local field strength and cause breakdown. At the same time, there are stress concentration points on the inner hole edge and outer edge of the resistor sheet, which are also weak points of force. The results of this paper can provide a reference for the operation and maintenance of 750kV circuit breakers to avoid failures during operation.","PeriodicalId":227496,"journal":{"name":"2022 3rd International Conference on Advanced Electrical and Energy Systems (AEES)","volume":"1 20","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2022-09-23","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Analysis of the Influence of 800kV Circuit Breaker Opening and Closing Action on the Electromagnetic-stress Distribution Characteristics of Closing Resistance and Its Suppression Measures\",\"authors\":\"Yanyan Bao, Kang Liu, Feng Wang, Dingjun Wen, Guangdong Zhang, Jiaqi Li\",\"doi\":\"10.1109/AEES56284.2022.10079289\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"The Pre-insertion Resistors of the 800kV circuit breaker is mainly used to suppress the closing inrush current and operating overvoltage of the circuit breaker during the closing process. However, due to the special application environment of the circuit breaker, the abnormal rate of the closing resistance of the AC filter field is relatively high. The change of the internal field strength of the circuit breaker under several conditions of breakage of resistors in different positions and sizes, cracks inside and outside the resistors, and falling of fragments of the resistors are analyzed, and the stress changes of the resistors during the opening and closing process are also analyzed., combined with the analysis results, a vibration reduction measure of adding a pure aluminum transition sheet between each two resistor sheets is proposed. The research results show that when there is a crack on the inner ring surface of the resistor sheet (width about 1mm and length about 25mm), the electric field distribution around it The influence is very small. When there is a crack on the outer surface of the resistor sheet (width of about 1mm and length of about 25mm), it will have a certain influence on the distribution of the surrounding field strength, but the effect is limited and will not cause a significant change in the field strength; larger damaged fragments (length 50mm), the internal field strength will be distorted when dropped, especially the field strength around the falling debris is seriously distorted, up to 94kV/cm, which will lead to an abnormal increase in the local field strength and cause breakdown. At the same time, there are stress concentration points on the inner hole edge and outer edge of the resistor sheet, which are also weak points of force. The results of this paper can provide a reference for the operation and maintenance of 750kV circuit breakers to avoid failures during operation.\",\"PeriodicalId\":227496,\"journal\":{\"name\":\"2022 3rd International Conference on Advanced Electrical and Energy Systems (AEES)\",\"volume\":\"1 20\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2022-09-23\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2022 3rd International Conference on Advanced Electrical and Energy Systems (AEES)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/AEES56284.2022.10079289\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2022 3rd International Conference on Advanced Electrical and Energy Systems (AEES)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/AEES56284.2022.10079289","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

800kV断路器的预插电阻主要用于抑制断路器合闸过程中的合闸涌流和工作过电压。但是,由于断路器的特殊应用环境,交流滤波场的合闸电阻异常率比较高。分析了电阻器在不同位置、不同尺寸的电阻器破损、电阻器内外出现裂纹、电阻器碎片掉落等几种情况下,断路器内部场强的变化情况,并分析了电阻器在开闭过程中的应力变化情况。,结合分析结果,提出了在两个电阻片之间添加纯铝过渡片的减振措施。研究结果表明,当电阻片的内环表面(宽度约1mm,长度约25mm)存在裂纹时,其周围的电场分布对裂纹的影响很小。当电阻器片的外表面出现裂纹(宽度约1mm,长度约25mm)时,会对周围场强的分布产生一定的影响,但影响有限,不会引起场强的明显变化;较大的破损碎片(长度50mm),掉落时内部场强会发生畸变,尤其是掉落碎片周围的场强畸变严重,可达94kV/cm,会导致局部场强异常增加而引起击穿。同时,电阻器片的内孔边缘和外缘有应力集中点,也是受力的薄弱点。本文的研究结果可为750kV断路器的运行维护提供参考,避免断路器在运行过程中出现故障。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Analysis of the Influence of 800kV Circuit Breaker Opening and Closing Action on the Electromagnetic-stress Distribution Characteristics of Closing Resistance and Its Suppression Measures
The Pre-insertion Resistors of the 800kV circuit breaker is mainly used to suppress the closing inrush current and operating overvoltage of the circuit breaker during the closing process. However, due to the special application environment of the circuit breaker, the abnormal rate of the closing resistance of the AC filter field is relatively high. The change of the internal field strength of the circuit breaker under several conditions of breakage of resistors in different positions and sizes, cracks inside and outside the resistors, and falling of fragments of the resistors are analyzed, and the stress changes of the resistors during the opening and closing process are also analyzed., combined with the analysis results, a vibration reduction measure of adding a pure aluminum transition sheet between each two resistor sheets is proposed. The research results show that when there is a crack on the inner ring surface of the resistor sheet (width about 1mm and length about 25mm), the electric field distribution around it The influence is very small. When there is a crack on the outer surface of the resistor sheet (width of about 1mm and length of about 25mm), it will have a certain influence on the distribution of the surrounding field strength, but the effect is limited and will not cause a significant change in the field strength; larger damaged fragments (length 50mm), the internal field strength will be distorted when dropped, especially the field strength around the falling debris is seriously distorted, up to 94kV/cm, which will lead to an abnormal increase in the local field strength and cause breakdown. At the same time, there are stress concentration points on the inner hole edge and outer edge of the resistor sheet, which are also weak points of force. The results of this paper can provide a reference for the operation and maintenance of 750kV circuit breakers to avoid failures during operation.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信