{"title":"重复故障对熔断器特性的影响[包括讨论]","authors":"R. E. Riebs","doi":"10.1109/AIEEPAS.1952.4498582","DOIUrl":null,"url":null,"abstract":"With the introduction of the automatic circuit recloser, it became necessary to consider the effects of a fault current repeated several times at short intervals upon the time current characteristics of a fuse link. The link goes through several sequences of heating and cooling, each application of the fault bringing a higher end temperature. This paper describes a study of the exact manner in which a fuse link behaves when such a series of repeated faults is impressed upon it. The temperature of the fuse link is traced as the fuse heats with the application of a fault, cools after the first interruption, and is brought to still higher temperatures by succeeding applications of the fault. In this manner it is possible to determine whether a fuse will blow or be damaged by a given sequence of repeated faults, or remain undamaged. Information also is presented for determining how co-ordination is affected by preloading and ambient temperature variations. A feature of this study is that damage to the link can be predicted for faults of insufficient duration to cause blowing. Equipment used for the tests is described.","PeriodicalId":118797,"journal":{"name":"Transactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and Systems","volume":"7 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2008-05-07","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"The Effect of Repeated Faults on Fuse Characteristics [includes discussion]\",\"authors\":\"R. E. Riebs\",\"doi\":\"10.1109/AIEEPAS.1952.4498582\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"With the introduction of the automatic circuit recloser, it became necessary to consider the effects of a fault current repeated several times at short intervals upon the time current characteristics of a fuse link. The link goes through several sequences of heating and cooling, each application of the fault bringing a higher end temperature. This paper describes a study of the exact manner in which a fuse link behaves when such a series of repeated faults is impressed upon it. The temperature of the fuse link is traced as the fuse heats with the application of a fault, cools after the first interruption, and is brought to still higher temperatures by succeeding applications of the fault. In this manner it is possible to determine whether a fuse will blow or be damaged by a given sequence of repeated faults, or remain undamaged. Information also is presented for determining how co-ordination is affected by preloading and ambient temperature variations. A feature of this study is that damage to the link can be predicted for faults of insufficient duration to cause blowing. Equipment used for the tests is described.\",\"PeriodicalId\":118797,\"journal\":{\"name\":\"Transactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and Systems\",\"volume\":\"7 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2008-05-07\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Transactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and Systems\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/AIEEPAS.1952.4498582\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Transactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and Systems","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/AIEEPAS.1952.4498582","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
The Effect of Repeated Faults on Fuse Characteristics [includes discussion]
With the introduction of the automatic circuit recloser, it became necessary to consider the effects of a fault current repeated several times at short intervals upon the time current characteristics of a fuse link. The link goes through several sequences of heating and cooling, each application of the fault bringing a higher end temperature. This paper describes a study of the exact manner in which a fuse link behaves when such a series of repeated faults is impressed upon it. The temperature of the fuse link is traced as the fuse heats with the application of a fault, cools after the first interruption, and is brought to still higher temperatures by succeeding applications of the fault. In this manner it is possible to determine whether a fuse will blow or be damaged by a given sequence of repeated faults, or remain undamaged. Information also is presented for determining how co-ordination is affected by preloading and ambient temperature variations. A feature of this study is that damage to the link can be predicted for faults of insufficient duration to cause blowing. Equipment used for the tests is described.