Study of Soil Resistivity using Wenner Four Pin Method: Case Study

M. S. Sazali, C. Wooi, S. Arshad, T. Wong, Z. Abdul-Malek, H. Nabipour-Afrouzi
{"title":"Study of Soil Resistivity using Wenner Four Pin Method: Case Study","authors":"M. S. Sazali, C. Wooi, S. Arshad, T. Wong, Z. Abdul-Malek, H. Nabipour-Afrouzi","doi":"10.1109/PECon48942.2020.9314400","DOIUrl":null,"url":null,"abstract":"Soil resistivity is usually measured at the selected site either for new installation or in the existing grounding system. In this paper, soil resistivity test has been done to study the soil resistivity around the 33 kV substation according to IEEE 81-1983 standard. A factory site located in Kulim Hi-tech, Malaysia has been selected to research on the soil resistivity. The soil resistance measured in this study is then be calculated in using the soil resistivity formula. The soil resistivity shows that the longer the distance between rods, the lower the resistivity of soil due to larger soil volume. The lowest soil resistivity around the substation is 3.454 Ω.m, which is on the left side of the substation with a distance of 5 meters between the rods followed by front side with 15.71 Ω.m, right side with 34.243 Ω.m and backside with 45.239 Ω.m. While the highest soil resistivity is 176.306 Ω.m on the right side of the substation with a 2-meter distance between each rod.","PeriodicalId":6768,"journal":{"name":"2020 IEEE International Conference on Power and Energy (PECon)","volume":"219 1 1","pages":"386-391"},"PeriodicalIF":0.0000,"publicationDate":"2020-12-07","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2020 IEEE International Conference on Power and Energy (PECon)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/PECon48942.2020.9314400","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

Abstract

Soil resistivity is usually measured at the selected site either for new installation or in the existing grounding system. In this paper, soil resistivity test has been done to study the soil resistivity around the 33 kV substation according to IEEE 81-1983 standard. A factory site located in Kulim Hi-tech, Malaysia has been selected to research on the soil resistivity. The soil resistance measured in this study is then be calculated in using the soil resistivity formula. The soil resistivity shows that the longer the distance between rods, the lower the resistivity of soil due to larger soil volume. The lowest soil resistivity around the substation is 3.454 Ω.m, which is on the left side of the substation with a distance of 5 meters between the rods followed by front side with 15.71 Ω.m, right side with 34.243 Ω.m and backside with 45.239 Ω.m. While the highest soil resistivity is 176.306 Ω.m on the right side of the substation with a 2-meter distance between each rod.
用温纳四针法研究土壤电阻率:个案研究
土壤电阻率通常在新装置或现有接地系统的选定地点测量。本文根据IEEE 81-1983标准,对33kv变电站周围的土壤电阻率进行了试验研究。位于马来西亚Kulim高科技公司的一个工厂场地被选中进行土壤电阻率的研究。然后用土壤电阻率公式计算本研究测得的土壤电阻。土壤电阻率表明,杆距越长,土壤体积越大,土壤电阻率越低。变电站周围土壤电阻率最低为3.454 Ω。M,位于变电站左侧,杆距为5米,前面为15.71 Ω。M,右边是34.243 Ω。M和背面有45.239 Ω.m。土壤电阻率最高为176.306 Ω。M在变电站右侧,每根杆之间的距离为2米。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信