The Characteristics of Winding Temperature for the Natural Ester Filled Transformer up to and Including 500 kVA

Byung-Seol Lee, J. Jeong, C. Park, I. Song
{"title":"The Characteristics of Winding Temperature for the Natural Ester Filled Transformer up to and Including 500 kVA","authors":"Byung-Seol Lee, J. Jeong, C. Park, I. Song","doi":"10.1109/CEIDP.2008.4772918","DOIUrl":null,"url":null,"abstract":"Because of environmental friendly and higher fire point, Natural ester fluids are widely used for transformer cooling materials. Natural ester has higher viscosity than that mineral oil. Top oil temperature and hottest temperature will be warmer when using natural ester fluid in transformers designed for conventional transformer oil. Although natural ester has less influence on deterioration of cellulose paper than mineral oil, an increased hottest temperature might have an effect on the aging of insulating paper in coil winding. When comparing natural ester with mineral oil at the same designed transformers up to 500 kVA. The deviation of hottest temperature between the two is increased with load. For preventing additional aging of insulation paper, design changes are required when substituting natural ester for conventional transformer oil.","PeriodicalId":6381,"journal":{"name":"2008 Annual Report Conference on Electrical Insulation and Dielectric Phenomena","volume":"112 1","pages":"115-117"},"PeriodicalIF":0.0000,"publicationDate":"2008-10-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"4","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2008 Annual Report Conference on Electrical Insulation and Dielectric Phenomena","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/CEIDP.2008.4772918","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 4

Abstract

Because of environmental friendly and higher fire point, Natural ester fluids are widely used for transformer cooling materials. Natural ester has higher viscosity than that mineral oil. Top oil temperature and hottest temperature will be warmer when using natural ester fluid in transformers designed for conventional transformer oil. Although natural ester has less influence on deterioration of cellulose paper than mineral oil, an increased hottest temperature might have an effect on the aging of insulating paper in coil winding. When comparing natural ester with mineral oil at the same designed transformers up to 500 kVA. The deviation of hottest temperature between the two is increased with load. For preventing additional aging of insulation paper, design changes are required when substituting natural ester for conventional transformer oil.
500kva及以下天然酯填充变压器绕组温度特性
天然酯流体因其环保、燃点高等优点,被广泛用作变压器冷却材料。天然酯的粘度比那种矿物油高。在常规变压器油中使用天然酯流体,会使变压器的最高油温和最高油温升高。虽然天然酯对纤维素纸劣化的影响小于矿物油,但在卷绕过程中,最高温度的升高可能会对绝缘纸的老化产生影响。将天然酯与矿物油在相同设计的500kva变压器上进行比较。两者之间的最高温偏差随着负荷的增加而增大。为了防止绝缘纸的额外老化,在用天然酯代替常规变压器油时需要改变设计。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信