M. Judd, G. P. Cleary, C. J. Bennoch, J. Pearson, T. Breckenridge
{"title":"Power transformer monitoring using UHF sensors: site trials","authors":"M. Judd, G. P. Cleary, C. J. Bennoch, J. Pearson, T. Breckenridge","doi":"10.1109/ELINSL.2002.995899","DOIUrl":null,"url":null,"abstract":"Sensors operating in the ultra-high frequency (UHF) band have been used to detect internal discharges during site testing of a 1000 MVA oil-filled transformer. The transformer was operated at voltages exceeding normal levels by up to 15%. Two discharge sources were detected at both sensors using UHF test equipment. Discharge signals are analyzed in phase-resolved form and time-of-flight measurements are used to provide further information regarding their origin. The results indicate that the UHF method could prove very effective for transformer testing and online PD monitoring.","PeriodicalId":10532,"journal":{"name":"Conference Record of the the 2002 IEEE International Symposium on Electrical Insulation (Cat. No.02CH37316)","volume":"390 1","pages":"145-149"},"PeriodicalIF":0.0000,"publicationDate":"2002-04-07","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"25","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Conference Record of the the 2002 IEEE International Symposium on Electrical Insulation (Cat. No.02CH37316)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ELINSL.2002.995899","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 25
Abstract
Sensors operating in the ultra-high frequency (UHF) band have been used to detect internal discharges during site testing of a 1000 MVA oil-filled transformer. The transformer was operated at voltages exceeding normal levels by up to 15%. Two discharge sources were detected at both sensors using UHF test equipment. Discharge signals are analyzed in phase-resolved form and time-of-flight measurements are used to provide further information regarding their origin. The results indicate that the UHF method could prove very effective for transformer testing and online PD monitoring.