External Leakage Current Separation to Determine Arrester Condition Due to Contamination

N. Novizon, Mondrizal Mondrizal, Darwison Darwison, Aulia Aulia, Tesya Uldira Septiyeni
{"title":"External Leakage Current Separation to Determine Arrester Condition Due to Contamination","authors":"N. Novizon, Mondrizal Mondrizal, Darwison Darwison, Aulia Aulia, Tesya Uldira Septiyeni","doi":"10.25077/jnte.v12n2.1026.2023","DOIUrl":null,"url":null,"abstract":"Leakage current measurements can be used to determine the aging condition of the ZnO arrester. The leakage current that occurs in the arrester is divided into two, namely external and internal leakage currents. The external leakage current is affected by contamination and the internal leakage current is affected by the aging of the varistor in the arrester. The external and internal leakage currents are measured separately to determine their contribution to the arrester condition. In this study, the effect of salt contamination on the arrester was studied further. The level of contamination used consisted of low, medium and heavy. The obtained leakage current is analyzed using wavelet energy. The results of this study indicate that the wavelet energy of each leakage current is different and can be used as an indicator in further analysis. The conclusion obtained is that the external leakage current is affected by contamination and has a different energy with the internal leakage current due to aging of the varistor arrester components.","PeriodicalId":30660,"journal":{"name":"Jurnal Nasional Teknik Elektro","volume":" ","pages":""},"PeriodicalIF":0.0000,"publicationDate":"2023-06-30","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Jurnal Nasional Teknik Elektro","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.25077/jnte.v12n2.1026.2023","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

Abstract

Leakage current measurements can be used to determine the aging condition of the ZnO arrester. The leakage current that occurs in the arrester is divided into two, namely external and internal leakage currents. The external leakage current is affected by contamination and the internal leakage current is affected by the aging of the varistor in the arrester. The external and internal leakage currents are measured separately to determine their contribution to the arrester condition. In this study, the effect of salt contamination on the arrester was studied further. The level of contamination used consisted of low, medium and heavy. The obtained leakage current is analyzed using wavelet energy. The results of this study indicate that the wavelet energy of each leakage current is different and can be used as an indicator in further analysis. The conclusion obtained is that the external leakage current is affected by contamination and has a different energy with the internal leakage current due to aging of the varistor arrester components.
外部泄漏电流分离以确定因污染引起的避雷器状况
泄漏电流测量可用于确定ZnO避雷器的老化条件。避雷器中发生的泄漏电流分为两部分,即外部泄漏电流和内部泄漏电流。外部泄漏电流受到污染的影响,内部泄漏电流受到避雷器中变阻器老化的影响。分别测量外部和内部泄漏电流,以确定它们对避雷器状况的影响。在本研究中,进一步研究了盐污染对避雷器的影响。所使用的污染水平包括低、中和重。利用小波能量对获得的泄漏电流进行分析。研究结果表明,每个漏电流的小波能量不同,可以作为进一步分析的指标。得出的结论是,由于变阻器避雷器元件的老化,外部泄漏电流受到污染的影响,与内部泄漏电流具有不同的能量。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
20
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"