Sensitivity Analysis of Indoor Air Distribution Performances in an Office Room with Ceiling Cooling and Mechanical Ventilation

IF 1.7 4区 工程技术 Q3 CONSTRUCTION & BUILDING TECHNOLOGY
Xiaozhou Wu, Hao Gao, Diqi Yu, Jiying Liu, Jie Gao, Zhen Tian, Xiangli Li
{"title":"Sensitivity Analysis of Indoor Air Distribution Performances in an Office Room with Ceiling Cooling and Mechanical Ventilation","authors":"Xiaozhou Wu, Hao Gao, Diqi Yu, Jiying Liu, Jie Gao, Zhen Tian, Xiangli Li","doi":"10.1080/23744731.2023.2234251","DOIUrl":null,"url":null,"abstract":"A hybrid system with a ceiling cooling (CC) system and a mechanical ventilation system has been extensively applied in modern office buildings with large sensible cooling loads. Both the chilled ceiling and supply air may greatly influence indoor air distribution in the office room. Therefore in this paper, indoor air distribution performances in a ceiling cooling room with underfloor air distribution (UFAD) or mixing ventilation (MV) were sensitively analyzed by numerical simulation. Indoor air distribution performances, which were evaluated by the heat removal effectiveness, contamination removal effectiveness and air diffusion performance index, were quantitatively analyzed by using the orthogonal experiment method. The results showed that when the supply air temperature was 18 °C-24 °C for CC + UFAD and 16 °C-21 °C for CC + MV, the heat removal effectiveness changed by 0.01 with 1 °C increment of supply air temperature or ceiling surface temperature, and the contamination removal effectiveness increased by 0.001-0.002 with 1 W/m2 increment of external sensible cooling load. Moreover, the air diffusion performance index increased by 0.6%-1.1% with 1 °C increment of supply air temperature, and it decreased by 0.02% with 1 W/m2 increment of internal sensible cooling load. Finally, formulas of heat removal effectiveness, contamination removal effectiveness and air diffusion performance index for CC + UFAD and CC + MV were obtained by fitting, and they may provide guidance for the optimal design and control of a hybrid system with a ceiling cooling system and a mechanical ventilation system.","PeriodicalId":21556,"journal":{"name":"Science and Technology for the Built Environment","volume":null,"pages":null},"PeriodicalIF":1.7000,"publicationDate":"2023-07-11","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Science and Technology for the Built Environment","FirstCategoryId":"5","ListUrlMain":"https://doi.org/10.1080/23744731.2023.2234251","RegionNum":4,"RegionCategory":"工程技术","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q3","JCRName":"CONSTRUCTION & BUILDING TECHNOLOGY","Score":null,"Total":0}
引用次数: 0

Abstract

A hybrid system with a ceiling cooling (CC) system and a mechanical ventilation system has been extensively applied in modern office buildings with large sensible cooling loads. Both the chilled ceiling and supply air may greatly influence indoor air distribution in the office room. Therefore in this paper, indoor air distribution performances in a ceiling cooling room with underfloor air distribution (UFAD) or mixing ventilation (MV) were sensitively analyzed by numerical simulation. Indoor air distribution performances, which were evaluated by the heat removal effectiveness, contamination removal effectiveness and air diffusion performance index, were quantitatively analyzed by using the orthogonal experiment method. The results showed that when the supply air temperature was 18 °C-24 °C for CC + UFAD and 16 °C-21 °C for CC + MV, the heat removal effectiveness changed by 0.01 with 1 °C increment of supply air temperature or ceiling surface temperature, and the contamination removal effectiveness increased by 0.001-0.002 with 1 W/m2 increment of external sensible cooling load. Moreover, the air diffusion performance index increased by 0.6%-1.1% with 1 °C increment of supply air temperature, and it decreased by 0.02% with 1 W/m2 increment of internal sensible cooling load. Finally, formulas of heat removal effectiveness, contamination removal effectiveness and air diffusion performance index for CC + UFAD and CC + MV were obtained by fitting, and they may provide guidance for the optimal design and control of a hybrid system with a ceiling cooling system and a mechanical ventilation system.
吊顶制冷加机械通风办公室内气流组织性能敏感性分析
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
Science and Technology for the Built Environment
Science and Technology for the Built Environment THERMODYNAMICSCONSTRUCTION & BUILDING TECH-CONSTRUCTION & BUILDING TECHNOLOGY
CiteScore
4.30
自引率
5.30%
发文量
78
期刊介绍: Science and Technology for the Built Environment (formerly HVAC&R Research) is ASHRAE’s archival research publication, offering comprehensive reporting of original research in science and technology related to the stationary and mobile built environment, including indoor environmental quality, thermodynamic and energy system dynamics, materials properties, refrigerants, renewable and traditional energy systems and related processes and concepts, integrated built environmental system design approaches and tools, simulation approaches and algorithms, building enclosure assemblies, and systems for minimizing and regulating space heating and cooling modes. The journal features review articles that critically assess existing literature and point out future research directions.
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信