Depolarization Current Measurements on Field-Aged XLPE Cable Insulation

M. Abou-Dakka, A. Bulinski, S. Bamji, M. Selsjord
{"title":"Depolarization Current Measurements on Field-Aged XLPE Cable Insulation","authors":"M. Abou-Dakka, A. Bulinski, S. Bamji, M. Selsjord","doi":"10.1109/CEIDP.2008.4772809","DOIUrl":null,"url":null,"abstract":"Laboratory tests on field aged and unaged cables were performed using DC depolarization current measurements. Aged cables with water trees showed high dielectric losses and depolarization currents as compared with the reference, unaged cable. Both the area under the depolarization current waveform and dielectric loss factor, tandelta, increased with DC poling and the applied AC voltage, respectively. A new indicator of the insulation aging derived from the measured current is proposed to rate the degree of aging of cable insulation. This indicator increases with the poling field, and a DC poling voltage less than 50% of the nominal peak value of the cable operating voltage is sufficient to obtain reliable values. The cable insulation aging indicator could be a useful tool for monitoring the operating condition of cables in service and help utilities to develop cable replacement programs based on the actual state of the cable insulation conditions.","PeriodicalId":6381,"journal":{"name":"2008 Annual Report Conference on Electrical Insulation and Dielectric Phenomena","volume":"25 1","pages":"21-24"},"PeriodicalIF":0.0000,"publicationDate":"2008-10-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"6","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2008 Annual Report Conference on Electrical Insulation and Dielectric Phenomena","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/CEIDP.2008.4772809","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 6

Abstract

Laboratory tests on field aged and unaged cables were performed using DC depolarization current measurements. Aged cables with water trees showed high dielectric losses and depolarization currents as compared with the reference, unaged cable. Both the area under the depolarization current waveform and dielectric loss factor, tandelta, increased with DC poling and the applied AC voltage, respectively. A new indicator of the insulation aging derived from the measured current is proposed to rate the degree of aging of cable insulation. This indicator increases with the poling field, and a DC poling voltage less than 50% of the nominal peak value of the cable operating voltage is sufficient to obtain reliable values. The cable insulation aging indicator could be a useful tool for monitoring the operating condition of cables in service and help utilities to develop cable replacement programs based on the actual state of the cable insulation conditions.
场老化交联聚乙烯电缆绝缘去极化电流的测量
采用直流去极化电流测量方法对现场老化和未老化电缆进行了实验室测试。与未老化的参考电缆相比,带水树的老化电缆显示出较高的介电损耗和去极化电流。除极化电流波形下的面积和介质损耗因子δ分别随着直流极化和施加交流电压而增加。提出了一种由实测电流推导出的新的绝缘老化指标来评价电缆绝缘的老化程度。该指标随着极化场的增大而增大,当直流极化电压小于电缆工作电压标称峰值的50%时,即可获得可靠值。电缆绝缘老化指示器是监测在用电缆运行状况的有用工具,可以帮助电力公司根据电缆绝缘状况的实际情况制定电缆更换方案。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信