Research on Key Parameters of Long-term Induced Withstand Voltage and Partial Discharge Test for ±800 kV Converter Transformer in Lingzhou and Interference Elimination of Partial Discharge

Xiu Zhou, Xin Yang, Xu-tao Wu, Tian Tian, W. Si, W. Chang, Xiaolin Zhao, Xingwang Wu, Xiuguang Li, Ninghui He
{"title":"Research on Key Parameters of Long-term Induced Withstand Voltage and Partial Discharge Test for ±800 kV Converter Transformer in Lingzhou and Interference Elimination of Partial Discharge","authors":"Xiu Zhou, Xin Yang, Xu-tao Wu, Tian Tian, W. Si, W. Chang, Xiaolin Zhao, Xingwang Wu, Xiuguang Li, Ninghui He","doi":"10.1109/AEERO52475.2021.9708309","DOIUrl":null,"url":null,"abstract":"During the tests of long-term induced withstand voltage on site and handover partial discharge for ± 800 kV UHV converter transformers in Lingzhou, in accordance with the requirements of the regulations and standards for the above tests, the differences between the two types of converter transformers with angle valve and star valve in the two tests were studied respectively. And the parameters of the configured test equipment were calculated and verified. Taking the converter transformer with star valve as an example, the paper elaborates in detail from the test principles, instruments used, parameter calculations and on-site tests, also summarizes the precautions of each link, verifies the applicability and generalization of the research, and provides methods for the interference elimination of the relevant partial discharge test in the electrification converter station with charged electrification.","PeriodicalId":6828,"journal":{"name":"2021 International Conference on Advanced Electrical Equipment and Reliable Operation (AEERO)","volume":"3 1","pages":"1-6"},"PeriodicalIF":0.0000,"publicationDate":"2021-10-15","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2021 International Conference on Advanced Electrical Equipment and Reliable Operation (AEERO)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/AEERO52475.2021.9708309","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

Abstract

During the tests of long-term induced withstand voltage on site and handover partial discharge for ± 800 kV UHV converter transformers in Lingzhou, in accordance with the requirements of the regulations and standards for the above tests, the differences between the two types of converter transformers with angle valve and star valve in the two tests were studied respectively. And the parameters of the configured test equipment were calculated and verified. Taking the converter transformer with star valve as an example, the paper elaborates in detail from the test principles, instruments used, parameter calculations and on-site tests, also summarizes the precautions of each link, verifies the applicability and generalization of the research, and provides methods for the interference elimination of the relevant partial discharge test in the electrification converter station with charged electrification.
陵州±800 kV换流变压器长期感应耐压和局部放电试验关键参数及局部放电干扰消除研究
在灵州±800 kV特高压换流变压器现场长期感应耐压和切换局部放电试验中,根据上述试验规程和标准的要求,分别研究了角阀和星阀两种型式换流变压器在两次试验中的差异。并对所配置的试验设备参数进行了计算和验证。本文以带星形阀的换流变压器为例,从试验原理、使用的仪器、参数计算和现场试验等方面进行了详细阐述,并总结了各环节的注意事项,验证了研究的适用性和通用性,为带电换流站相关局部放电试验的干扰消除提供了方法。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信