Investigation of Steady State Two-Phase Short Circuit Modes Of Phase-Shifting Autotransformer with Hexagon Scheme and with Adjusting Autotransformer

IF 0.3 Q4 ENERGY & FUELS
V. Bosneaga, V. Suslov
{"title":"Investigation of Steady State Two-Phase Short Circuit Modes Of Phase-Shifting Autotransformer with Hexagon Scheme and with Adjusting Autotransformer","authors":"V. Bosneaga, V. Suslov","doi":"10.52254/1857-0070.2023.1-57.05","DOIUrl":null,"url":null,"abstract":"The purpose of work is to investigate two - phase short-circuiting modes of new autotransformer FACT’s - type device and is intended for power systems flexible connection. The developed mathematical model contains the main phase-shifting and additional regulating autotransformers. The model allows studying of asymmetrical modes of such schemes, including the un-identical load connection in different phases of phase-shifting transformers. Visual vector diagrams of winding’s voltages, currents and relative magnetic fluxes of magnetic core legs for main and regulating autotransformers for the modes with two-phase short-circuiting with and without ground have been elaborated. It is shown that significant distortions of the polygon shape occurred. It is revealed that in two-phase short - circuiting mode without ground, and the loads identically connected in different phases, the relative magnetic fluxes of the legs of main and regulating autotransformers are asymmetrical, but their sum is zero, and the magnetic flux does not come out into surrounding space. Load currents in this mode contain only direct and reverse sequences components. When the load is un-identically connected in different phases, significant zero-sequence currents occur, and magnetic flux goes out into surrounding space. However, load currents do not contain symmetrical components of zero sequence. A similar analysis of two-phase short circuit modes with ground showed that even with the identical connection of the loads, there is zero sequence both in the magnetic fluxes and in the load currents. Moreover, zero sequence is present when the load is connected differently on the phases.","PeriodicalId":41974,"journal":{"name":"Problemele Energeticii Regionale","volume":null,"pages":null},"PeriodicalIF":0.3000,"publicationDate":"2023-02-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Problemele Energeticii Regionale","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.52254/1857-0070.2023.1-57.05","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q4","JCRName":"ENERGY & FUELS","Score":null,"Total":0}
引用次数: 0

Abstract

The purpose of work is to investigate two - phase short-circuiting modes of new autotransformer FACT’s - type device and is intended for power systems flexible connection. The developed mathematical model contains the main phase-shifting and additional regulating autotransformers. The model allows studying of asymmetrical modes of such schemes, including the un-identical load connection in different phases of phase-shifting transformers. Visual vector diagrams of winding’s voltages, currents and relative magnetic fluxes of magnetic core legs for main and regulating autotransformers for the modes with two-phase short-circuiting with and without ground have been elaborated. It is shown that significant distortions of the polygon shape occurred. It is revealed that in two-phase short - circuiting mode without ground, and the loads identically connected in different phases, the relative magnetic fluxes of the legs of main and regulating autotransformers are asymmetrical, but their sum is zero, and the magnetic flux does not come out into surrounding space. Load currents in this mode contain only direct and reverse sequences components. When the load is un-identically connected in different phases, significant zero-sequence currents occur, and magnetic flux goes out into surrounding space. However, load currents do not contain symmetrical components of zero sequence. A similar analysis of two-phase short circuit modes with ground showed that even with the identical connection of the loads, there is zero sequence both in the magnetic fluxes and in the load currents. Moreover, zero sequence is present when the load is connected differently on the phases.
六边形和可调自耦变压器移相自耦变压器稳态两相短路方式的研究
本工作的目的是研究新型自耦变压器FACT型装置的两相短路模式,旨在实现电力系统的柔性连接。所开发的数学模型包括主相移和附加调节自耦变压器。该模型允许研究此类方案的非对称模式,包括移相变压器不同相位中的不相同负载连接。阐述了主自耦变压器和调节自耦变压器在有地和无地两相短路模式下绕组电压、电流和磁芯腿相对磁通的可视化矢量图。结果表明,多边形发生了明显的畸变。结果表明,在无接地的两相短路模式下,不同相负载相同连接时,主变压器和调节变压器支路的相对磁通量是不对称的,但其总和为零,磁通量不会进入周围空间。此模式下的负载电流仅包含直接和反向序列分量。当负载在不同相位的连接不相同时,会出现显著的零序电流,磁通量会进入周围空间。然而,负载电流不包含零序对称分量。对两相接地短路模式的类似分析表明,即使负载连接相同,磁通量和负载电流也存在零序。此外,当负载在相位上不同地连接时,存在零序。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
CiteScore
0.70
自引率
33.30%
发文量
38
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信