{"title":"Calculation and Analysis of The Radial Short-circuit Electromotive Force of The Converter Transformer Winding","authors":"Zhong-cheng Zhao, Guan Wang, Suxian Liu, Liangkai Wang, Hongbin Wu","doi":"10.1109/AEERO52475.2021.9708164","DOIUrl":null,"url":null,"abstract":"For a 530KV/406MVA single-phase dual-winding converter transformer, according to its actual operating circuit, set a three-phase short-circuit fault to obtain the maximum short-circuit current. The finite element software comsol is used to build a two-dimensional axisymmetric model of the transformer, the leakage magnetic density and radial short-circuit electromotive force of the high and low voltage windings are obtained, and the radial steady-state check of the converter transformer is performed. The calculation and analysis results show that the model and calculation method can realize the calculation of the radial short-circuit force of the windings of the converter transformer and the calculation of the radial mechanical strength.","PeriodicalId":6828,"journal":{"name":"2021 International Conference on Advanced Electrical Equipment and Reliable Operation (AEERO)","volume":"25 2 1","pages":"1-5"},"PeriodicalIF":0.0000,"publicationDate":"2021-10-15","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2021 International Conference on Advanced Electrical Equipment and Reliable Operation (AEERO)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/AEERO52475.2021.9708164","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0
Abstract
For a 530KV/406MVA single-phase dual-winding converter transformer, according to its actual operating circuit, set a three-phase short-circuit fault to obtain the maximum short-circuit current. The finite element software comsol is used to build a two-dimensional axisymmetric model of the transformer, the leakage magnetic density and radial short-circuit electromotive force of the high and low voltage windings are obtained, and the radial steady-state check of the converter transformer is performed. The calculation and analysis results show that the model and calculation method can realize the calculation of the radial short-circuit force of the windings of the converter transformer and the calculation of the radial mechanical strength.