F. Komori, A. Kojima, M. Hikita, Y. Suzuoki, T. Mizutani
{"title":"Phase-resolved study on partial discharge for degradation diagnosis in polymeric insulating materials using model electrode system","authors":"F. Komori, A. Kojima, M. Hikita, Y. Suzuoki, T. Mizutani","doi":"10.1109/ICSD.1998.709248","DOIUrl":null,"url":null,"abstract":"Using MGI (metal-gap-insulator) and IGI (insulator-gap-insulator) electrode systems with 0.1 mm- or 4.0 mm-thick LDPE samples, we studied the temporal change of PD characteristics. The PD pattern and statistical parameter (PD inception phase) changed with aging time. The IGI electrode system showed a similar change in PD pattern with degradation to that of the MGI electrode system. The PDs in MGI electrodes with the 4.0 mm-thick sample showed new PD characteristics which were absent in the 0.1 mm-thick sample. This was attributed to pit formation just before breakdown. There results suggest the possibility of insulation diagnosis from the beginning to the last stage of PD degradation.","PeriodicalId":13148,"journal":{"name":"ICSD'98. Proceedings of the 1998 IEEE 6th International Conference on Conduction and Breakdown in Solid Dielectrics (Cat. No.98CH36132)","volume":"34 1","pages":"153-156"},"PeriodicalIF":0.0000,"publicationDate":"1998-06-22","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"6","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"ICSD'98. Proceedings of the 1998 IEEE 6th International Conference on Conduction and Breakdown in Solid Dielectrics (Cat. No.98CH36132)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ICSD.1998.709248","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 6
Abstract
Using MGI (metal-gap-insulator) and IGI (insulator-gap-insulator) electrode systems with 0.1 mm- or 4.0 mm-thick LDPE samples, we studied the temporal change of PD characteristics. The PD pattern and statistical parameter (PD inception phase) changed with aging time. The IGI electrode system showed a similar change in PD pattern with degradation to that of the MGI electrode system. The PDs in MGI electrodes with the 4.0 mm-thick sample showed new PD characteristics which were absent in the 0.1 mm-thick sample. This was attributed to pit formation just before breakdown. There results suggest the possibility of insulation diagnosis from the beginning to the last stage of PD degradation.